Loading...
HomeMy WebLinkAbout20180208PAC to Staff Attachment Bridger D.2 SSR.pdfGateway West D.2 Project SSR/SSCI Study Final Report Preparedfor:PacifiCorpand Power Engineers Prepared by:Robert D'Aquila General Electric International,Inc. Energy Consulting Group October 24,2017 Gateway West D.2 Project SSR/SSCI Study Forward This project evaluates subsynchronous resonance (SSR)and subsynchronous control interaction (SSCI) issues associated with the Gateway West D.2 project.This report was prepared by General Electric International,Inc.(GEII),acting through its Energy Consulting group,based in Schenectady,New York. Questions and any correspondence concerning this document should be referred to: Robert D'Aquila 1 River Road Building 53,Room 302H Schenectady,New York 12345 Phone:(518)385-0848 E-mail:Robert.Daquila@ge.com Copyright 2017 General Electric Company,U.S.A Gateway West D.2 Project SSR/SSCI Study Legal Notices This report was prepared by General Electric International,Inc.as an account of work sponsored by Power Engineers.General Electric International,Inc.,nor any person acting on their behalf: 1)Makes any warranty or representation,expressed or implied,with respect to the use of any information contained in this report,or that the use of any information,apparatus,method,or process disclosed in the report may not infringe privately owned rights. 2)Assumes any liabilities with respect to the use of or for damage resulting from the use of any information,apparatus,method,or process disclosed in this report. GE Energy Consulting i Gateway West D.2 Project SSR/SSC1 Study CONTENTS 1 EXECUT I VESUMM A RY ................................................................................1-1 2 PROJECTOVERV I EW ...............................................................................2 -1 2.1 Transmission System and Series Capacitor Operation........................................................................2-2 3 BRI DGERSS R..................................................................................................................3 -1 3.1 Br i dgerTors i on a I Modes....................................................................................................................3 -1 3.2 Tra nsm i ss i onCond it i ons ..............................................................................................................................3 -1 3.3 Benchma rk i ng A g a i nstPerv i ousBr i d ge rSSR A n a lys i s .............................................................................3 -3 3.4 SSRSt a b i Ii tyw i thG atew a yD .2 .....................................................................................................................3 -5 3.5 Benchmark System Limiting Conditions and SSR Margin......................................................................3-10 3.6 Possible Modifications to RCSC Switching Scheme.................................................................................3-13 4 SSCI SCREEN I NG .................................................................................................................4-1 4.1 SSCI forG a tew a yD .2..................................................................................................4-1 4.2 SSCI with Full Gateway Project...................................................................................4-5 GE Energy Consulting ,,Gateway West D.2 Project EXECUTlVESUMMARYSSR/SSci Study 1 EXECUTIVE SUMMARY Pacificorp is planning the developmentof Gateway West Segment D.2 by 2020.This project includes a new 500 kV line from Aeolus to Anticline and a new 345 kV line between Bridger and Anticline.The project is intended to deliver wind generation in Eastern Wyomingtowards the west.Power will flow west from Aeolus to Bridger,and across the Bridger 345 kV lines. The three 345 kV transmission lines from the Jim Bridger Plant west to Populus and to Threemile Knoll are series compensated.The series capacitors are needed to maintain stabilityof the Jim Bridger units,particularlywhen the plant is operating at high power output. However,the series capacitors cause subsynchronousresonance (SSR)issues for the Bridger units. The SSR risk is managed using protection and mitigation equipment at the plant as well as an automatic series capacitor switching scheme.The switching scheme inserts the series capacitors based on flow on individual 345 kV lines,outputof individual Bridger units and total plant output.This scheme is successful in large part because the flow on the Bridger 345 kV lines is very closely tied to plant output. AII other things being equal,a large steam turbine generator is least susceptible to SSR when operating at high load.This is due to the high mechanical torsional damping caused by the steam flow.When the Bridger units are operating at high load (i.e.Iowest SSR e×posure),the flow on the 345 kV lines to the west is high and the series capacitors are needed for system stability.The series capacitors can be inserted to maintain system stability without significant SSR risk. As unit load decreases,mechanical torsional damping reducers and the units become more susceptible to SSR.With the low line flow,the series capacitors are not needed to maintain stability.The series capacitors are bypassed to reduce SSR risk without a significant impact on system stability. Althoughthe Gateway D.2 project does not include series compensation,it will affect the SSR condition at Bridger,both directly and indirectly.The new transmission line will change the impedance seen by the Bridge generation.This will shift the e×isting resonances.Additionally, the flow on the Bridger 345 kV line will not be tied directlyto Bridger plant output.The lines could have high flow (and require series capacitors for stability)even when the Bridger units are at low load and most susceptible to SSR. The primary objective of this study is to assess the SSR stability analysis of the Bridger units with Gateway D.2,review of the current series capacitor bypass scheme and determine if the scheme can or should be changed. Results show that Gateway D.2 improves the SSR condition for the Bridger units.With the improved SSR,the following changes to the Remotely Controlled Series capacitor (RCSC)logic may allow for more fle×ible operation of the series capacitors without significantlyincreasing risk to the Bridger units. The current Locally Controlled Series capacitor (LCSC)logic should remain unchanged. GE Energy Consulting copyright ©2017 General Electric International,Inc.(GEII)1-1 ,,Gateway West D.2 Project EXECUTlVESUMMARYSSR/SSci Study ·Retain the existing 135-185MW Iimit on individual unit generation. With respect to the total plant MW Iimit,there are two options to consider: a.Higher SSR Risk Option:Remove the existing total plant MW Iimit.This will increase SSR risk a little above the current risk.With the higher SSR risk,the TSR line/au×iliarytrip function should be enabled.This function is used to trip the source of SSR (RCSC in this case)when torsional oscillations are detected. This reduces the chances of a generator trip. b.Lower SSR Risk Option:Lower the e×isting 1325-1475 MW plant limit to about 650-800 MW.This option will require at least two units to be operating before the RCSC is inserted.Enabling the au× trip function would not be critical,but would reduce risk of generator trips. Add minimum line flow logic to the RCSC banks (if not already part of the RCSC logic). This will only allow the RCSC banks to be switched in when flow is above a minimum level (possibly the same MW Ievel and same contacts as LCSC MW flow contacts).This logic will help to bypass the RCSC upon loss of the Bridger-Anticline line with low Bridger generation. There is existing logic that will bypass the RCSC if the SEDC on any on-line unit is out of service. This logic was disabled for Unit 2 after the blocking filter was installed.With the above changes,this logic should be enabled for all units. The Gateway D.2 project will also introduce the risk of subsynchronouscontrol interaction (SSCl).SSCI is a condition where an electrical system resonance caused by series capacitors can cause wind turbine controlsto be unstable.Wind plants connected directlyto Aeolus 230 kV will have some SSCI risk with the D.2 project,but the risk is low.However,as the Gateway project e×pands to include additional 500 kV lines and series capacitors,the SSCI risk is high. Wind plant owners and developers of future plants in the area should be made aware of the future SSCI risk in order to select appropriate wind turbinesand controls. GE Energy Consulting copyright ©2017 General E ectric Internationa ,Inc.(GEII)1-2 ,,Gateway West D.2 Project Project Overview'SSR/SSCI study 2 PROJECT OVERVIEW Pacificorp is planning the developmentof Gateway West Segment D.2 by 2020.This project includes a new 500 kV line from Aeolus to Anticline and a new 345 kV line between Bridger and Anticline.The first phase of this project does not include series compensation. The project is intended to deliver wind generation in Eastern Wyoming towardsthe west. Power will flow west from Aeolus to Bridger,and across the Bridger 345 kV lines. The three 345 kV transmission lines from the Jim Bridger Plant west to Populus and to Threemile Knoll are series compensated.The series capacitors are needed to maintain stability of the Jim Bridger units,particularly when the plant is operating at high power output.However,the series capacitors cause subsynchronousresonance (SSR)issues for the Bridger units. The SSR risk is managed using protectionand mitigation equipmentat the plant as well as an automatic series capacitor switching scheme.The switching scheme inserts the series capacitors based on flow on individual 345 kV lines,outputof individual Bridger units and total plant output.This scheme is successful in large part because the flow on the Bridger 345 kV lines is very closely tied to plant output. AII other things being equal,a large steam turbine generator is least susceptible to SSR when operating at high load.This is due to the high mechanical torsional damping caused by the steam flow.When the Bridger units are operating at high load (i.e.Iowest SSR e×posure),the flow on the 345 kV lines to the west is high and the series capacitors are needed for system stability.The series capacitors are inserted to maintain system stability without significantSSR risk. As unit load decreases,mechanical torsional damping reducers and the units become more susceptible to SSR.With the low line flow,the series capacitors are not needed to maintain stability.The series capacitors are bypassed to reduce SSR risk without a significantimpact on system stability. Althoughthe Gateway D.2 project does not include series compensation,it will affect the SSR condition at Bridger,both directly and indirectly.The new transmission line will change the impedance seen by the Bridge generation.This will shift the e×isting resonances.Additionally,the flow on the Bridger 345 kV line will not be tied directly to Bridger plant output.The lines could have high flow (and require series capacitors for stability)even when the Bridger units are at low load and most susceptible to SSR. The primary objective of this study is to assess the SSR stability analysis of the Bridger units with Gateway D.2,review of the current series capacitor bypass scheme and determine if the scheme can or should be changed. The Gateway D.2 project may also introduce the risk of subsynchronous control interaction (SSCl).SSCI is a condition where an electrical system resonance caused by series capacitors can cause wind turbine controls to be unstable.This study includes a screening for possible SSCI for wind plants near the Aeolus with the new project.SSCI GE Energy Consulting copyright ©2017 General Electric International Inc.(GEII)2-1 ,,Gateway West D.2 Project Project Overview'SSR/SSci Study screening is presented for the D.2 system as well as for the currently-planned full Gateway system. 2.1 Transmission System and Series capacitor Operation Figure 2-1 is a simplified one-line diagram of the current transmission system west of Bridger (without D.2).This diagram shows the three Bridger 345 kV line with their series capacitors. The series capacitors have been sized and segmented based on SSR constraints of the Bridger units.The segments are inserted and bypassed based on transmission line flow and Bridger unit operation.The locally controlled series capacitors (LCSC)are inserted first,based on line flow (measured at the series capacitor,hence "locally controlled"). The remotelycontrolled series capacitors (RCSC)are switched based individual unit and total Bridger plant generation.They will be inserted after the LCSC are inserted. The following is a description of the series capacitor switching logic,per the PacifiCorp document "East &West of Populus Series Compensation Rev 5.doc×". East of Populus Series Compensation:- The series compensationin the Populusto Bridger #1 &#2 and Three Mile Knoll to Bridger 345 kV lines (#4,#5 &#6)are each split into two segments.The 'L'segment in series capacitors 4,5,6 (see Fig.2)is switched or bypassed by local control and segment 'R'in series capacitors 4,5,6 (See Fig. 2)is switched by remote control signal based on Bridger generation levels.For Populus to Bridger #1 &#2 345 kV lines,respective locally controlled series capacitor is bypassed if the line flow is less than or equal to 260 MW and is inserted if the line flow is more than or equal to 350 MW.For 3 Mile Knoll to Bridger 345 kV line,the respective locally controlled series compensation is bypassed if the line flow is 266 MW or less and is inserted if the line flow is 350 MW or more. The remotely controlled series compensation segment is switched based upon the Jim Bridger's net generation.It is bypassed if the total net Jim Bridger generation is 1325 MW or less and inserted if the 1475MW or more.If any of the Bridger unit is loaded less than 135 MW,the remote series capacitors are also bypassed.If only three Jim Bridger units are online and total net generation is 1475 MW or more,the remote series capacitor is inserted.If 4th UniÍ iS brought online,the remote series capacitors are bypassed until the 4th Unit iS loadedup to 185 MW. GE Energy Consulting copyright ©2017 General Electric Internationa Inc.(GEII)2-2 ,,Gateway West D.2 Project Project Overview'SSR/SSCI Study POPULUS PROJECT SERIES CAPACITOR CONFIGURATION Goshen 3 MileKnoll Kinport 28.5 Ohms 28.5 Ohms 15.9 Ohms L R 3Borah Bridger 5.Ohms POpUIUS 13.96 O1h s Value)/ #2 20 s O #1 L R Remotely Controlled #2 20.59 25.74 #1 Ohms Ohms LEGEND:- WEST OF ExistingPOPULUS New Normal/30Minute Emergency Rating 15.9 Ohms Borah -Populus 345kV Line 1 13.96 Ohms (New #1 Series Compensation @ BorahValue) Ben Lomond 2 15.9 Ohms Borah -Populus 345kV Line #2 Series Compensation @ Borah 3 15.9 Ohms Kinport -Populus 345kV Line Series Compensation @ Kinport 4 20.59 Ohms Populus -Bridger 345kV Line #2 25.74 Ohms Series Compensation @ Populus Terminal 5 20.59 Ohms Populus -Bridger 345kV Line 25.74 Ohms #1 Series Compensation @ Populus 6 28.5 Ohms 3 Mile Knoll -Bridger 345kV Line 28.5 Ohms Series Compensation @ 3 Mile Knoll Figure 2-1 System and Series capacitors West of Bridger (without Gateway D.2) GE Energy Consulting copyright ©2017 General E ectric Internationa nc.(GEII)2-3 ,,Gateway West D.2 Project Bridger SSR'SSR/SSci Study 3 BRlDGER SSR 3.1 Bridger Torsional Modes Measured torsionalfrequencies for the Bridger are listed in Table 3-1.Units 3 and 4 have full GE turbines (HP/IP,LPA,LPB and generator rotor).The original GE HP/IP turbine on Unit 1 has been replaced with a Hitachi HP/IP turbine.This changed the torsional frequencies slightlyfrom Units 3 &4. In 2013,the original GE HP/IP,LPA and LPB turbines on Unit 2 were replaced with Hitachi turbines.This caused a larger shift in torsional frequencies.Without mitigation,Unit 2 with the new Hitachi turbineswould have SSR issues.An SSR blocking filter was installed on the unit at the time of turbine change. Table 3-1 Jim Bridger Units Torsional Modes Mode Unit 1(H-HP/IP,Unit 2 (H)*Unit 3 (GE)Unit 4 (GE) GE LPA &LPB) 1 18.87 18.09 19.11 19.04 2 32.28 29.91 32.51 32.49 3 43.10 36.06 43.28 43.28 *Unit 2 has Hitachi HP/IP,LPA and LPB turbines and an SSR blocking filter Given these torsional frequencies,Units 1,3 &4 assumed identical from an SSR standpoint.The following generation conditions were studied: SSR analysis of Units 1,3 &4: With one,two and three units on line With and without Unit 2 on line SSR analysis of Unit 2: With none,one,two and three other Bridger units on line In total,10 different generation/SSR conditions were evaluated. 3.2 Transmission Conditions SSR analysis was performed for wide range of system conditions,as listed in Table 3-2. Each of these conditions were evaluatedwith the RCSC inserted and bypassed and with the D.2 project in and out of service.They were studied for the ten different generation conditions listed above. GE Energy Consulting copyright ©2017 General Electric International,Inc.(GEII)3-1 ,,Gateway West D.2 Project Bridger SSR'SSR/SSClstudy Table 3-2 Systerr Conditions studied for Bridger SSR Borah StKinportline/caps Pop 1,Pop 2,3MK Line/cap (Borah 1,Borah 2,Kinport)Lines South (Ben Lmn status(1=LCSC+RCSC,2=(1=Scinserted,2=SC :L&2,Terminal,1=line Case LCSC Only,O =line tripped)bypassed,O =line tripped)in,O =line tripped) CO1 L111 X111 S111 CO2 L111 X211 S111 CO3 L111 X221 S111 CO4 L111 X222 S111 CO5 L111 X011 S111 CO6 L111 X021 S111 CO7 L111 X111 SO11 CO8 L111 X111 SO10 C11 L110 X111 S111 C12 L110 X211 S111 C13 L110 X221 S111 C14 L110 X222 S111 C15 L110 X011 S111 C16 L110 X021 S111 C17 L110 X111 SO11 C18 L110 X111 SO10 C21 L112 X111 S111 C22 L112 X211 S111 C23 L112 X221 S111 C24 L112 X222 S111 C25 L112 X011 S111 C26 L112 X021 S111 C27 L112 X111 SO11 C28 L112 X111 SO10 C31 LO11 X111 S111 C32 LO11 X211 S111 C33 LO11 X221 S111 C34 LO11 X222 S111 C35 LO11 X011 S111 C36 LO11 X021 S111 C37 LO11 X111 SO11 C38 LO11 X111 SO10 C41 L211 X111 S111 C42 L211 X211 S111 C43 L211 X221 S111 C44 L211 X222 S111 C45 L211 X011 S111 C46 L211 X021 S111 C47 L211 X111 SO11 C48 L211 X111 SO10 GE Energy Consulting copyright ©2017 General E ectric Internationa ,Inc.(GEII)3-2 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI Study 3.3 BenchmarkingAgainst Pervious Bridger SSR Analysis The last Bridger SSR analysis performed by GE was in 2012,associates with the Populus project and the Unit 2 turbine replacement/SSR blocking filter project.Figure 3-1shows results from the 2012 analysis.This plot shows Bridger damping torque with Units 1,3 and 4 on line and the RCSC inserted. Figure 3-2 shows SSR damping for the same system/Bridgerconditions using the new model supplied by PacifiCorp for this project.However,the line from Bridger to Anticline is open,effectivelyremoving the D.2 project.Results are very close to the 2012 analysis. This new model with the Bridger-Anticline line open can serve as a benchmarkto gauge the impact of the D.2 project. Note that there is a very slight upward shift in the damping torque dips for the current system model.The dips are closer to the 2nd ÍOFSÍOOO TOde and reduce the SSR stability margin by a very slight amount.This is likely due to a small change in series capacitor ohms on the banks west of Bridger. These plots show the Bridger torsional modes as I bars.The top of the I bar represent no-load mechanical damping and the bottom represents full load damping.The mechanical damping is based on measurements without SEDC (supplemental e×citation damping controller).The Bridger SEDC increase mechanical damping by roughly a factor of two for Units 1,3 &4.The increase in damping for Unit 2 with the Hitachi turbinesand SSR damping filter even greater (over 3×).The increased damping from the SEDC is considered margin and is not included in SSR stability studies. GE Energy Consulting copyright ©2017 General E ectric Internationa Inc.(GEII)3-3 ,,Gateway West D.2 Project Bridger SSRO'SSR/SSCI study GE Units -3 Units on line,RCSC Inserted Benchmark w/o Filter 2 1 O -4 -5 -6 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Figure 3-1 Results from 2012 SSR Study Current System w/o D2,RCSC In service 1 -4 -5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Figure 3-2 Results with Current Model,Bridger-Anticline Line Out of Service GE Energy Consulting Copyright ©2017 General Electric international,Inc.(GEll)3-4 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI Study 3.4 SSR Stabilitywith GatewayD.2 This section shows the impact of the D.2 project on Bridger SSR stability using SSR damping torque plots.The plots are grouped as follows: Figure 3-3 Units 1,3&4 with RCSC inserted Figure 3-4 Unit 2 with RCSC inserted Figure 3-5 Units 1,3&4 with RCSC bypassed Figure 3-6 Unit 2 with RCSC bypassed The figures show SSR for the benchmarksystem in the top plot and for the D.2 system in the bottom plot.The I bars for each torsional mode span from no-load to full-load mechanical damping.An additional point is shown on the I bar that represents an estimate of mechanical damping at 25%Ioading,roughly the cut off point for insertion/bypassof the RCSC. Figure 3-3 and Figure 3-4 show a lot of unstable SSR cases with the RCSC inserted,both for the benchmarksystem and the D.2 system.AII the unstable conditions are mitigated by RCSC switching scheme.This is evident in the plots with RCSC bypassed. The Gateway D.2 project improves Bridger SSR for all study conditions.There are still unstable SSR conditions with the RCSC inserted butthe electrical damping is higher than for the benchmark system.Even with the D.2 project,RCSC switching logic will be needed.However,the D.2 project may provide an opportunityto relax some of the RCSC constraints. GE Energy Consulting copyright ©2017 General E ectric Internationa Inc.(GEll)3-5 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study Current System w/o D2,RCSC In service -4 -5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) D2 System,RCSC in service 1 0 4 5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Figure 3-3 Units 1,3 &4 SSR,RCSC Inserted,Benchmark (top)and D.2 (bottom)systems GE Energy consulting Copyright©2017 General Electric international,Inc.(GEll)3-6 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study Unit 2,w/o D2,RCSC Inserted 1 E4 5 6 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Unit 2,D2 in service,RSCS in service E4 5 6 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-4 Unit 2 SSR,RCSC Inserted,Benchmark (top)and D.2 (bottom)Systems GE Energy Consulting Copyright ©2017 General Electric international,Inc.(GEll)3-7 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study Current System w/o D2,RCSC o/s 1 0 4 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) D2 System with RCSC o/s 03 4 5 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-5 Units 1,3 &4 SSR,RCSC Bypassed,Benchmark (top)and D.2 (bottom)systems GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)3-8 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study Unit 2,w/o D2,RCSC Bypassed 1 ' 2 E4 5 6 7 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,D2 In,RCSC Bypassed 2 1 E4 5 6 7 8 10 15 20 25 30 35 40 45 50 Rotor frequency (Hz) Figure 3-6 Unit 2 SSR,RCSC Bypassed,Benchmark (top)and D.2 (bottom)Systems GE Energy Consulting Copyright©2017 General Electric international,Inc.(GEll)3-9 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI Study 3.5 Benchmark System LimitingConditions and SSR Margin For the benchmarksystem with the existing RCSC scheme,the banks would only be in service with three or four Bridger units on line.The minimum load per individual unit (above 185 MW to insert,below 135 MW to bypass)and total plant load limit (above 1475 MW to insert,below 1325 MW to bypass)ensure all conditions are stable.Limiting conditions are shown in the figures below.The conditions shown are Three units on line,2 at full load (~525MW),one at ~275 MW,1325 MW total generation,RCSC inserted:Damping torque plots with three units on line and the RCSC inserted are shown in Figure 3-7.The top plot shows SSR for the units with GE turbines (1,3 &4)and the bottom plot shows SSR for Units 2 with the SSR blocking filter.Damping for the full set of contingencies is shown. The red bo×es on the mode 2 I bar appro×imate the mechanical damping at 275 MW. AII cases are SSR stable.There are some system conditions that show very little margin, but they are stable.These plots do not account for the added margin of the SEDC and the shared damping between units (the unit at 275 MW will appear to have higher damping,due to the higher damping of the units operating at full load),so the actual margin is higher. Four units on line,3 at 400 MW,one at 150 MW:Figure 3-8 shows damping torque plots for all conditions with four Bridger units on line.The red boxes appro×imate the mechanical damping 150 MW.AII cases are SSR stable with margin. These two e×amples serve as a reference to the current SSR stability margin. GE Energy Consulting copyright ©2017 General E ectric Internationa Inc.(GEII)3-10 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study Current System w/o D2,RCSC In service,3 units total 1 4 5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,w/o D2,RCSC Inserted -Unit 2 with 2 other units on line (3 units total) CLE4 6 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-7 Benchmark System (w/o D.2)with Three Bridger Units On line.SSR for Untis 1, 3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright ©2017 General Electric international,Inc.(GEll)3-11 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI Study Current System w/o D2,RCSC In service,4 units total 1 E 4 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,w/o D2,RCSC Inserted -Unit 2 with 3 other units on line (4 units total) 1 0 E4 O 5 6 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-8 Benchmark System (w/o D.2)with Four Bridger Units On line.SSR for Untis 1, 3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)3-12 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study 3.6 Possible Modifications to RCSC SwitchingScheme Given that the Gateway D.2 project will improve the Bridger SSR condition,there may opportunityto rela×some of the RCSC constraints.The plots below show operation with 1,2,3 &4 units on line,all with RCSC inserted.The appro×imate mechanical damping at 150 MW is indicated by a black dash on the |Bar.The minimum load level for mode 2 SSR stability is indicate with a red bo×.Each set of plots is described below. Figure 3-9 shows SSR damping with one unit on line (Ul,3 or 4 on top plot,U2 on bottom plot).Ul,3 &4 would be stable at the minimum RCSC load leve.U2 would only be stable at loading above about 300 to 400 MW.The limiting conditions for U2 are loss of one of the Bridger-west 345 kV lines.Under normal transmission conditions U2 would be stable at the minimum RCSC load level. Figure 3-10 shows SSR damping with two units on line (Ul,3 &4 on top plot,U2 on bottom plot).The units would be SSR stable at roughly 200 MW generation,just above the current RCSC level. Figure 3-11 shows SSR damping with three units on line (Ul,3 &4 on top plot,U2 on bottom plot).Figure 3-12 shows SSR damping with four units on line (Ul,3 &4 on top plot,U2 on bottom plot).With three or four units on line,the units would be SSR stable with all operating at or above the current RCSC level. The limiting conditions for SSR tend to be loss of one of the Bridger-west 345 kV lines or bypassing of the west of Populus series capacitors banks.Figure 3-13 shows SSR damping for the normal system condition (n-0)for all combinationsof units on line (1,2, 3 &4 units on line).Under normal transmission conditions,the units would be SSR stable when operating above the RCSC limit. With the improved SSR condition,the following changes to the RCSC logic may allow for more flexible operation of the series capacitors without significantly increasing risk to the Bridger units.Note that the current LCSC logic is assumed to remain unchanged. Retain the existing 135-185MW Iimit on individual unit generation. With respect to the total plant MW Iimit,there are two options to consider: a.Higher SSR Risk Option:Remove the e×isting total plant MW Iimit.This will increase SSR risk a little above the current risk.With the higher SSR risk,the TSR line/auxiliarytrip function should be enabled.This function is used to trip the source of SSR (RCSC in this case)when torsional oscillations are detected.This reduces the chances of a generatortrip. b.Lower SSR Risk Option:Lower the e×isting 1325-1475 MW plant limit to about 650-800 MW.This option will require at least two units to be operating before the RCSC is inserted.Enabling the au× trip function would not be critical,but would reduce risk of generatortrips. Add minimum line flow logic to the RCSC banks (if not already part of the RCSC logic).This will only allow the RCSC banks to be switched in when flow is above a minimum level (possibly the same MW Ievel and same contacts as LCSC MW GE Energy Consulting copyright ©2017 General Electric International Inc.(GEII)3-13 Gateway West D.2 Project Bridger SSRSSR/SSCI Study flow contacts).This logic will help to bypass the RCSC upon loss of the Bridger- Anticline line with low Bridger generation. There is e×isting logic that will bypass the RCSC if the SEDC on any on-line unit is out of service.This logic was disabled for Unit 2 after the blocking filter was installed. With the above changes,this logic should be enabled for all units. GE Energy Consulting Copyright ©2017 General E ectric Internationa ,Inc.(GEll)3-14 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI Study D2 System,RCSC in service,1 unit on line (U1,3 or 4) 1 0 1 4 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,D2 in service,RSCS in service with no other units on line E4 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-9 D.2 System with One Bridger Unit On line.SSR for Untis 1,3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)3-15 ,,Gateway West D.2 Project Bridger SSRO'SSR/SSCI study D2 System,RCSC in service,2 units on line 1 4 5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,D2 in service,RSCS in service with 10ther unit on line 1 E4 6 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-10 D.2 System with Two Bridger Unit On line.SSR for Untis 1,3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)3-16 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI study D2 System,RCSC in service,3 units on line 01 03 4 5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,D2 in service,RSCS in service with 2 other units on line 1 E4 5 6 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-11 D.2 System with Three Bridger Unit On line.SSR for Untis 1,3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)3-17 ,,Gateway West D.2 Project Bridger SSRO'SSR/SSCI Study D2 System,RCSC in service,4 units on line 4 5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,D2 in service,RSCS in service with 3 other units on line 1 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-12 D.2 System with Four Bridger Unit On line.SSR for Untis 1,3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)3-18 ,,Gateway West D.2 Project Bridger SSR'SSR/SSCI StudyO D2 System,RCSC in service,All Generation Conditions,Base System 4 5 10 15 20 25 30 35 40 45 50 Rotor Frequency (Hz) Unit 2,D2 in service,RSCS in service,All Generating conditions,Base System 1 0 E4 6 7 10 15 20 25 30 35 40 45 50 Frequency (Hz) Figure 3-13 D.2 System with 1,2,3&4 Bridger Units On line,Base System (n-0)SSR for Untis 1,3&4 (top)and Unit 2 (bottom) GE Energy Consulting Copyright©2017 General Electric International Inc.(GEll)3-19 ,,Gateway West D.2 Project SSCl Screening'SSR/SSci study 4 SSCI SCREENING SubsynchronousControl Interaction (SSci)is a condition where an electrical system resonance caused by series capacitors can cause wind turbine controlsto be unstable. SSCI screening is performed using impedance scan techniques.This typically involves calculatingthe impedance looking into the grid from the he wind plant interconnection transformer (POl bus).The impedance of the wind plant (including POl transformer, collector system and effective impedance of the wind turbinesand controls)is added in series to the system impedance. The impedance is calculated over a range of frequency,typically from 5 to 55 Hz.The scans are performed for a range of system conditions,including different synchronous generation dispatches and transmission outages.The impedance scans are evaluated for unstable or lightlydamped electrical system resonances which flag possible unstable SSCI conditions.These conditions would be reviewed with the wind turbine vendor and possibly require electro-magnetictransient (e.g.PSCAD,ATP or EMTP)analysis. A brief SSCI screening analysis has been performed for the D.2 system and for the full Gateway system.The analysis only considers the system impedance,not the wind plant impedance.Results are presented in the following sections 4.1 SSCI for GatewayD.2 Since the Gateway West line will not be series compensated in the D.2 phase,any electrical system resonances and possible SSCI conditions would be caused by the series capacitors on the 345 kV lines west of Bridger.Scans were first run looking into the Aeolus 230 kV bus with all 230 kV lines disconnected.This puts the Aeolus 230 kV bus radial to Bridger and gives a screen of electrical resonances that wind plants could be e×posed to.The wind plants would see the impedance from the collector system to Aeolus 230 kV and the effective impedance of the wind turbine and it controlsadded to the Aeolus impedance. The analysis was performed with none,one,two,three and four units on line.Since Bridger 2 has an SSR blocking filter,analysis with one unit was performed with U1 only and with U2 only.Figure 4-1shows a plot of the resistance and reactance looking into Aeolus 230 kV for each generation scenario. The resonance caused by the series capacitors is seen as reversals in reactance and sharp spikes in resistance.Concerning conditions for SSCI are when the reactance dips from positive to negative and back to positive.The frequencywhere reactance crosses from negative to positive is the resonant frequency. The resistance at that point gives an indication of the stability of the interaction.A low or negative resistance raises a flag for possible instabilities.While the system resistance is positive for all test conditions,it is possible that the wind plant can add negative effective resistance,due to the wind turbine and controls.Therefore,this analysis considers any condition with a zero-crossing reactance a possible SSCI risk. GE Energy Consulting copyright ©2017 General Electric International Inc.(GEII)4-1 ,,Gateway West D.2 Project SSCl Screening'SSR/SSCI Study In this case,there is one study condition with a possible SSCI risk.When all Bridger units are off line there is a resonance at 25 Hz (orange reactance trace crosses from negative to positive). The supplied data set shows a wind plant at Q0706_POI 230 kv,connected radially to the Aeolus 230 kv).This plant would have the lease numberout outages to make it radial to Aeolus 230 kV vs.Other wind plants in Eastern Wyoming.Impedance scans were performed looking into the POl bus for the base (n-0)condition and three outages: Aeolus-Freezout line open,Aeolus-Shirly lines open and both set of lines out making the plant radial to Aeolus.Analysis was performed with no Bridger units on line.Plots of resistance and reactance are shown in Figure 4-2. The radial condition (green reactance trace)has an impedance similar to that looking into Aeolus 230 kv,but with the added impedance of the line from Q0706 to Aeolus.This shifts the resonance to 24 Hz and raises the reactance to the point where is just slightly positive over the entire frequencyrange.While technicallynot an SSCI risk,SSCI should still be considered for the Q0706 plant. Other plants further from Aeolus would likely show even lower SSCI risk,due to the higher impedance and more intermediate lines between those plants and Aeolus. This analysis shows that with the Gateway D.2 project,wind plants connecting near Aeolus have low (but not zero)SSCI risk.The wind plants would have to be radial to Aeolus and all Bridger generation would have to be off line to be at risk.New and existing plant owners should be made aware of this risk. GE Energy Consulting copyright ©2017 General E ectric Internationa Inc.(GEII)4-2 Gateway West D.2 Project .SSCl ScreeningSSR/SSCI study 0.06 0.05 -No BridgerUnitsR -1Bridger(1,3or4)R -2 Bridger Units R 0.04 -3 Bridger Units R -4 Bridger Units R -1BridgerUnit(U2)R c 0.03 0.02 0.01 0 5 10 15 20 25 30 35 40 45 50 55 Electricial Frequency (hz) 0.08 0.07 -NoBridgerUnitsX 1Bridger(1,30r4)X 0.06 -2 Bridger Units X -3 Bridger Units X -4 Bridger Units X 0.05 -1 Bridser unit (u2)x 0.04 0.03 0.02 0.01 0 5 10 15 20 25 30 35 40 45 50 55 -0.01 Electricial Frequency (hz) Figure 4-1 R (top)and X (bottom)Looking into Aolus 230 kV Bus with 0,1,2,3 &4 Bridger Units on Line (230 kV lines from Aolus disconnected) GE Energy Consulting Copyright©2017 General Electric international,Inc.(GEll)4-3 Gateway West D.2 Project .SSCl ScreeningSSR/SSCI study 0.06 Base(n-0)R 0.05 -Radial to Bridger R -Trip Freezout Lines R -Trip Shirly Lines R 0.04 c 0.03 0.02 0.01 0 5 10 15 20 25 30 35 40 45 50 55 Electricial Frequency (hz) 0.08 Base (n 0)X0.07 Radial to Bridger X -Trip Freezout Lines X 0.06 -TripShirlyLinesX 0.02 0.01 , O 5 10 15 20 25 30 35 40 45 50 55 Electricial Frequency (hz) Figure 4-2 R (top)and X (bottom)Looking into Q0706 POI 230 kV Bus with no Bridger Units on Line,Base System and Three Outages GE Energy Consulting Copyright©2017 General Electric international,Inc.(GEll)4-4 ,,Gateway West D.2 Project SSCl Screening'SSR/SSCI Study 4.2 SSCI with Full GatewayProject SSCI was performed on a system modeling the final Gateway project as it is currently planned.The intent here is to identify possible SSCI conditions in future.This will allow wind plant developers to be aware of possible SSTI and select appropriate technology to avoid issues in the future. The full Gateway system model provided includes Gateway West and South 500 kV lines with series compensation.The Aeolus 230 kV station has a wind plant (Q707)connected through 230/34.5 kV POl transformer.The Q0706 wind plant is connected to Aeolus through a 230 kV line (same as in the D.2 model). Since there is a plant connected directlyto the Aeolus 230 kV bus,all impedance scans are performed looking into that bus.Scans were performed for the following outage conditions: 1.Base System (n-0) 2.Outage of two Aeolus-Sherly 230 kV lines 3.Outage of Aeolus-Freezout 230 kV line 4.Outage of Aeolus-Windstar230 kV line 5.Outage of Aeolus-Freezout and Aeolus-Windstar230 kV lines 6.AII 230 kV line out,Aeolus 230 radial to 500 kV Gateway lines Analysis was performed with all Bridger units off line and all Bridger units on line.The wind plants and SVC connected to Aeolus were disconnected.Figure 4-3 shows a plot of the reactance looking into Aeolus 230 kV for the conditions listed above (the radial condition #6 is not included in these plots).The upper set of plots has all Bridger units off line and the lower plot has all four Bridger units on line.There are several resonance points for the base (n-0)system.These become deeper with more lines out of service. The resonances are in the 30hz to 37Hz range. Figure 4-4 shows the reactance for radial condition (#6)with no Bridger generation on line.There are several sharp resonance conditions that are SSCI concerns. This analysis confirmsthat wind plants near Aeolus will have a significantSSCI risk when the full Gateway 500 kV project is built.New and existing wind plant developers should be made aware of the SSCI risk. GE Energy Consulting copyright ©2017 General E ectric Internationa Inc.(GEll)4-5 Gateway West D.2 Project .SSCl ScreeningSSR/SSCI study 0.04 -BaseX 0.03 ShidyLinesOutX Freezout&WindstarX -FreezoutX 0.02 --WindstarX 0.01 0 5 10 15 20 25 3 35 40 45 50 55 -0.01 -0.02 -0.03 Electricial Frequency (hz) 0.04 -BaseX 0.03 ShirlyLinesOutX Freezout&WindstarX -FreezoutX 0.02 -windstarx 0.01 0 5 10 15 20 25 35 40 45 50 55 -0.01 -0.02 -0.03 Electricial Frequency (hz) Figure 4-3 Aolus 230 kV Reactance for Conditions 1through 5,No Bridger Units On Line (top)and Four Bridger Units On Line (bottom) GE Energy Consulting Copyright©2017 General Electric International,Inc.(GEll)4-6 ,,Gateway West D.2 Project SSCl Screening'SSR/SSCI Study 0.2 0.15 Radial X 0.1 0.05 co 5 10152025303540455055 -0.05 -0.1 -0.15 -0.2 Electricial Frequency (hz) Figure 4-4 Aolus 230 kV Reactance forRadial Condition (#6),No Bridger Units On Line GE Energy Consulting Copyright©2017 General Electric Internationa[Inc.(GEll)4-7