Loading...
HomeMy WebLinkAboutAvista 250421-250424 IPUC Form 1 - Lewiston Field IPUC Pipeline Safety Inspection Inspector(s): Galli Date(s): 250421-250424 Company/Owner: Avista Utilities Unit/OPID: 31232 Standard: ® Training: ❑ TIMP/DIMP: ❑ OQ: ❑ Incident: ❑ Damage Prevention: ❑ Drug &Alcohol: ❑ Inspection Days: 6.5 Inspection Summary April 21, 2025: (2.0 Standard) (Galli 1.0)(Brooks 1.0) IPUC inspector Brooks and Galli traveled to Lewiston, Idaho to inspect field installed operating equipment for the Avista Lewiston inspection unit. April 22-23, 2025: (4.0 Standard) (Galli 2.0) (Brooks 2.0) Met with Avista company representatives in the Clarkston, Washington district office for a briefing, reviewed welding records, past year work orders and began field audit of Lewiston installed equipment. Six regulator stations were inspected for relief operation, regulator lock-up, general condition of the station including pipe-to-soil wrap, and cathodic protection. Five rectifiers, five carrier-to-casings and fifteen valves were also inspected. IPUC inspector Brooks and Galli traveled back to Boise, Idaho. April 24, 2025: (0.5 Standard) (Galli 0.5) Wrote inspection report, completed audit forms: PHMSA IA question set with OQ protocol 9, IPUC Form 1, Post-Inspection Preliminary Written Findings and attached inspection documents. Discrepancies: Regulator(404) had a minor dithiazine buildup on the pilot stem, preventing full lockup and causing a gradual rise in downstream pressure. The issue was resolved on-site by replacing the pilot stem. Corrective Action Required: ❑ Yes ® No Compliance Letter#: NA Follow Up Required: ❑ Yes ® No By Date: NA Lead Inspector: Galli Date: Reviewer: Brooks Date: 250424 �5 0 Signature: _ Signature: i IPUC Form 1 Rev. 12/11/2024