Last Updated: 8/5/2016
2016 TRANSMISSION PROJECTS SUMMARY
Spokane/Davenport/Othello/Colville
(1) Benton - OthelloSS 115kV Transmission Line: Line Upgrade/Rebuild (ER 2457, BI FT130)
Region: Othello (Manager: Ian Eccles) Reconductors and Rebuilds
Designer/Engineer: Bryan Hyde (x2990)
Area Engineer: Tim Figart
Area RBM: Paul Kimmell
Area RE Representative: Randy Daniels
Construction Window: 2015-2016 and 2016-2017 (Winter)
Construction Forces: Contract
Scope:
2015-2016 and 2016-2017 construction (phases 2 and 3) of 2014-2016 project.
This project is intended to upgrade/rebuild Avista’s 26 mile section of the Benton – Othello Switching Station
115kV Transmission Line with conductor capable of a continuous 120 MVA loading (205 MVA limit capacity).
The reconductor/rebuild will include a crossing of the Columbia River. Planning studies show overloading of the
existing transmission lines thermal rating during specific outages in Grant PUD's Transmission System.
The Construction window for phases 2 and 3 will straddle fiscal years 2015-2016 and 2016-2017, with
construction tentatively scheduled for December 2015 through March of 2016, and November 2016 through
March 2017. A significant portion of phases 2 and 3 are on federally owned property, complicating the permitting
process.
(2) Devils Gap - Lind 115kV Transmission Line: Line Rebuild (ER 2564, BI ST302)
Region: Davenport (Manager: Cesar Godinez) Reconductors and Rebuilds
Designer/Engineer: CAI Consultants with Aaron Tremayne as Project Manager (x2178)
Area Engineer: Tim Figart
Area RBM: Steve Trabun/Paul Kimmell
Area RE Representative: Larissa Pruitt
Construction Window: 2014-2017 (Spring/Fall)
Construction Forces: Spokane Operations/Contract
Scope:
2016: Phase 3 design and procurement.
2017: Phase 3 construction.
This project is intended to rebuild 65% of the Devil's Gap to Lind 115kV line with new steel structures. Replace
all larch on the line, and those cedar structures needing replacement or repair based on condition assessment from
the last inspection in 2009. While no load growth or planning projects are expected in the near future, this line
requires extensive repair and replacement work. Over half of the line's structures are larch wood material, now
at the end of its expected service life. Also, the area subject to recurring ice loading failures will be addressed.
2016-2017 work will address the area from a point south of Sprague to a point near Reardan.
Staff_PR_102 Attachment C Page 1 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(3) Devils Gap - Stratford 115kV: LiDAR Mitigation and Minor Rebuild (ER 2581, BI BT308)
Region: Spokane/Othello (Managers: Eric Rosentrater and Ian Eccles) NERC Mitigation/Asset Management
Designer/Engineer: Dan Adams (x2455)
Area Engineer: Tim Figart
Area RBM: Paul Kimmell
Area RE Representative: Randy Daniels
Construction Window: August-November
Construction Forces: Contract
Scope:
2016 construction (phase 2) of 2015-2017 project.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL) and Contractual requirements.
(4) OthelloSS - Warden #1 & #2 115kV: LiDAR Mitigation and Minor Rebuild (ER 2579, BI WT301)
Region: Othello (Manager: Ian Eccles) NERC Mitigation/Asset Management
Designer/Engineer: Dan Adams (x2455)
Area Engineer: Tim Figart
Area RBM: Paul Kimmell
Area RE Representative: Randy Daniels
Construction Window: April
Construction Forces: Othello Operations
Scope:
2016 construction (phase 2) of 2015-2016 project.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL) and Contractual requirements.
(8) Garden Springs - Sunset 115kV Transmission Line: Line Rebuild (ER 2310, BI ST305)
Region: Spokane (Manager: Eric Rosentrater) Reconductors and Rebuilds
Designer/Engineer: CAI Consultants with Aaron Tremayne as Project Manager (x2178)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Dave Chambers
Construction Window: 2017 (Spring/Fall)
Construction Forces: Spokane Operations/Contract
Scope:
2016: Design and procurement phase.
2017: Construction phase.
This project is intended to Rebuild/Reconductor the 2-mile 115kV transmission line section between the future
Garden Springs Substation (present S. Fairchild Tap switching location) and the Sunset Substation. The project
will utilize new steel structures capable of an OPGW overbuild and a 795 ACSS “Drake” conductor capable of
314 MVA capacity at 200 degrees C.
Staff_PR_102 Attachment C Page 2 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(9) 9th & Central – Sunset 115kV Transmission Line: Line Upgrade/Rebuild (ER 2557, BI ST503)
Region: Spokane (Manager: Eric Rosentrater) Reconductors and Rebuilds
Designer/Engineer: Bryan Hyde (x2990)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Dave Chambers
Construction Window: 2016
Construction Forces: Spokane Operations/Contract
Scope:
2016 construction phase of project.
This project is intended to upgrade/rebuild a 4.25 mile portion of the 9th & Central-Sunset 115kV Transmission
Line Southeast Substation and the Glenrose Tap. This existing 250Cu 19 Strand conductor section will be
upgraded with new steel structures capable of an OPGW overbuild and a 795 ACSS “Drake” conductor capable
of 314 MVA capacity at 200 degrees C. Additionally, Minor rebuild and LiDAR Line Rating Mitigation work
will be performed at various locations between 9th & Central and Sunset Substations.
Future project phases will address rebuilding of the 2.75 mile 250Cu 19 Strand conductor section adjacent to
Sunset Substation.
(10) Beacon - Boulder #2 115kV Transmission Line: Line Upgrade/Rebuild (ER 2474, BI ST101)
Region: Spokane (Manager: Eric Rosentrater) Spokane Valley Transmission Reinforcement
Designer/Engineer: Damon Fisher (x2540)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Randy Myhre
Construction Window: 2016-2017
Construction Forces: Spokane/Contract
Scope:
Phase 1: 2016 construction phase of project.
Phase 2: 2017 construction phase of project.
This project is intended to upgrade/rebuild a 7-mile portion of the Beacon-Boulder #2 115kV Transmission Line
between Beacon and Irvin. The existing 556 AAC conductor will be upgraded with new steel structures capable
of an OPGW overbuild and a 795 ACSS “Drake” conductor capable of 314 MVA capacity at 200 degrees C.
Phase 1 work will address the 2-mile line section between Irvin and Millwood Substations. Phase 2 work will
address the 5-mile line section between Beacon and Millwood Substations.
(11) Beacon - Ross Park 115kV: Minor Rebuild (ER 2057, BI AMT12)
Region: Spokane (Manager: Eric Rosentrater) Asset Management
Designer/Engineer: Aaron Tremayne (x2178)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Dave Chambers
Construction Window: September/October
Construction Forces: Spokane Operations
Scope:
This is a multi-year Minor Rebuild Project intended to reinforce the line in anticipation of rebuilding RossPark
Substation (in support of Facilities).
Staff_PR_102 Attachment C Page 3 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(13) Harrington 115kV Substation: Transmission Integration (ER 2289, BI BT305)
Region: Davenport (Manager: Cesar Godinez) Substation - Distribution Sub Rebuilds
Designer/Engineer: Pat Clevenger (x2109)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Larissa Pruitt
Construction Window: Spring 2016
Construction Forces: Davenport Operations
Scope:
Integrate rebuilt Substation.
(14) Gifford 115kV Substation: Transmission Integration (ER 2204, BI WT500)
Region: Colville (Manager: Kermit Olson) Substation - Distribution Sub Rebuilds
Designer/Engineer: Dan Adams (x2455)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Larissa Pruitt
Construction Window: TBD
Construction Forces: Colville Operations
Scope:
Integrate rebuilt Substation.
(15) Irvin 115kV Switching Station: Irvin Integration (ER 2446, BI ST102)
Region: Spokane (Manager: Eric Rosentrater) Spokane Valley Transmission Reinforcement
Designer/Engineer: Damon Fisher (x2540)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Randy Myhre
Construction Window: 2015-2017
Construction Forces: Spokane Operations
Scope:
2016 shoo-fly construction (phase 3) @ north side planned station site as part of 2014-2017 project.
This project is part of the Spokane Valley Transmission Reinforcement Program, and is designed to integrate new
Transmission lines between the Irvin Switching Station (located at Pines and Trent) and the Millwood Substation
(located adjacent to IEP in Millwood), and between Irvin and Opportunity/Beacon/Boulder Stations.
(16) 9th & Central 115kV Substation Expansion: Transmission Integration (ER 2204, BI ST801)
Region: Spokane (Manager: Eric Rosentrater) Substation - Distribution Sub Rebuilds
Designer/Engineer: Aaron Tremayne (x2178)
Area Engineer: Tim Figart
Area RBM: Steve Trabun
Area RE Representative: Dave Chambers
Construction Window: 2017
Construction Forces: Spokane Operations
Scope:
Design portion of 2017 Construction project.
Staff_PR_102 Attachment C Page 4 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
This project integrates a new line position at 9th & Central Substation for the existing Latah Tap Transmission
Line, while also establishing a breakered bus position for the 115/13kV transformer (presently tapped of the 9th
& Central-Sunset line)
(17) Addy - Devils Gap 115kV: Minor Rebuild – Spar Arm Replacement (ER 2057, BI AMT12)
Region: Colville (Manager: Kermit Olson) Asset Management
Designer/Engineer: Todd Ellsworth (x2773)
Construction Window: September-October
Construction Forces: Colville Operations
(18) Benewah - Boulder 230kV: Minor Rebuild (ER 2057, BI AMT12)
Region: Spokane (Manager: Eric Rosentrater) Asset Management
Designer/Engineer: Pat Clevenger (x2109)
Construction Window: April/May
Construction Forces: Spokane Operations
(19) Devils Gap – Nine Mile 115kV: Low Priority Ratings Mitigation (ER 2579, BI ST505)
Region: Spokane (Manager: Eric Rosentrater)
Designer/Engineer: Dan Adams (x2455)
Construction Window: September
Construction Forces: Spokane Operations
(20) Addy - Devils Gap 115kV: Low Priority Ratings Mitigation (ER 2579, BI ST506)
Region: Colville (Manager: Kermit Olson)
Designer/Engineer: CAI Consultants with Aaron Tremayne as Project Manager (x2178)
Construction Window: Design Only
Construction Forces: TBD
(21) Addy – Kettle Falls 115kV: Low Priority Ratings Mitigation (ER 2579, BI WT502)
Region: Colville (Manager: Kermit Olson)
Designer/Engineer: CAI Consultants with Aaron Tremayne as Project Manager (x2178)
Construction Window: Design Only
Construction Forces: TBD
Staff_PR_102 Attachment C Page 5 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(22) Addy – Gifford 115kV: Low Priority Ratings Mitigation (ER 2579, BI WT505)
Region: Colville (Manager: Kermit Olson)
Designer/Engineer: CAI Consultants with Aaron Tremayne as Project Manager (x2178)
Construction Window: Design Only
Construction Forces: TBD
CDA/Sandpoint/Kellogg/St. Maries
(23) Bronx - Cabinet 115kV (Phase 4): Condition/Capacity Rebuild (ER 2423, BI AMT81)
Region: Sandpoint (Manager: Jim Kane) Reconductors and Rebuilds
Designer/Engineer: Aaron Tremayne (x2178)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: May-August
Construction Forces: Contract
Scope:
Phase 4 (2016) is intended to upgrade/rebuild an 8-mile portion of the Bronx-Cabinet 115kV Transmission Line
between Bronx Substation and a point approximately 1-mile east of Oden Substation. The existing smaller
capacity conductor will be replaced with the higher capacity 795 ACSS “Drake” conductor to alleviate (based on
planning studies) thermal overloads. New weathering steel structures will be installed over the 8-mile section to
support the 795 conductor and an OPGW shield/communications wire.
(24) Noxon 230kV Switching Station: Rebuilt Station Transmission Integration (ER 2532, BI AT300)
Region: Sandpoint (Manager: Jim Kane) Noxon Switchyard Rebuild
Designer/Engineer: Damon Fisher (x2540)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: TBD
Construction Forces: TBD
Scope:
2016 (Phase 2) construction phase of 2015-2019 construction project.
This project is intended to rebuild the existing Noxon Rapids 230 kV Switchyard due to the present age and
condition of the equipment in the station. The station is the interconnection point of the Noxon Rapids Hydro
Electric Dam as well as a principal interconnection point between Avista and BPA, and as such is a significant
asset in the reliable operation of the Western Montana Hydro Complex.
Phase 2 scope is TBD.
Staff_PR_102 Attachment C Page 6 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(25) Noxon-Hot Springs #2 230kV: LiDAR Mitigation and Minor Rebuild (ER 2581, BI AT301)
Region: Sandpoint (Manager: Jim Kane) NERC Mitigation/Asset Management
Designer/Engineer: Bryan Hyde (x2990)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: July-November
Construction Forces: Contract
Scope:
2016 construction phase of 2015-2017 project.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL).
(26) Benewah – Pine Creek 115kV: LiDAR Mitigation and Minor Rebuild (ER 2579, BI CT304)
Region: Pullman/CDA/Kellogg (Managers: Jenny Blaylock/Chris Schlothauer/Steve Aubuchon)
NERC Mitigation/Asset Management
Designer/Engineer: Bryan Hyde (x2990)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: March-May
Construction Forces: Contract
Scope:
2016 construction phase of 2015-2016 project.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL).
(27) Benewah – Pine Creek (St. Maries Tap) 115kV: LiDAR and Minor Rebuild (ER 2579, BI CT501)
Region: Kellogg/St. Maries (Managers: Steve Aubuchon/Anna Scarlett) NERC Mitigation/Asset Management
Designer/Engineer: Patrick Clevenger (x2109)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: October
Construction Forces: CDA/Kellogg/St. Maries Operations
Scope:
2016 construction phase of 2015-2016 project.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL).
Staff_PR_102 Attachment C Page 7 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(28) Burke-Pine Creek 115kV (Phase 3): Pine Creek to Gov’t Gulch #3 & #4 (ER 2550, BI CT101)
Region: CDA/Kellogg (Managers: Chris Schlothauer/Steve Aubuchon) Reconductors and Rebuilds
Designer/Engineer: Aaron Tremayne (x2178)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: 2017
Construction Forces: Contract
Scope:
2016: Design phase.
2017: Procurement/Construction (Phase 3).
This project is intended to Rebuild/Reconductor a 4-mile section on each of the Burke-Pine Creek 115kV
transmission lines (#3) immediately east of the Pine Creek Substation. The project will utilize new steel
structures capable of an OPGW overbuild and a 795 ACSR “Drake” conductor capable of 155 MVA capacity at
80 degrees C.
Future project phases will address rebuilding the remaining sections of the Burke-Pine Creek lines to bring them
to a capacity of 155 MVA at 80 degrees C.
(29) CDA-Pine Creek 115kV: Rebuild/Reconductor (ER 2556, BI CT300)
Region: CDA/Kellogg (Managers: Chris Schlothauer/Steve Aubuchon) Reconductors and Rebuilds
Designer/Engineer: Bryan Hyde (x2990)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: 2017-2019
Construction Forces: Contract
Scope:
2016: Design phase.
2017: Procurement/Construction (Phase 1).
This project is intended to Rebuild/Reconductor the 30-mile 115kV transmission line section between the CDA
(15th Street) and Pine Creek Substations. The project will utilize new steel structures capable of an OPGW
overbuild and a 795 ACSS “Drake” conductor capable of 314 MVA capacity at 200 degrees C.
(30) Ramsey-Rathdrum #3 115kV: Minor Rebuild at Pole Line Road (ER 2057, BI AMT13)
Region: CDA (Manager: Chris Schlothauer) Asset Management
Designer/Engineer: Patrick Clevenger (x2109)
Area Engineer: Scott Weber
Area RBM: Patty Shea/Sharmon Schmitt
Area RE Representative: Dave Padon
Construction Window: TBD
Construction Forces: CDA Operations
Scope:
This is condition rebuild project covert h-frame structures to 6 single pole steel structures (OPGW ready). Project
will move Avista structures out of road right-of-way and on to private easement.
Staff_PR_102 Attachment C Page 8 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(31) Bronx-Cabinet (Construction Substation) 115kV: Replace Switch A-69 (ER 2254, BI AMT10)
Region: Sandpoint (Manager: Jim Kane) Asset Management
Designer/Engineer: Bryan Hyde (x2990)
Construction Window: TBD
Construction Forces: Sandpoint Operations
Pullman/Moscow/Clarkston/Lewiston/Grangeville
(32) Benewah-Moscow 230kV Transmission Line: Structure Replacement (ER 2577, BI PT305)
Region: Pullman (Manager: Jenny Blaylock) Reconductors and Rebuilds
Designer/Engineer: Damon Fisher (x2540)
Area Engineer: Tim Olson/Liz Frederiksen
Area RBM: Paul Kimmell
Area RE Representative: Randy Daniels
Construction Window: August-December
Construction Forces: Contract
Scope:
2016 (Phase 2) construction phase of 2015-2017 project.
This project is intended to replace structures and increase clearance on Avista’s 44 mile Benewah-Moscow 230kV
Transmission Line. The project will make the line ready for OPGW fiber installation and a future 1590 ACSS
Lapwing conductor.
(33) Moscow-Orofino (Juliaetta-Orofino) 115kV: LiDAR Mitigation and MR (ER 2579, BI WT300)
Region: Pullman/Grangeville (Managers: Jenny Blaylock/Jeff Schwendener) NERC Mitigation/Asset
Management
Designer/Engineer: Pat Clevenger (x2109)
Area Engineer: Tim Olson/Liz Frederiksen
Area RBM: Mike Tatko
Area RE Representative: Randy Daniels
Construction Window: April-June
Construction Forces: Contract
Scope:
2016 (Phase 2) construction phase of 2015-2016 project.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL).
(34) Moscow-Orofino (Juliaetta-Moscow) 115kV: LiDAR Mitigation and MR (ER 2579, BI WT300)
Region: Pullman/Grangeville (Managers: Jenny Blaylock/ Jeff Schwendener) NERC Mitigation/Asset
Management
Designer/Engineer: Pat Clevenger (x2109)
Area Engineer: Tim Olson/Liz Frederiksen
Area RBM: Mike Tatko
Area RE Representative: Randy Daniels
Construction Window: September-November
Construction Forces: Contract
Staff_PR_102 Attachment C Page 9 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
Scope:
2016 construction phase.
This is a combined Minor Rebuild and Line Ratings Mitigation Project (LiDAR) intended to replace
poles/structures failing Wood Pole Inspection, while also providing adequate line to ground clearance to match
present and future SCADA Variable Limit (SVL).
(36) Hatwai-Lolo 230kV: MR to Mitigation River Crossing Clearances (ER2057, BI AMT13)
Region: Lewiston (Manager: Josh DiLuciano) Asset Management
Designer/Engineer: Bryan Hyde (x2990)
Area Engineer: Tim Olson/Liz Frederiksen
Area RBM: Mike Tatko
Area RE Representative: Randy Daniels
Construction Window: TBD
Construction Forces: Contract
(38) Jaype-Orofino 115kV: Minor Rebuild (ER 2057, BI AMT13)
Region: Orofino (Manager: Jeff Schwendener) Asset Management
Designer/Engineer: Pat Clevenger (x2109)
Construction Window: August
Construction Forces: Grangeville Operations
Staff_PR_102 Attachment C Page 10 of 11
2016 Transmission Projects Summary.docx
Last Updated: 8/5/2016
(39) Dry Creek-Lolo 230kV: Minor Rebuild (ER 2057, BI AMT13)
Region: Lewiston (Manager: Josh DiLuciano) Asset Management
Designer/Engineer: Todd Ellsworth (x2773)
Construction Window: /May
Construction Forces: Lewiston Operations
(40) Dry Creek-Pound Lane 115kV: Minor Rebuild (ER 2057, BI AMT12)
Region: Pullman/Lewiston (Managers: Jenny Blaylock/Josh DiLuciano) Asset Management
Designer/Engineer: Pat Clevenger (x2109)
Construction Window: October
Construction Forces: Pullman/Lewiston Operations
(41) Grangeville- Nez Perce #1 115kV: Minor Rebuild (ER 2057, BI AMT13)
Region: Grangeville (Manager: Jeff Schwendener) Asset Management
Designer/Engineer: Pat Clevenger (x2109)
Construction Window: TBD
Construction Forces: Grangeville Operations
(42) Lind-Shawnee 115kV: Low Priority Ratings Mitigation (ER 2579, BI PT501)
Region: Pullman (Manager: Jenny Blaylock)
Designer/Engineer: CAI Consultants with Aaron Tremayne as Project Manager (x2178)
Construction Window: Design Only
Construction Forces: TBD
(43) Grangeville-Nez Perce #1 115kV: Replace Cottonwood Switch A-336 (ER 2254, BI AMT10)
Region: Grangeville (Manager: Jeff Schwendener) Asset Management
Designer/Engineer: Bryan Hyde (x2990)
Construction Window: TBD
Construction Forces: Grangeville Operations
(44/45) Grangeville-Nez Perce #2 115kV: Replace Switches A-376 & A-346 (ER 2254, BI AMT10)
Region: Grangeville (Manager: Jeff Schwendener) Asset Management
Designer/Engineer: Bryan Hyde (x2990)
Construction Window: TBD
Construction Forces: Grangeville Operations
Staff_PR_102 Attachment C Page 11 of 11