HomeMy WebLinkAboutIntermountain Gas 250401 Form 1 HPSS Idaho PUC Pipeline Safety Inspection Summary
Inspector(s): I Perkins Date(s):
March 24-28, 2025
Company/Owner: Intermountain Gas Company (IGC) FUnit#/OPID 8160
Inspection Type&Time (1 day, 0.5 day) Total Inspection Days: 6
Standard: I 6.0 Training: (T)(D) Integrity Management: Incident:
Follow-up: OQ: I I Damage Prevention: D&A:
Inspection Summary
March 24, 2025: (2.0 Standard) 1.0 Perkins/1.0 Galli
IPUC Inspectors Perkins/Galli traveled to Pocatello and conducted 37 High Pressure Service Sets
(HPSS)inspections in American Falls and Aberdeen. Zero discrepancies were noted.
March 25, 2025: (1.0 Standard)
IPUC Inspector Perkins attended Intermountain Gas Company monthly safety briefing at Pocatello
office, accompanied meter inspector Sherman Schmidt while performing annual inspection on Reg
Stations#48675-RS-59877, 48679-RS-59725, 48679-RS-60085 and conducted 37 High Pressure
Service Sets (HPSS) inspections in Pocatello
March 26, 2025: (1.0 Standard)
IPUC Inspector Perkins traveled to Grace, Soda Spring and Lava Hot Springs and conducted 70 High
Pressure Service Sets (HPSS) inspections.
March 27, 2025: (1.0 Standard)
IPUC Inspector Perkins traveled to Grace and Bancroft and conducted 36 High Pressure Service Sets
(HPSS) inspections and worked on Form 1.
March 28, 2025: (1.0 Standard)
IPUC Inspector Perkins traveled back to Boise and completed Form 1.
Discrepancies
Throughout the Grace/Bancroft area the pipeline markers and HPSS markers are unreadable and need
replaced and in multiple places there were no carsonites at the HPSS.
48675-RS-59877 - Small leak on the blowdown valve
48679-RS-59725- Primary reg did not lock up, repairs were made and reg locked up
48679-RS-60085- Primary reg did not lock up, repairs were made and reg locked up
48325-HPSS-62290- 4699472193 Leak at the relief regulator
48825-HPSS-64762 - Buried Stop
48825-HPSS-66918 -Abandoned?
48825-HPSS-66952 - Leak at test plug on needle valve
48825-HPSS-66936 -Abandoned?
48829-HPSS-63241- Unable to locate
48829-HPSS-66946 - Needs painted
IPUC Form 1
Idaho PUC Pipeline Safety Inspection Summary
48829-HPSS-66963 - Needs painted
48829-HPSS-69482 - Unable to locate
48829-HPSS-69541 - Unable to locate
48829-HPSS-69531 - Buried stop and vent
48829-HPSS-66961- Abandoned?
48829-HPSS-66950- Unable to locate
48827-HPSS-64771 - Unable to locate
48827-HPSS-66916 - Unable to locate
48827-HPSS-66269 - Leak at test plug on needle valve
48827-HPSS-64341 -Abandoned?
48827-HPSS-64159 - Leak at relief flange
48827-HPSS-64821 - Unable to locate
48827-HPSS-62277 - Unable to locate
48827-HPSS-1150319 - Unable to locate
48827-HPSS-62458- Abandoned?
48827-HPSS-69832-Unable to locate
Operator to provide work orders for all finding/discrepancies and completion dates.
Corrective Action Required: See line above Yes X I No
Follow-up Required: by (date): 0/2025 Yes I X I No
Inspector(Lead):
Perkins / Date: 03/28/25
Reviewer: Date: �kS Oy d
Brooks
IPUC Form 1