HomeMy WebLinkAboutIntermountain Gas 240905 Meridian Construction IPUC Construction Inspection
Inspector(s): Galli Date(s): 09/05/2024
Company/Owner: Unit/OPID: 08160
Intermountain Gas Company (IGC)
Address: 4232 S Graycliff Way City/District: Meridian
Contractor/Job #: Foreman: Employees: See job list
413-51534 Adrian Wesley
Job Description: Install %" Service Line(s) System Type: ® Distribution ❑ Transmission
Operator Supervisor: Kyle One-Call Ticket: 2024350116
On-Site: N
Total Inspection Days: 0.5
Tasks: Rating Critical Procedure# Comments
1. Materials—Handling, Storage, N/A OPS 11
Labeling
2. Trenching/Boring—Depth, Clearance N/A OPS 308
OPS 322
3. Bedding/Backfill N/A OPS 308
SF 418
4. Pipe Installation(Tracer Wire) N/A OPS 308
OPS 322
5. Valve Installation N/A OPS 703
6. Coating Condition N/A OPS 401
OPS 403
7. Manuals—Field Procedures, O & M UNSAT OPS 611
8. Testing—Pressure, Duration, Type N/A OPS 505
9. OQ Qualifications SAT OPS 800 Verified
10. Casing Seal/Installation N/A OPS 325
11. Service Line Installation N/A OPS 302
12. Tie-In/Hot Tapping N/A OPS 600
13. Meter Location/Regulator Testing N/A OPS 302
14. Equipment Calibration Verification N/A OPS 501 Did not observe
15. EFV Installation N/A OPS 301
16. MAOP N/A OPS 602
OPS 606
OPS 900
OPS 1000
17. Pure N/A OPS 603 Did not observe
18. Safety Equipment SAT SF 418 Fire Extinguisher and
SF 422 JSA
19. Abandonment N/A OPS 607
20. Line Locating UNSAT OPS 611 Hand dig without
markings
P U C Form 4 Rev. 12/21/2023
IPUC Construction Inspection
21. Plastic Pipe N/A OPS 307
- Joiner(s) Qualified OPS 309
- Fusion Tools OPS 324
- Heat Plate OPS 325
- Joining Procedure OPS 800
-Squeeze Off
22. Steel Pipe N/A OPS 200
- Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
- Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
4800
Additional Comments:
IPUC inspector(s) observed Das-Co, a contractor for IGC install 3/4" service line(s).
Address: 4232 S Graycliff Way, Meridian, ID
Observations Included: Safety equipment, verification of OQ records, valid dig ticket but no visible
markings.
Discrepancies: Upon arrival the IPUC inspector observed a Das-Co crew hand digging a trench in the
immediate vicinity of live power. The crew had an unexpired dig ticket, however no visible markings or
flags were in the area. While attempting to locate the gas service stub, the crew inadvertently made
contact and damaged a communication line conduit (unknown if the communication conduit was live).
Per Idaho Statute 55-2205 (2), 55-2205 (5), 55-2207 (2), and MDU OPS 611 Section 2.1 and 2.5; all -
underground facilities shall be located and marked prior to commencing excavation.
Das-co Area Superintendent was notified and advised the crew to skip the install until new locates are
completed. IGC Compliance Manager was notified of the probable violation. M G
Corrective Action Required: NOPV 1202413 Yes X No
Follow-up Required: By Date: October 25 024 Yes X j No
Inspector (Lead): -
� Date: 09/16/2024
Galli
Reviewer:
Date:
Brooks
IPUC Form 4 Rev. 12/21/2023