Loading...
HomeMy WebLinkAboutAvista 230718 IPUC Form 1 - Sandpoint Field Audit Idaho PUC Pipeline Safety Inspection Summary Inspector(s): jBrooks, Galli Date(s): 07/17-19 &21/2023 Company/Owner: Avista Utilities I Unit#/OPID 131232 Inspection Type& Time (1 day, 0.5 day) Total Inspection Days:17.5 Standard: 1 7 Training: (T)(D) Integrity Management: Incident: Follow-up: I I OQ: 10.51 Damage Prevention: D&A: Inspection Summary Audit consisted of inspecting field installed operating equipment for the Avista Sandpoint inspection unit. January 31,2023: (0.5 Standard Prep) Prep for Sandpoint Field Audit July 17,2023: (2.0 Standard Travel) Traveled to Sandpoint July 18,2023: (2.0 Standard) IPUC inspectors Brooks and Galli conducted a field audit of Avista's Sandpoint district. Audit included: Review of construction records, emergency operations manual, verification of OQs, 4 regulator stations and 1 odorizor (200, 201, 208, 209, 206*), 5 carrier/casings, 2 rectifiers, 16 control valves and 2 patrols. One regulator station(206) failed lockup due to dithiazine issues on the worker regulator. Regulator was fixed on-site by replacing pilot stem and plans were in place for installation of a pilot filter. The Kootenai River Bridge Crossing had a low CP of-0.585. CP Technician was able to fix at the nearest recifier by securing a couple loose connections. Final CP was -1.58. *follow up inspection for prior year failure. July 19,2023: (0.5 OQ, 0.5 Standard post) Wrote the inspection report, completed audit forms: PHMSA IA question set, IPUC Form 1, Preliminary Written Findings and attached inspection documents. July 21,2023: (2 Standard Travel) Traveled from Sandpoint Attached: IPUC Form 1, Inspection Summary Preliminary Written Findings 1PUC Field Equipment Worksheets Corrective Action Required: Yes No X Follow-up Required: by(date): Yes No X Inspector(Lead): Date: Brooks 7/20/2023 Reviewer: Date: IPUC Form 1