HomeMy WebLinkAboutIntermountain Gas 240307.2 Meridian Construction I PUC Construction Inspection
Inspector(s): Galli Date(s): 03/07/2024
Company/Owner: Unit/OPID: 08160
Intermountain Gas Company IGC)
Address: Oaks North#12 City/District: Meridian
Contractor/Job#: Foreman: Employees: See Job List
317-3318 Justin Dicaprio
Job Description: Install 3/4" Service Line(s) System Type: ® Distribution ❑ Transmission
Operator Supervisor: Will Lynsey One-Call Ticket: 2024062110
On-Site: N
Total Inspection Days: 1.0
Tasks: Rating Critical Procedure# Comments
1. Materials—Handling, Storage, SAT OPS 11
Labeling
2. Trenching/Boring—Depth, Clearance SAT OPS 308
OPS 322
3. Bedding/Backfill N/A OPS 308
SF 418
4. Pipe Installation (Tracer Wire) SAT OPS 308
OPS 322
5. Valve Installation N/A OPS 703
6. Coating Condition N/A OPS 401
OPS 403
7. Manuals—Field Procedures, O &M SAT
8. Testing—Pressure, Duration, Type N/A OPS 505
9. OQ Qualifications SAT OPS 800 In folder
10. Casing Seal/Installation N/A OPS 325
11. Service Line Installation N/A OPS 302
12. Tie-In/Hot Tapping N/A OPS 600
13. Meter Location/Regulator Testing N/A OPS 302
14. Equipment Calibration Verification SAT OPS 501 Temp Gauge exp 2/2024
New Gauge 05/2024
15. EFV Installation N/A OPS 301
16. MAOP N/A OPS 602
OPS 606
OPS 900
OPS 1000
17. Pure N/A I OPS 603
18. Safety Equipment SAT SF 418
SF 422
19. Abandonment N/A OPS 607
20. Line Locating N/A OPS 611
IPUC Form 4 Rev. 12/2v2023
IPUC Construction Inspection
21. Plastic Pipe UNSAT OPS 307 Se Comments
-Joiner(s) Qualified OPS 309
- Fusion Tools OPS 324 (a
-Heat Plate OPS 325
- Joining Procedure OPS 800 _
22. Steel Pipe N/A OPS 200
- Welder(s) Qualified OPS 201
Pipe/Coating—Inspected/Repaired OPS 202
- Cathodic Protection OPS 306
-Non-Destructive Testing OPS 401
- Welding Procedures OPS 407
- Removal of asbestos wrap OPS 402
- Exothermic Welding OPS 403
4800
Additional Comments:
IPUC inspector Galli observed Crown Utilities a contractor for IGC install 2"main in the Oaks North
#12 subdivision in Meridian, ID.
Address: Oaks North#12 Meridian, ID
Observations Include: Correct trench depth, safety equipment, verification of OQ records, verification
of equipment calibrations, tracer wire and butt fusion. Quizzed employee on applicable AOCs of fusion
procedures.
Discrepancies and Violations:
• Observed an expired pyrometer dated 02/2024 and was replaced with an unexpired pyrometer
dated 05/2024.
• Observed contractor fuse a 2"pipe and end cap together without refacing after adjusting the
clamp. FOC Will Lynsey was notified and LOC I202403 will be written to IGC for failure to
comply with OPS 605, OPS 307 and TR-33. FOC instructed the contractor to cut out the fuse
and redo it.
Corrective Action Required: LOC I202403 Yes X No
FoRow-up Required: By Date: Yes X No _
Inspector (Lead):
Date: 03/07/2024
Galli
Reviewer:
Brooks Date: -9
IPUC Form 4 Rev. 12/21/2023