Loading...
HomeMy WebLinkAboutDominion 210913-15 Field and Records Idaho PUC Pipeline Safety Inspection Summary Inspector(s): Perkins Date(s): See below Sept 9, 13-15 and 21,2021 Company/Owner: Dominion Energy Unit/OPID: 1 12876 Inspection Type&Time (1 day, 0.5 day) Total Inspection Days: 5 Standard: 4.5 Construction:F] Training: [7 (T)(D)Integrity Management: Incident: M/M: = Follow-up: = OQ: 0.5 Damage Prevention: D&A: Inspection Summary 2021, CRM, Records, and Field Inspection Dominion Energy September 9, 2021: (1 Standard Prep) Prepared for the Dominion Energy records/CRM inspection through review of the PHMSA inspections Form 2 and 2020 inspection results. The company's pipeline system in Idaho consists of transmission and distribution lines. September 13, 2021: (.5 Standard Travel, .5 CRM) Traveled from Boise, ID to Salt Lake City, UT and met with Dominion Energies compliance and engineering personnel and Control room personnel at Dominion's Office/CRM to review records and CRM procedures. September 14, 2021: (1.0 Standard) Idaho Public Utilities Commission Inspector met with Dominion Energies compliance and engineering personnel at Dominion's Offices in Logan, Utah to review records for the previous year 2020. The PHMSA Form 2 (Standard Inspection Report of a Gas Distribution Operator) and PHMSA Form 13 (D&A Inspection Form) were used as a guides throughout the audit to ensure all areas were completed as they pertain to required records. September 15, 2021: (.5 Standard/Travel, .5 OQ) Met with Dominion Energy representatives in the Logan district office for in-brief and to begin field audit. Regulator Stations FR0001, FC0001, FC0003, FC0004, FC0005, FC0006, and PS0001 were inspected for proper operating parameters, regulator lock-up, relief device operation, cathodic protection pipe-to-soil readings, pipe to soil interface wrap protection, station warning signs and right-of-way clearances. Three casing-to-carrier isolation checks, one cathodic protection rectifier and nine emergency isolation valves were checked for proper operation and found to be operating properly. An IPUC Form 3 (exit interview) was performed following the inspection with Justin Berg(Pipeline Compliance), Clark Jarrett(Measurement& Control (M&C)Tech), Kelly Facer(CP Tech),James Sharp (M&C Tech), Reid Hess (Manager Gas Control) and Redd Ivins (CRM Shift Lead) of Dominion Energy. Observations: Reg Stations: FR0001, FC0001, FC0003, FC0004, FC0005, and FC0006 not plumbed for lock-up, but were able to manipulate to ensure lock-up would occur. IPUC Form 1 Idaho PUC Pipeline Safety Inspection Summary September 21, 2021: (1 Standard Post) Completed forms and typed report. Attached: PHMSA Form 13, Pipeline Drug &Alcohol Questions IPUC Form 1, Inspection Summary IPUC Form 2, Supplemental Checklist IPUC Form 3, Exit Interview Corrective Action Required: Yes No X Follow-up Required: by (date): Yes No X Close-out Letter Issued: Yes X No Inspector (Lead): / � _n Date: Reviewer: Date: IPUC Form 1