HomeMy WebLinkAboutIntermountain Gas 250128-29 Caldwell Construction IPUC Construction Inspection Inspector(s): Perkins Date(s): 28-29 January 2025 Company/Owner: Intermountain Gas Company (IGC) Unit/OPID: 8160 Address: 19127 Red Label Ln Ste 101-108 City/District: Caldwell Contractor/Job#: 053345-317 Foreman: Operator Supervisor: J. Garcia /Vem- S e Q'5 per,9 Job Description:2" Service install off%" high pressure System Type: 0 GD ❑ GT ❑ GG One-Call Ticket: 2025040911 Total Inspection Days: 2 Tasks: Procedure# Rating Comments 1. Materials-Handling, Storage, Labeling OPS 11 SAT 2. Trenching/Boring-Depth, Clearance OPS 308 SAT OPS 322 3. Bedding/Backfill OPS 308 SAT _ SF 418 4. Pipe Installation (Tracer Wire) OPS 308 SAT OPS 322 5. Valve Installation OPS 703 SAT 2" curb Valve 6. Coating Condition OPS 401 SAT %" service line coating in like new OPS 403 condition 7. Manuals-Field Procedures, O &M SAT 8. Testing-Pressure, Duration, Type OPS 505 N/A 9. OQ Qualifications OPS 800 SAT 10. Casing Seal/Installation OPS 325 N/A 11. Service Line Installation OPS 302 SAT 12. Tie-In/Hot Tapping OPS 600 SAT V welded on tapping tee 13. Meter Location/Regulator Testing OPS 302 N/A 14. Equipment Calibration Verification OPS 501 SAT Dates in file 15. EFV Installation OPS 301 SAT 2" curb Valve 16. MAOP OPS 602 SAT 330PSI :Y" service line to 2" service OPS 606 line at 60PSI OPS 900 OPS 1000 17. Purge OPS 603 N/A 18. Safety Equipment SF 418 SAT SF 422 19. Abandonment OPS 607 N/A 20. Line Locating OPS 611 SAT IPUC Form 4 Rev.12/10/2024 IPUC Construction Inspection 21. Plastic Pine OPS 307 SAT Fusing =_ - Joiner(s) Qualified OPS 309 -Fusion Tools OPS 325 - Squeezing OPS 800 -Heat Plate - Joinin Procedure 22. Steel Pine OPS 200 SAT Welded on V tapping tee, - Welder(s) Qualified OPS 201 coating/wrap applied Pipe/Coating—Inspected/Repaired OPS 202 - Cathodic Protection OPS 306 -Non-Destructive Testing OPS 401 -Welding Procedures OPS 407 - Removal of asbestos wrap OPS 402 - Exothermic Welding OPS 403 Additional Comments: Address: 19127 Red Label Ln Ste 101-108 Caldwell, Idaho Observations Included: Line locating, correct trench depth, bedding, backfilling, fusing,welding, wrapping/ coating, purged 2" coiled roll, curb valve installation, safety equipment, tracer wire, verification OQ records. The contractor was having trouble confirming wall thickness prior to welding on tapping tee so they called out IGC to come confirm with their equipment. Corrective Action Required: ❑ Yes ® No Compliance Letter#: Lead Inspector: Perkins Date: Reviewer: Brooks Date: 250129 Signature: Signature: -13 C? IPUC Form 4 Rev. 12/10/2024