HomeMy WebLinkAboutIntermountain Gas 260908-09 Boise Safety IPUC Pipeline Safety Inspection
Inspector(s): Perkins, Gatti, Green Date(s): 260908-09
Company/Owner: Intermountain Gas Company Unit/OPID: 08160
(IGC)
Standard: ® Training: ❑ TIMP/DIMP: ❑ OQ: ❑
Incident: ❑ Damage Prevention: ❑ Drug & Alcohol: ❑ Inspection Days: 4.0
Inspection Summary
September 8-9, 2026: (4.0)
Observed the integrity test site located at 6455 S. Eisenman Rd, Boise, Idaho, following identification of a
potential coating anomaly through a Direct Current Voltage Gradient(DCVG) inspection. Contractor
excavated the site using a Vac truck and installed a shore box. It was determined that a rock impingement
damaged the protective coating in 3 different locations. IGC corrosion techs conducted a soil resistivity
test, circled all anomalies, conducted a coating thickness test, removed coating and cleaned up the pipe.
To assess the integrity of the affected area, IGC engaged Acuren to perform non-destructive testing (NDT)
and a comprehensive integrity inspection over a segment approximately 3 feet in length.
Corrective Action Required: ❑ Yes ® No Compliance Letter#: NA
Lead Inspector: Perkins Date: Reviewer: Brooks Date:
a(�0909
Signature: 260909/ � Signature:
IPUC Form I Rev. 12/08/2025