HomeMy WebLinkAboutIntermountain Gas 250317 Weiser Construction IPUC Construction Inspection
Inspector(s): Perkins Date(s): 17 March 2025
Company/Owner: Intermountain Gas Company(IGC) Unit/OPID: 8160
Address: 1355/1365 Crescent St (1375 Crescent IGC) City/District: Weiser
Contractor/Job: W012044642, Foreman: Operator Supervisor: None
W012044617 C. Zimmerman
Job Description: %" Services System Type: ® GD ❑ GT ❑ GG
One-Call Ticket: 2025110615, 2025102653 Total Inspection Days: 1.0
Tasks: Procedure# Rating Comments
1. Materials—Handling, Storage, Labeling OPS 11 SAT
2. Trenching/Boring—Depth, Clearance OPS 308 SAT 24"
OPS 322
3. Bedding/Backfill OPS 308 SAT Native soil
SF 418
4. Pipe Installation(Tracer Wire) OPS 308 SAT
OPS 322
5. Valve Installation OPS 703 N/A
6. Coating Condition OPS 401 N/A
OPS 403
7. Manuals—Field Procedures, O & M SAT
8. Testing—Pressure, Duration, Type OPS 505 SAT 100 PSI-15 Min
9. OQ Qualifications OPS 800 SAT
10. Casing Seal/Installation OPS 325 N/A
11. Service Line Installation OPS 302 SAT
12. Tie-In/Hot Tapping OPS 600 N/A
13. Meter Location/Regulator Testing OPS 302 N/A
14. Equipment Calibration Verification OPS 501 SAT Dates in file
15. EFV Installation OPS 301 SAT 1200
16. MAOP OPS 602 N/A
OPS 606
OPS 900
OPS 1000
17. Purge OPS 603 SAT
18. Safety Equipment SF 418 SAT
SF 422
19. Abandonment OPS 607 N/A
20. Line Locating OPS 611 SAT
IPUC Form 4 Rev. 12/10/2024
IPUC Construction Inspection
21. Plastic Pine OPS 307 SAT Stab fittings
- Joiner(s) Qualified OPS 309
- Fusion Tools OPS 325
- Squeezing OPS 800
- Heat Plate
- Joining Procedure
22. Steel Pine OPS 200 N/A
- Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
-Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
Additional Comments:
Address: 1355/1365 Crescent St Weiser, Idaho
Observations:
• Safety equipment was verified
• Conducted pressure test, purging, and verification of OQ records.
• Performed Stabbing, EFV installation, tracer wire placement, trenching, bedding, and
backfilling.
• Checked for gas quality to ensure compliance and line located after installation
• Quizzed the employee on squeeze/release times.
Address: 1375 Crescent St Weiser, Idaho
Upon arriving at the subdivision, I detected the distinct smell of a gas leak. I proceeded to spray the meter
bar on the house and identified a leak at the union connecting the riser to the meter bar. I immediately
contacted the IGC leak line, and a service technician from the Nampa district promptly responded to repair
the issue.
Corrective Action Required: ❑ Yes ® No Compliance Letter#:
Lead Inspector: ins Date: Reviewer: Brooks �, Date:
250317
Signature: Signature: 0_�
IPUC Form 4 Rev. 12/10/2024