HomeMy WebLinkAboutAmeriGas 260914-17 AmeriGas Propane Tamarack Field Inspection IPUC Pipeline Safety Inspection
Inspector(s): Galli, Brooks Date(s): 260914, 2&69 9-_4
Company/Owner: AmeriGas Propane Unit/OPID: 32013
Standard: ® Training: ❑ TIMP/DIMP: ❑ OQ: ❑
Incident: ❑ Damage Prevention: ❑ Drug & Alcohol: ❑ Inspection Days: 1.0
Inspection Summary
2026 AmeriGas Propane—Tamarack Field Inspection
Audit consisted of IPUC inspectors Galli and Brooks inspecting field installed equipment for the
AmeriGas Tamarack inspection unit. The PHMSA IA question set was used as a guide throughout the
audit to ensure all areas were completed.
September 14,2026: (0.5 Standard) (Galli 0.25) (Brooks 0.25)
Inspectors Galli and Brooks traveled to Tamarack Resort and met with AmeriGas Propane company
representatives at the vaporizer site for a briefing and began the field audit. (1)propane truck transfer site,
(1)underground propane container, (2) vaporizers, (1) regulator station were inspected for regulator lock-
up, general condition of the station including pipe-to-soil wrap and cathodic protection, (9) control valves
and pipeline markers.
September 17,2026: (0.5 Standard) (Galli 0.5)
Completed and attached audit forms: PHMSA IA question set with OQ Protocol 9, IPUC Form 1, Post-
Inspection Preliminary Written Findings and attached inspection documents.
Discrepancies:
1. Pipeline markers need to include a phone number consistent with 192.707(d).
2. The multimeter used during the field inspection to verify adequate cathodic protection was not
calibrated in accordance with the manufacturer's recommendations. The accuracy and reliability of
the measurements could not be verified, rendering the results invalid.
3. Field inspections and Annual Maintenance were not performed using calibrated pressure gauges.
The accuracy and reliability of pressure measurements could not be validated.
Corrective Action Required: ® Yes ❑ No Compliance Letter#: NOPV AG202601
Lead Inspector: Galli Date: Reviewer: Brooks Date:
260917 ��/oo�
Signature: � Signature:
IPUC Form 1 Rev. 12/08/2025