HomeMy WebLinkAbout20190924Avista to Staff Ltr-Areva-070402.TIF04/04/2007 14:24 FAX 509 495 4796 AVISTA GEN & PRODUCTION
001 001
Customer: Avista
Object: Coyote Spring Transformer
Attn: Mike Gonella
Dear Mike
AREVA
Monday, 2 April 2007
Please be advised that we have completed the analysis of the gas data from the serveron on the
transformer in your Coyote Spring plant.
Acording to our expert in Paris, the detection of Acetylene gases may reflect an arcing into the oil of
the transformer. This may be at an early stage and could develop into a more critical issue should
this transformer be kept on line; accordingly, we support your idea to immediately take the
transformer off-line and replacing it, in the interim, with your Siemens back-up unit so that additional
tests may be carried out.
Regarding the transient monitoring device that is on our transformer, our Turkish factory will
arrange to send us the key for the control box. If you agree, we can send someone to the site to
confirm whether data was recorded. In such case, we could assist you by sending it to our R&D
center for analysis. We may also wish to have a representative of AREVA T&D INC. present for
any physical examination, investigation or analysis of the transformer; thus, we ask that you provide
us with the operative dates and times for all such activities.
You should be aware that AREVA T&D Inc.'s willingness to assist you at this stage and/or
participate in any examination, investigation or analysis of the subject transformer, shall not be
construed in any way whatsoever as an admission of liability or responsibility with respect to the
current transformer situation. Furthermore, AREVA T&D Inc.'s suggestions, if any, regarding
potential sources or remedial solutions are advisory only. AREVA T&D Inc. hereby disclaims any
liability relative to any such suggestions or information as may be communicated to AVISTA.
AVISTA shall be solely responsible for any action taken on the basis of information provided by
AREVA T&D Inc.
In view of the foregoing action plan, please confirm that we will be proceeding as described above,
and also including the collection of transient data by an AREVA T&D INC. representative and
participation in the examination, investigation or analysis or the affected transformer.
With best regards
Olivier Lejay
Tendering Manager — Power Transformers
voice: 724-483-7891
fax: 724-483-7771
e-mail: olivier.lejay@areva-td.com
T&D
One Power Lane — Charleroi, PA 15022 — Tel.: 724-483-7308 — Fax : 724-483-7771