HomeMy WebLinkAboutIntermountain Gas 231024 Star Construction IPUC Construction Inspection
Inspector(s): Galli, Brooks Date(s): 10/24/2023
Company/Owner: Unit/OPID: 08160
Intermountain Gas Company IGC
Address: 8956 W Snow Wolf Dr, City/District: Star
9924 W Sunchaser St, 9943 N Costa Madera Ave
Contractor/Job #: Foreman: Employees: See job list
367-009825, 367-007748, Michael Krebs
367-07503
Job Description: 3/a" Service Line Circle: Distribution
Operator Supervisor: John One-Call Ticket: 420176,412890, 412891
On-Site: N
Total Inspection Days: 2
Tasks: Rating Critical Procedure# Comments
1. Materials—Handling, Storage, SAT OPS 11
Labeling
2. Trenching/Boring—Depth, Clearance SAT OPS 308
OPS 322
3. Bedding/Backfill SAT OPS 308
SF 418
4. Pipe Installation (Tracer Wire) SAT OPS 308
OPS 322
5. Valve Installation N/A OPS 703
6. Coating Condition N/A OPS 401
OPS 403
7. Manuals—Field Procedures, O & M SAT
8. Testing—Pressure, Duration, Type SAT OPS 505 Tested at 98 psi
9. OQ Qualifications SAT OPS 800
10. Casing Seal/Installation N/A OPS 325
11. Service Line Installation SAT OPS 302
12. Tie-In/Hot Tapping N/A OPS 600
13. Meter Location/Regulator Testing N/A OPS 302
14. Equipment Calibration Verification SAT OPS 501 Pyrometer: 9/8/24
Pressure Gauge: 7/12/24
15. EFV Installation SAT OPS 301 EFV 1200
16. MAOP N/A OPS 602
OPS 606
OPS 900
OPS 1000
17. Pure N/A OPS 603
18. Safety Equipment SAT SF 418
SF 422
19. Abandonment N/A I OPS 607
20. Line Locating SAT I OPS 611
IPUC Form 4 Rev. April 2023
IPUC Construction Inspection
21. Plastic Pipe SAT OPS 307
- Joiner(s) Qualified OPS 309
- Fusion Tools OPS 324
- Heat Plate OPS 325
- Joining Procedure OPS 800
22. Steel Pipe N/A OPS 200
- Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
-Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
4800
Additional Comments:
IPUC inspector Galli and Brooks observed Das-Co a contractor for IGC install 3/4" service lines.
IPUC Inspector Brooks attempted to observed Das-co crews at 1438 N Cole Bluff Cottage, Boise, ID
and 6616 N Spindrift Way, Meridian, ID. Das-co was unable to complete the jobs due to equipment
malfunction and space limitations.
Address: 8956 W Snow Wolf Drive, Star, ID
Observations included: trenching, line locating, tracer wire, butt fusion, EFV 1200 installation,
successful pressure test at 98 psi for 15 minutes, squeeze off,bedding and backfill. Quizzed employees
on applicable AOCs of fusion and squeeze off procedures. All observed activity was completed in
accordance with IGC Operations and Maintenance Manual.
Address: 9924 W Sunchaser St, 9943 N Costa Madera Ave
Observations included: trenching, line locating, tracer wire,butt fusion, EFV 1200 installation and
bedding. All observed activity was completed in accordance with IGC Operations and Maintenance
Manual.
Corrective Action Required: Yes No X
Follow-up Required: By Date: Yes No X
Inspector (Lead): Date: 10/24/2023
Galli
Reviewer: `
Date: 1'o-
Brooks
1PUC Form 4 Rev. April 2023