HomeMy WebLinkAboutAmeriGas 260916 AmeriGas NFPA 58 IPUC Pipeline Safety Inspection
Inspector(s): GaW, Brooks Date(s): 260916
Company/Owner: AmeriGas Propane Unit/OPID: 32013
Standard: ® Training: ❑ TIMP/DIMP: ❑ OQ: ❑
Incident: ❑ Damage Prevention: ❑ Drug& Alcohol: ❑ Inspection Days: 1.0
Inspection Summary
2026 AmeriGas—NFPA 58
September 16, 2026: (1.0 Standard) (0.5 Brooks) (0.5 Galli)
Inspectors Galli and Brooks reviewed AmeriGas's safety and training policies against the IA question set
for compliance with applicable regulations regarding NFPA 58 standards. Wrote IPUC Form 1 and sent
Post-Inspection Written Preliminary Findings to Chad Krouse, Compliance Manager.
Discrepancies:
6.29.4.3 Emergency controls shall be conspicuously marked, and the controls shall be located so as to be
readily accessible in emergencies.
Key Valve Procedure (Page 2 of 3) - Underground valves must have a unique valve number in the valve
box to ensure operation of the proper valve during emergencies or regular maintenance.
None of the emergency valves had unique identifiers in the valve box per the Key Valve procedure in the
AmeriGas Operations and Maintenance Manual. Additionally, NFPA 6.29.4.3 broadly references
emergency controls and the Key Valve procedure limits the unique identification to only underground
valves. Staff recommends the Key Valve procedure be updated to match NFPA standards.
Corrective Action Required: ® Yes ❑ No Compliance Letter#: NOPV AG202601
Lead Inspector: GaW Date: Reviewer: Brooks Date:
260917
Signature: Signature: a.L i0 a 6
IPUC Form 1 Rev. 12/08/2025