HomeMy WebLinkAboutIntermountain Gas 240605 Boise Construction IPUC Construction Inspection
Inspector(s): Perkins Date(s): 06/05/2024
Company/Owner: Unit/OPID: 08160
Intermountain Gas Company (IGC)
Address: 2411 S Shoshone St Trailers 10/11/12 City/District: Boise
Contractor/Job Foreman: Employees: See Job List
24NG4005.2 German Gomez
Job Description: Install %" PE Services off 2" System Type: ® Distribution ❑ Transmission
main
Operator Supervisor: One-Call Ticket: 2024213679
On-Site: N
Total Inspection Days: 1.0
Tasks: Rating Critical Procedure# Comments
1. Materials—Handling, Storage, SAT OPS 11
Labeling
2. Trenching/Boring—Depth, Clearance SAT OPS 308
OPS 322
3. Bedding/Backfill SAT OPS 308
SF 418
4. Pipe Installation(Tracer Wire) SAT OPS 308
OPS 322
5. Valve Installation N/A OPS 703
6. Coating Condition N/A OPS 401
OPS 403
7. Manuals—Field Procedures, O & M SAT
8. Testing—Pressure, Duration, Type SAT OPS 505 94 PSI
9. OQ Qualifications SAT OPS 800 In folder
10. Casing Seal/Installation N/A OPS 325
11. Service Line Installation SAT OPS 302
12. Tie-In/Hot Tapping SAT OPS 600 Bolt on tapping tee
13. Meter Location/Regulator Testing N/A OPS 302
14. Equipment Calibration Verification SAT OPS 501 Dates in folder
15. EFV Installation SAT OPS 301
16. MAOP N/A OPS 602
OPS 606
OPS 900
OPS 1000
17. Pure SAT OPS 603
18. Safety Equipment SAT SF 418
SF 422
19. Abandonment N/A OPS 607
20. Line Locating SAT OPS 611
IPUC Form 4 Rev. 12/21/2023
IPUC Construction Inspection
21. Plastic Pipe SAT OPS 307
-Joiner(s) Qualified OPS 309
- Fusion Tools OPS 324
-Heat Plate OPS 325
-Joining Procedure OPS 800
22. Steel Pine N/A OPS 200
-Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
-Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
4800
Additional Comments:
IPUC inspector Perkins observed Das-Co, a contractor for IGC Install 3/" service lines in Boise, ID.
Address: 2411 S Shoshone St Tlr 10/11/12
Observations Include: Fusing 3ea 3/" service risers/EFV's and associated piping, verification of OQ
records, tracer wire, trenching/backfilling, pressure testing, purging, and line locating. Quizzed
personnel on AOC's for bolt on saddle tee's. All observed procedures were followed in accordance with
IGC Operations and Maintenance Manual.
Corrective Action Required: Yes 1 No X
Follow-up Required: By Date Yes No X
Inspector(Lead): Date: 06/05/2024
Perkins
Reviewer:
Brooks Date: 6- �y
IPUC Form 4 Rev. 12/2v2023