HomeMy WebLinkAboutIntermountain Gas 240703 Meridian Construction IPUC Construction Inspection
Inspector(s): Galli Date(s): 07/03/2024
Company/Owner: Unit/OPID: 08160
Intermountain Gas Company (IGC)
Address: 4417 & 4161 S Graycliff Way City/District: Meridian
Contractor/Job#: Foreman: Employees: Adrian Wesley
051224-413, 049807-413 Darcy Ugalde
Job Description: Install 3/" Service Lines System Type: x Distribution ❑ Transmission
Operator Supervisor: Kyle One-Call Ticket: 2024261816, 2024261815
On-Site: N
Total Inspection Days: 1
Tasks: Rating Critical Procedure# Comments
1. Materials —Handling, Storage, SAT OPS 11
Labeling
2. Trenching/Boring—Depth, Clearance SAT OPS 308 24 inches
OPS 322
3. Bedding/Backfill SAT OPS 308 Sand used
SF 418
4. Pipe Installation(Tracer Wire) SAT OPS 308 14-Guage
OPS 322
5. Valve Installation N/A OPS 703
6. Coating Condition N/A OPS 401
OPS 403
7. Manuals—Field Procedures, O & M SAT
8. Testing—Pressure, Duration, Type SAT OPS 505 See additional comments
9. OQ Qualifications SAT OPS 800 Verified
10. Casin Seal/Installation N/A OPS 325
11. Service Line Installation SAT OPS 302
12. Tie-In/Hot Tapping N/A OPS 600
13. Meter Location/Regulator Testing SAT OPS 302
14. Equipment Calibration Verification SAT OPS 501 Verified and in file
15. EFV Installation SAT OPS 301 EFV 1200
16. MAOP N/A OPS 602
OPS 606
OPS 900
OPS 1000
17. Purge SAT OPS 603
18. Safety Equipment SAT SF 418 Fire Extinguisher and
SF 422 JSA
F 19. Abandonment I N/A I OPS 607
20. Line Locating SAT OPS 611 Continuity Testing
IPUC Form 4 Rev. 12/2v2023
IPUC Construction Inspection
21. Plastic Pipe SAT OPS 307
-Joiner(s) Qualified OPS 309
- Fusion Tools OPS 324
-Heat Plate OPS 325
- Joining Procedure OPS 800
-Squeeze Off
22. Steel Pipe N/A OPS 200
- Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
- Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
4800
Additional Comments:
IPUC inspector Galli observed Das-Co, a contractor for IGC install 3/4" service line(s)in Meridian, ID.
Address: 4417 S Graycliff Way, Meridian, ID
Observations Include: Correct trench depth, safety equipment, verification of OQ records, verification
of equipment calibrations, line locating, tracer wire, visual acceptance of plastic butt fusions, EFV 1200
installation, successful pressure test at 100 psi for 15 minutes, squeeze off, purging, bedding with sand,
backfill and continuity testing. All observed procedures were followed in accordance with IGC
Operations and Maintenance Manual.
Address: 4161 S Graycliff Way, Meridian, ID
Observations Include: Correct trench depth, safety equipment, verification of OQ records, verification
of equipment calibrations, line locating, tracer wire, visual acceptance of plastic butt fusions and EFV
1200 installation. All observed procedures were followed in accordance with IGC Operations and
Maintenance Manual.
Corrective Action Required: Yes No X
Follow-up Required: By Date: Yes No X
Inspector (Lead): Date: 07/03/2024
Galli
Reviewer:
Brooks
Date: 7.
IPUC Form 4 Rev. 12/21/2023