HomeMy WebLinkAboutIntermountain Gas 260122 Meridian Construction IPUC Construction Inspection
Inspector(s): Galli,Brooks Date(s): 260122
Company/Owner: Intermountain Gas Company (IGC) Unit/OPID: 8160
Address: 695 & 792 N Traquair Place City/District: Meridian
Contractor/Job#: W012405051, Foreman: Operator Supervisor: None
W012428152 J. Gonzalez
Job Description: %" Service Line System Type: M GD ❑ GT ❑ GG
One-Call Ticket: 2026040067, 2026022010 Total Inspection Days: 2.0
Tasks: Procedure Rating Comments
1. Materials—Handling, Storage, OPS 11 UNS EXPIRED PIPE 12/01/2022
Labeling '/" inch dated 07/2025 & 11/2025
2. Trenching/Boring—Depth, Clearance OPS 308 SAT At least 24" deep
OPS 322
3. Bedding/Backfill OPS 308 SAT Bedding with sand
SF 418
4. Pipe Installation(Tracer Wire) OPS 308 SAT 1 14 gauge in open trench
OPS 322 12 gauge under driveway
5. Valve Installation OPS 703 N/A
6. Coating Condition OPS 401 N/A
OPS 402
OPS 403
7. Manuals—Field Procedures, O & M SAT IGC procedures followed
8. Testing—Pressure, Duration, Type OPS 505 SAT 98 and 100 psi for 15 minutes
9. OQ Qualifications OPS 800 SAT Verified
10. Casing Seal/Installation OPS 325 N/A
11. Service Line Installation OPS 302 SAT
12. Tie-In/Hot Tapping OPS 600 N/A
13. Meter Location/Regulator Testing OPS 302 SAT 3 feet away from electrical
14. Equipment Calibration Verification OPS 501 SAT Verified
15. EFV Installation OPS 301 SAT EFV 1200
16. MAOP OPS 602 N/A
OPS 606
OPS 900
OPS 1000
17. Purge OPS 603 SAT Cleaning purge
18. Safety Equipment SF 418 SAT Fire extinguisher and JSA
SF 422
IPUC Form 4 Rev.12/08/2025
IPUC Construction Inspection
19. Abandonment OPS 607 N/A
20. Line Locating OPS 611 SAT Hand dig to locate service stub
21. Plastic Pine OPS 307 SAT Observed V butt fusion
- Joiner(s) Qualified OPS 309 Stab fittings
- Fusion Tools OPS 325
- Squeezing OPS 800
- Heat Plate
-Joining Procedure
22. Steel Pipe OPS 200 N/A
- Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
-Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
Additional Comments:
Observations included (695 N Traquair Place, Meridian, ID): Safety equipment, JSA, valid dig ticket,
verified operator qualifications, verified equipment calibration, correct trench depth, verified proper
rollback of completed 3/4"butt fusions, EFV 1200 installation, tracer wire and bedding with sand,
successful pressure test, squeeze off, mechanical fittings (con-stab coupler), backfill and continuity testing.
Quizzed contract employee on applicable AOCs for squeeze off procedures.
Observations included(792 N Traquair Place, Meridian, ID): Safety equipment, JSA, valid dig ticket, hand
dig to locate service stub, verified operator qualifications, verified equipment calibration, correct trench
depth, verified proper rollback of completed 3/4" butt fusions, EFV 1200 installation, tracer wire and
bedding with sand, successful pressure test, squeeze off and backfill.
Discrepancies:
Identified expired PE piping being installed at 792 N Traquair Place. The expired pipe was dated 12-1-
2022 which directly conflicted with the IGC OPS 11 that states a maximum of 3 years. No UV
documentation was provided to prove the piping was protected from exposure. The expired PE pipe was
replaced with unexpired PE pipe to complete service line installation.
Corrective Action Required: ® Yes ❑ No Compliance Letter#: NOPV I202601
Lead Inspector: Galli Date: Reviewer: Brooks Date:
260122
Signature: � Signature:
IPUC Form 4 Rev. 12/08/2025