HomeMy WebLinkAboutAvista 210621-24 Kellogg Field Construction Idaho PUC Pipeline Safety Inspection Summary
Inspector(s): Perkins/Ulmer/Brooks I Date(s): JJune 21-24, 2021
Company/Owner: Avista Utilities Unit/OPID: I Kellogg/31232
Inspection Type &Time (1 day, 0.5 day) Total Inspection Days:1 12
Standard: 11 Construction:= Training: (T)(D)Integrity Management: Incident:
M/M: = Follow-up: OQ: Damage Prevention: D&A:
Inspection Summary
Audit consisted of inspecting field installed operating equipment for the Avista's Kellogg,Idaho inspection
unit.Records and procedures for all Idaho Avista units were inspected March 16-17,2021 virtually from
our office in Boise,Idaho.
June 21,2021: (3 Standard travel)
Traveled to Coeur d'Alene, ID to conduct inspection.
June 22-23 2021: (5 Standard) (1 OQ)
Met with Avista company representatives in the Kellogg, Idaho district office for in-brief and began field audit of
Kellogg installed equipment.
Regulator Stations 230,235,240,242,244,248,249,252,260270,273,274,275,276 and 278, were randomly selected
and inspected for relief operation, regulator lock-up and general condition of the station including pipe-to-soil
wrap and corrosion. Seven cathodic rectifiers,twenty valves, six carrier-to-casings and three patrols were
inspected for the Kellogg district with four defects noted(Reg Sta#235 and 260 worker failed lock-up and 270
monitor failed lock-up also Patrol at Terror Gulch-Expansion joint possible out of range deflection and pipe is
lifting off the rollers). IPUC Form 3 was conducted with Randy Bareither.
June 24,2021: (3 Standard)
Traveled back to Boise, ID. Wrote the inspection report, completed audit forms: PHMSA IA question set, IPUC
Forms 1, 3 and attached inspection documents.
Attached:
PHMSA Form 2, IA Equivalent,Field Portion(Not attached)
IPUC Form 1, Inspection Summary
IPUC Form 3, Exit Interview
IPUC Field equipment Work sheets
Corrective Action Required: Yes X No
Follow-up Required: by(dat ): 23 June 2022 Yes X No
Inspector (Lead): ��% Date:
Perkins 2
Reviewer: Date:
IPUC Form 1