HomeMy WebLinkAboutDominion 210614-17 Integrity Dig Franklin Idaho PUC Pipeline Safety Inspection Summary
Inspector(s): Ulmer I Date(s): jJun 14-17, 202
Company/Owner: DEUWI Unit/OPID: I Franklin
Inspection Type &Time (1 day, 0.5 day) Total Inspection Days: 4
Standard: Construction: Training: (T)(D) Integrity Management: 3.5 Incident:
M/M: Follow-up: OQ: 0.5 Damage Prevention: D&A:
Inspection Summary
Audit consisted of Dominion Energy Utah/Wyoming/Idaho (DEUWI) Integrity Management (IM) verification dig
in Franklin, Idaho.
Jun 14, 2021: (1 TIMP travel)
Travel to Logan, Utah to meet with DEUWI personnel for the IM verification dig.
Jun 15-16, 2021: (1.5 TIMP, .5 OQ)
Observed IM verification dig at 175 S Hwy 91, Franklin, Idaho, Whitaker Construction crew exposed 10" FBE
coated steel line that was identified during the survey to have an anomaly. They did a visual check,jeeped pipe
and CP tech did a soil resistivity test and checked anode output. The crew found coating issues on a
compression sleeve and a spot at the 6 o'clock position on the pipe. Approx. 24' of the 10" pipe was cleaned,
sandblasted, 2-part epoxied, and wax wrapped at the transition. Flow sand was used as backfill.
Jun 17, 2021: (1 TIMP)
Traveled back to Boise, completed forms and typed report.
Attached:
IPUC Form 1, Inspection Summary
PHMSA Form 15 OQ Field
Corrective Action Required: Yes No X
Follow-up Required: #y( e : Yes No X