HomeMy WebLinkAbout20171218PAC to Staff Attachment Utah_DPU 10.11e.pdfFrom:Wilson,Jason T. To:Smith,Brandon Cc:Hall,William (NTO);Ouist,Craiq;Kim,Seonq Tae;Hagen.Dave;Perez,Luis;Stratton,Greq;Leistner,Steven; Patzkowski,Milton Subject:Huntington LAPS Decommissioning Date:Wednesday,May 20,2015 10:25:01 AM Attachments:Summer2015 TOT2B-2C SOL Study Report-v2.docx Brandon, The Huntington LAPS can be decommissioned following completion of the Sigurd to Red Butte 345 kV line.The scheme was not considered in any contingencies in the latest 2B/2C SOL study report, and system operating limits were determined without the RAS in-service.Please refer to the page 6 of the attached SOL report for language indicating that the scheme was not considered in the study. No further study is required to remove the scheme from service.Note,this SOL study was presented to and approved by RMOSG on April 2,2015. Decommissioning of the Huntington LAPS was approved by the WECC RASRS on April 8,2015. Please refer to the excerpt from the draft meeting minutes below. Huntington LAPS Decommissioning The primary function was to enhance the simultaneous transfer capability on TOT2B1/TOT2Cby initiating generator tripping actions.The scheme is limited as the lines have not been operated above the arming thresholds historically.PacifiCorp plans to decommission the scheme in June 2015 following completion of the Sigurd-Red Butte 345-kV line. On a motion bv Mr.Barone and seconded bv Mr.Ham.the RASRS approvedremoval of the Huntington RAS by consensus. Please let me know if you need any further information. Thanks, Jason Jason Wilson,PE Senior Transmission Planner PacifiCorp Main Grid Planning Phone:(801)220-4056 Email:iason.t.wilson©oacificoro.com