HomeMy WebLinkAboutIntermountain Gas 241028-29-30 Emmett Construction IPUC Construction Inspection
Inspector(s): Perkins Date(s): 10/28-29-30/2024
Company/Owner: Unit/OPID: 08160
Intermountain Gas Company(IGC)
Address: 1286 E Sales Yard Rd City/District: Emmett
Contractor/Job # Foreman: Employees: See line-up in file
004897-283 German Gomez
Job Description: Install %" Service Line off 4" System Type: ® Distribution ❑ Transmission
High Pressure main and install HPSS
Operator Supervisor: One-Call Ticket: 2024400082
On-Site: N
Total Inspection Days: 3.0
Tasks: Rating Critical Procedure# Comments
1. Materials—Handling, Storage, SAT OPS 11
Labeling
2. Trenching/Boring—Depth, Clearance SAT OPS 308
OPS 32222
3. Bedding/Backfill SAT OPS 308 Sand &Native Soil
SF 418
4. Pipe Installation (Tracer Wire) SAT OPS 308
OPS 322
5. Valve Installation N/A OPS 703
6. Coating Condition SAT OPS 401 Brown bore pipe
OPS 403
7. Manuals—Field Procedures O & M SAT
8. Testing—Pressure, Duration, Type SAT OPS 505 780 psi, 98 psi
9. OQ Qualifications SAT OPS 800 In folder
10. Casing Seal/Installation N/A OPS 325
11. Service Line Installation SAT OPS 302
12. Tie-In/Hot Tapping SAT OPS 600 Tapping tee
13. Meter Location/Regulator Testing SAT OPS 302 HPSS
14. Equipment Calibration Verification SAT OPS 501 Dates in folder
15. EFV Installation SAT OPS 301 300 steel EFV
16. MAOP SAT OPS 602 825 psi
OPS 606
OPS 900
OPS 1000
17. Pure SAT OPS 603
18. Safety Equipment SAT SF 418
SF 422
19. Abandonment N/A OPS 607
20. Line Locating SAT OPS 611 Pot Holing
IPUC Form 4 Rev. 12/21/2023
IPUC Construction Inspection
21. Plastic Pipe AT OPS 307 Fused riser _-
- Joiner(s) Qualified OPS 309
- Fusion Tools OPS 324
- Heat Plate OPS 325
- Joining Procedure OPS 800
22. Steel Pipe SAT OPS 200 V bore pipe & tapping
- Welder(s) Qualified OPS 201 tee. Ground coating off
Pipe/Coating—Inspected/Repaired OPS 202 to attach tee.
- Cathodic Protection OPS 306
-Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
4800
Additional Comments:
IPUC inspector Perkins observed Das-Co, a contractor for IGC install V Service Line off 4"
High Pressure main and install HPSS in Emmett, ID.
Address: 1286 E Sales Yard Rd
Observations Include: Fusing, welding, verification of OQ records, potholing, line locating, trenching,
bedding/backfilling, pressure testing, purging, EFV install and tracer wire tie-in. All observed
procedures were followed in accordance with IGC Operations and Maintenance Manual.
Corrective Action Required: Yes No X
Follow-up Required: By Date: Yes No X
Inspector (Lead): Date: 10/30/2024
Perkins
Reviewer:
Brooks Date: �Q-3�•��(
IPUC Form 4 Rev. 12/21/2023