Loading...
HomeMy WebLinkAboutAvista 260519 Moscow Safety Inspection IPUC Pipeline Safety Inspection Inspector(s): Galli, Green Date(s): 260518-260521 Company/Owner: Avista Utilities Unit/OPID: 31232 Standard: ® Training: ❑ TIMP/DIMP: ❑ OQ: ❑ Incident: ❑ Damage Prevention: ❑ Drug& Alcohol: ❑ Inspection Days: 7.0 Inspection Summary Avista Moscow Field Audit May 19-20,2026: (4.0 Standard) (Galli 2.0) (Green 2.0) Met with Avista company representatives in the Pullman, Washington district office for a briefing, reviewed welding records, past year work orders, verified calibrations of inspection equipment and began the field audit. Twenty-two regulator stations were inspected for relief operation, regulator lock-up, general condition of the station including pipe-to-soil wrap, and cathodic protection. Three rectifiers, six carrier-to-casings, thirty-one control valves and one high-pressure service set were also inspected. May 21, 2026: (2.0 Standard) (Galli 1.0) (Green 1.0) IPUC inspector Galli and Green traveled back to Boise, Idaho. May 26, 2026: (1.0 Standard) (Galli 1.0) Wrote inspection report, completed audit forms: PHMSA IA question set with OQ protocol 9, IPUC Form 1, Post-Inspection Preliminary Written Findings, attached inspection documents and wrote NOPV A202602. Discrepancies: • The inlet valve at Regulator Station 3760 was not listed in Maximo, no annual inspection data. • Soil erosion has occurred around Regulator Station 369. Recommend adding topsoil and/or gravel to restore proper grade and prevent further washout. • The pipe-to-soil interface at HPSS 3089 was damaged, exposing bare steel. The regulator technician removed the damaged wrap and painted the exposed steel on-site. Wax wrap was applied the following day. Corrective Action Required: ® Yes ❑ No Compliance Letter#: A202602 Lead Inspector: Galli Date: Reviewer: Brooks Date: 260528 Signature: Signature: IPUC Form 1 Rev. 12/08/2025