Inspector(s): Perkins/Brooks Date(s): Mar 14-17, 2022
Company/Owner: Intermountain Gas Company Unit/OPID: I Nampa Field
Inspection Type &Time (1 day, 0.5 day) I Total Inspection Days:1 5.5
Standard:F5 Construction: F-1 Training: F__] (T)(D) Integrity Management: E:1 Incident: E]
M/M: F7 Follow-up: F-1 OQ: 0.5 Damage Prevention: D&A: a
Inspection Summary
Audit consisted of inspecting field installed equipment for the Nampa, Idaho inspection units. The PHMSA IA
question set and IGC equipment listing were used as a guide throughout the audit to ensure all areas were
completed/covered. Records (28-29 Mar 22) and procedures (1 Feb 22) for all Idaho Intermountain Gas Units
were inspected at the Intermountain Gas Company(IGC) headquarters in Boise, Idaho.
January 27, 2022: (0.5 Standard Prep)
Prepared for IGC Nampa Field Audit
March 14-16, 2022: (3.5 Standard 0.5 OQ)
Met with IGC company representatives in the Nampa district office for in-brief and to begin field audit and
review OQ records for all personnel taking part in the inspection.
Regulator Stations 48325-RS-60738, 48325-RS-59705, 48321-RS-59930,48321-RS-59936, 48318-RS-59835,
30129,48321-RS-59737,48321-RS-59722, 48318-RS-59834,48318-RS-59836, 48318-RS-59808,48318-RS-
59839,48267-RS-59883,48267-RS-59862,48267-RS-59881, 48263-RS-59863,48263-RS-59728,48371-RS-
59985,48371-RS-59978, 48363-RS-59909,48363-RS-59887, 48367-RS-59888, and 48367-RS-59916 were
inspected for proper operating parameters, regulator lock-up, relief device operation, cathodic protection pipe-
to-soil readings, pipe-to soil interface wrap protection, station warning signs and right-of-way clearances.
20 casing-to-carrier isolation checks,five cathodic protection rectifiers, three pipeline patrols, and 17
emergency/isolation valves were checked for proper operation, observations listed below.
An IPUC Form 3 (exit interview) was performed following the district inspection with Will Lindsey
(Compliance/Audit Specialist) of Intermountain Gas Company.
Observations:
Reg Station: Failed lock-up Primary: 48325-RS-60738,48321-RS-59930,48321-RS-59936,48318-RS-59839,
48267-RS-59881, 48363-RS-598871 corrected on the spot.
Reg Station: Failed lock-up Secondary: 48321-RS-59936, corrected on the spot.
Low CP read: 48371-RS-59985
Reg Stations needing corrosion control/paint: 48318-RS-59839, 48363-RS-59909
Mar 17, 2022: (1 Standard Post)
Completed forms and typed report.
IPUC Form 1
Idaho PUC Pipeline Safety Inspection Summary
Attached:
IPUC Form 1, Inspection Summary
IPUC Form 3, Exit Interview
IPUC Field Equipment Status Worksheets
Misc. photos
PHMSA Form 15 OQ Field
Corrective Action Required: Yes X No
Follow-up Required: by(date): 15 Sep 22 Yes X No
Inspector (Lead): Date:
Bruce Perkins 3/17/2022
Reviewer: Date: \
Jeff Brooks ' \