Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
20241008Clearwater to Staff 1 Attachment - Circuits and Meters for Separate CPD Consumption.pdf
PROPOSED POWER PASSTHROUGH DETAILS AROUND HOW WE WILL PASSTHROUGH ELECTRICAL COSTS FROM CLW TO SOFIDEL Avista and Clearwater Paper working together to present to the IPUCto allow for pass thru power billing. • Avista & CLW are proposing to keep the exchange how it currently exist. • Utilize internal data for the following breakers. • Breaker 7-3A (3L) • Breaker 7-3B (3L) • Breaker 8-3A (1 L, 2L, Converting & Warehouse) Request No. 1 : The circuits in question will completely separate Clearwater Paper and Sofidel. CLEARII PAPER ©Clearwater Paper Corporation 2024 1 METERS FOR PROPOSED BILLING PROCESS Currently have the following metering equipment in place to calculate energy usage (kwhrs) and peak demand (kva) for CPD. 7-3A — JEMS meter for measuring energy usage, SEL 751A relay used for measuring peak demand 7-313 — SEL 735 meter for measuring energy usage. SEL 751 A relay used for measuring peak demand 8-3A — JEMS meter for measuring energy usage, SEL 751 A relay used for measuring peak demand Output from these meters are compiled into a data historian (PI ). From here, the historical data is used to calculate total energy usage and peak 30-minute demand for the month . 7-3A 7-31B 8-3A Milli fJ oa Cj o m ® ii C `l IICLEAR PAPER WATER ff H ©Clearwater Paper Corporation 2024 2