Loading...
HomeMy WebLinkAbout20240909IPC to Staff 95(e) - Attachment 5 - MLPR200001 Unit 2 Commissioning.pdf IDIAW POWER® An IDACORP Company Milner Unit 2 Power Supply Electrical Engineering Excitation Initial Settings and Operational Commissioning Procedures October 2023 ©2023 Idaho Power Idaho Power Company Abbreviated Title Table of Contents Tableof Contents..............................................................................................................................i 1 Preparation.................................................................................................................................. 1 1.1 Project Information............................................................................................................. 1 1.2 Field Measurements........................................................................................................... 1 1.3 Equipment Verification....................................................................................................... 1 1.4 Initial DECS400 Field Setup&Load DECS Settings File....................................................... 1 1.5 IRIG&Networking Setup....................................................................................................2 2 Controls Checkout........................................................................................................................ 2 2.1 SEL-751A Relay....................................................................................................................2 2.2 DECS-400 Inputs..................................................................................................................3 2.3 DECS-400 Outputs...............................................................................................................3 3 SCADA List....................................................................................................................................3 4 Initial DECS-400 Settings..............................................................................................................3 4.1 Configure.............................................................................................................................3 4.1.1 Controller Logic Load.................................................................................................3 4.1.2 Rated Data.................................................................................................................4 4.1.3 Options.......................................................................................................................4 4.1.4 Auxiliary Inputs..........................................................................................................5 4.1.5 Meter Drivers............................................................................................................. 5 4.1.6 System Data...............................................................................................................6 4.1.7 Transient Boost..........................................................................................................6 4.2 Settings................................................................................................................................ 6 4.2.1 AVR/FCR/FVR............................................................................................................. 6 4.2.2 VAR/PF....................................................................................................................... 7 4.2.3 Startup.......................................................................................................................8 Internal Use Only Page i Idaho Power Company Abbreviated Title 4.3 Gain.....................................................................................................................................8 4.3.1 AVR Gains(Primary)...................................................................................................8 4.3.2 AVR Gains(Secondary)...............................................................................................9 4.3.3 FCR Gains...................................................................................................................9 4.3.4 FVR Gains...................................................................................................................9 4.3.5 Other Gains................................................................................................................9 4.4 Limiting.............................................................................................................................. 10 4.4.1 Configuration........................................................................................................... 10 4.4.2 Summing Point OEL(Primary).................................................................................. 11 4.4.3 Summing Point OEL(Secondary)............................................................................. 12 4.4.4 UEL(Primary)........................................................................................................... 12 4.4.5 UEL(Secondary)....................................................................................................... 12 4.4.6 Takeover OEL........................................................................................................... 12 4.4.7 SCL(Primary&Secondary)...................................................................................... 12 4.4.8 VARL(Primary&Secondary).................................................................................... 12 4.4.9 Scaling(Primary&Secondary)................................................................................. 13 4.5 Protection......................................................................................................................... 13 4.5.1 General Protection(Primary)................................................................................... 13 4.5.2 General Protection (Secondary).............................................................................. 13 4.5.3 24 Voltz/Hz............................................................................................................... 13 4.5.4 Loss of Sensing......................................................................................................... 13 4.5.5 EDM.......................................................................................................................... 14 4.5.6 Relay Setup.............................................................................................................. 14 4.6 Data Log............................................................................................................................ 15 4.6.1 Log Setup(Initial)..................................................................................................... 15 4.6.2 Mode Trigger............................................................................................................ 15 4.6.3 Log Selection............................................................................................................ 15 Internal Use Only Page ii Idaho Power Company Abbreviated Title 4.6.4 Level Triggers........................................................................................................... 16 4.6.5 Logic Triggers........................................................................................................... 16 5 Commissioning........................................................................................................................... 17 5.1 Operations Loading Summary........................................................................................... 17 5.2 Final Data Acquisition Summary....................................................................................... 18 5.3 Off-Line Tests—Turbine Spinning..................................................................................... 19 5.2.1 FCR Mode—Verify Field Voltage,Initial Field Voltage............................................ 19 5.2.2 FCR Mode—Step Response 2%............................................................................21 5.2.3 AVR Mode—Step Response 2%...............................................................................22 5.2.4 AVR Mode—Step Response 5%...............................................................................24 5.2.5 OEL—Offline............................................................................................................25 5.2.6 Soft Start..................................................................................................................26 5.2.7 Voltage Matching.....................................................................................................26 5.3 On-Line Testing.................................................................................................................29 5.3.1 Verification(Before Going Online)..........................................................................29 5.3.2 Synchronize the Unit................................................................................................29 5.3.3 AVR Mode-Light Load,Step Response....................................................................30 5.3.4 FCR Mode-Light Load,Step Response....................................................................31 5.3.5 Over Excitation Limit................................................................................................31 5.3.6 Under Excitation Limit.............................................................................................33 5.3.7 FCR Mode-Heavy Load,Step Response..................................................................34 5.3.8 AVR Mode-Heavy Load,Step Response..................................................................34 Glossary...................................................................................................................................36 Review/Revision History.........................................................................................................37 Internal Use Only Page iii Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 1 Preparation 1.1 Project Information • Project Server Location: \\FresnoPowerP rod uction\PIants_Hydro\17 MLPR Milner\Projects\2020-MLPRI2-AVR Upgrade-MLPR200001\Engineering-Commissioning\Unit 2 • Modeling Server Location: \\Fresno\powerproducton\Plants_Hydro\17 MLPR Milner\Condition Assessment and Info\NERC MOD\2023-MLPR2-MOD026 1.2 Field Measurements 1. ❑ Micro-Ohm Resistance Test,Value: mf2 @ 20°C o Original Value is 0.***f2 @ **°C o Manufacture Value is 1.1850 @ 25°C(This is a questionable value, very large but maybe) 2. ❑ Review Final Rotor I Test Report,Value: Mfg (Including Slip Rings,Initial Maintenance Record) 3. ❑ Complete final field measurements forms and save to SharePoint Site; Plant Condition Assessment Library-All Documents 1.3 Equipment Verification 1. ❑Verify Unit Style Number:DECS-400-1-C-5-U 0 1=PSS o C=125V(ac or dc) o 5=5A CT Secondary o U=Battery Backup for real-time clock. 1.4 Initial DECS400 Field Setup & Load DECS Settings File 1. ❑ Power Up DECS-400(If net Fi fy it tins been power cycled recently;f eg(Sting) 2. ❑ (New Only)Load Predefined Logic Scheme—Single DECS-400 without PSS. (Reference Figure 111 DECS400Instruction manual,Rev.U) 3. ❑ Load Initial DECS Settings File,or edit existing for pre-commissioning settings. 4. ❑ Verify Isolation Module wiring has:(Per Basler Drawings, 1302A) Internal Use Only Page 1 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure o Voltage on±125V o Shunt on 100mV&/800A 5. ❑ Update Field Rated Data with field DLRO Testing values.Use IR to measure temperature of the rotor not just the ambient air for temperature measurement. 1.5 IRIG & Networking Setup 1. ❑Verify IRIG physically Connected and Setup the IRIG Settings and adjust for MST. a. Communications->NTP Settings ❑Set the IP address to the NTP(Clock:unknown) ❑ Enable NTP(If using NTP) ❑Set Time zone offset to-420min.(UTC-07:00,MDT:UTC-06:00) b. Tools->Device Real-Time Clock ❑ Enable Automatically Adjust to Daylight Savings (UTC-07:00,MDT:UTC-06:00)Thus, IRIG UTC MDT 15:00 8:00 9:00 18:00 11:00 12:00 23:00 17:00(5pm) 18:00(6pm) 2. ❑ Modbus physical connection and verify communication. 3. ❑ Set or verify IP Address(If Network connected) 2 Controls Checkout This section would cover any additional checkout items beyond the initial checkout by the design and installation team. 2.1 SEL-751A Relay ❑ Review if new install.General review of controls and operations per standards. Internal Use Only Page 2 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 2.2 DECS-400 Inputs ❑ Review if new install.General review of controls and operations per standards. 2.3 DECS-400 Outputs ❑ Review if new install.General review of controls and operations per standards. 3 SCADA List There should be no changes to the SCADA 10 from the DECS. ❑Verify field data is being set to EMS from the Plant. ❑Verify the field data sent to EMS is also sent to PI and configured correctly. 4 Initial DECS-400 Settings 4.1 Configure If th., Rot hRr R occ -4 h„Alfr;4b'Pd Rpfpr@Rc;p the occ!'.....FA'SSi9R'Rg guide.This unit will not utilize a PSS due to the unit's capacity. 4.1.1 Controller Logic Load 1. ❑ Load logic into controller for single DECS without PSS. Internal Use Only Page 3 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 4.1.2 Rated Data 110. jQQ :c manufact rsd :OS: Standard ANSI 1� cYA ?over lnc:cr D® Noe. stood l38C0 5: Y Duty CCNT. Runevay speed l090 RPM 53i A Stator vI.k'ing 4yr Inertia Canst. 2.!? kHs/I VA ccnneCt:on 6J Hz Excitation 4!a A 95 V EEPhases Insulation class stator/fleld vdq. F/F %rect:cn of rotation seen from sliprinq s:ee Q Temperature rise above cold FAIR In stator v:nalrq: ® K. :n field v:ne:nq= SJ K 4.1.3 Options Setting Comments Voltage Sensing ABC 3-Phase Per281302A,All phases normal rotation. Field Type Main Field Static Exciter Bridge Control Signal -10V->+10V Standard Temperature Mode DEG.C Standard Underfrequency Mode V/Hz Standard Current Sensing Three Per 281102.dwg CT Sr' A-B Generator Frequency 60 Nameplate Voltage Matching Disabled At Startup, will enable during commissioning later. Internal Tracking Enabled Standard on single DECS to track between FCR and AVR modes. External Tracking Disabled This is used for Dual DECS designs. Inner Loop Field Regulator Disabled Internal Use Only Page 4 Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure 4.1.4 Auxiliary Inputs Setting Comments Input Type Voltage Summing Type Inner Loop g,,..,.��T,,..,.input ro«v��,.,.,,r� The Input Function Remote Setpoint Aux is not used. Aux Gain Settings used if using Aux control. AVR(Mode)Gain 1.0 FCR(Mode)Gain 1.0 FVR(Mode)Gam. 1.0 VAR(Mode)Gain 1.0 PF(Mode)C Droop Compensation Enabled,5% This is for parallel generators, otherwise Disabled. Line Droop Compensation Disabled,0% Cross Current Compensation Disabled,0% 4.1.5 Meter Drivers Setting Comments Meter Driver 1 Disabled No devices connected per 2813402A. System Parameter Metered .. Minimum Value .. Maximum Value .. Meter Driver 1 Disabled No devices connected per 2813402A. System Parameter Metered .. Minimum Value .. Maximum Value .. Internal Use Only Page 5 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 4.1.6 System Data Setting Comments Gen PT:Primary Voltage 14,400 Per281102 Gen PT:Secondary Voltage 120 Per281102 Gen CT:Primary Current 800 Per281102 Gen CT:Secondary Current 5 Per281102 Bus PT:Primary Voltage 14,560 Per281105/281107 Bus PT:Secondary Voltage 120 Per281105/281107 Internal Tracking Delay 1.0 Standard Internal Tracking Transvers Rate 3.0 Standard(2.0 is also used) External Tracking(Secondary) Not Used,for Dual Decs. External Tracking Transverse R Not Used,for Dual Decs Field Current Sensing:Shunt 800 Per 281302A Field Voltage Isolation Transducer 125 Per281302A 4.1.7 Transient Boost Setting Comments Transient Excitation Boosting Disabled Not used forWo. 4.2 Settings 4.2.1 AVR/FCR/FVR Setting Comments AVR Setpoint 13,800 Internal Use Only Page 6 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Min%(Rated) 95.0 Standard is 0.95, Verify with TO. Max%(Rated) 105.0 Per nameplate Transverse Rate 30 Standard 30. AVR Pre-Position 1 Setpoint 13,800 This brings it up to rated. Mode Release Transverse Rate/Enable Disabled Same as above if disabled. AVR Pre-Position 2 Setpoint 13,800 Mode Release Transverse Rate/Enable Disabled Some as above if disabled. FCR 20%of Rated Field Current to start. Setpoint (280) (416A x 20%=83A) SNL(2017)=^280A(MOD025,online) Min%(Rated) 20.00 Initial Setting for startup. Max%(Rated) 105.0 Standard 105.0 but may be adjusted later. Transverse Rate 120 60-200 been used.Standard 120. FCR Pre-Position 1 Setpoint 83 Initial Setting for startup Mode Release Transverse Rate/Enable Disabled FCR Pre-Position's Setpoint 83 Initial Setting for startup Mode Release Transverse Rate/Enable Disabled 4.2.2 VAR/PF Not Used Internal Use Only Page 7 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 4.2.3 Startup Setting Comments Primary Soft Start Level 25 Standard 25. Primary Soft Start Time 15 Standard 15. Secondary Soft Start Level Not Used(Make same as primary) Secondary Soft Start Time Not Used(make Same as primary) Field Flash Dropout Level 50 Standard 50. Maximum Field Flash Time 10 Standard 10.(up to 25) Voltage Matching Band 10.00 Standard 10.0 Voltage Matching(Gen-Bus PT) 100.2 Plant unit specific. Volts/Hz High Limiter 1.08 Standard 1.08 Volts/Hz Low Limiter 1.06 Standard 1.06 Volts/Hz Time Limiter 10.0 Standard 10.0 4.3 Gain 4.3.1 AVR Gains(Primary) Setting Comments Kp—Proportional Gain 80.0 default 80. Ki—Integral Gain 20.0 default20. Kd—Integral Gain default 40. (Rotating Exciters) Td—Integral Gain 00.1 default 0.01 Kg—AVR Loop Gain 15.0 default 15. Internal Use Only Page 8 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 4.3.2 AVR Gains(Secondary) Make these the same as the primary.Secondary is not used in controller,but just in case making them the same as the primary ensures the same control between them. Setting Comments Kp—Proportional Gain 80.0 Existing,default 80. Ki—Integral Gain 20.0 Existing,default 20. Kd—Integral Gain 90.0 Existing,default 40. (Rotating Exciter) Td—Integral Gain 0.01 Existing,default 0.01 Kg—AVR Loop Gain 15.0 Existing,default 15. 4.3.3 FCR Gains Setting Comments Kp—Proportional Gain default 0. Ki—Integral Gain default 0. Kd—Integral Gain default 0.(Rotating Exciter) Td—Integral Gain Nkdefault 0. Kg—AVR Loop Gain 1000 default1000. L in 4.3.4 FVR Gains Not Used. 4.3.5 Other Gains Setting Comments VAR Not used 1.0 Internal Use Only Page 9 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Kg—Loop Gain 0.0 PF Not Used Ki—Integral Gain 1.0 Kg—Loop Gain 0.0 OEL Ki—Integral Gain 1.0 Standard 1.0-15.0 Kg—Loop Gain 20.0 Standard 2.0-35.0 UEL Ki—Integral Gain 1.0 Standard 1.0 Kg—Loop Gain 20.0 Standard 2.0-20.0 SCL Not Used Ki—Integral Gain 1.0 g—Looplabb, 0.0 Voltage Matching Kg—Loop Gain 2.0 Standard 1.0-3.0 When inner loop selected in the Inner Loop Field Regulator Settings/Auxiliary Input/Summing Type,then this gain is enabled. Ki—Inner Loop 0.0 Standard.0.0 Kg—Inner Loop 1.0 Standard.1.0 VARL Not used? 1.0 Kg—Loop Gain 0.0 4.4 Limiting 4.4.1 Configuration Setting Comments Limiter Modes Internal Use Only Page 10 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure OEL Enable Standard. UEL Disable UEL will be enabled in commissioning later. SCL Disable VARL Disable DEL Mode Summing Point Standard OEL Voltage Dependency Disabled dv/dt Level Disabled This is enabled by enabling the voltage dependency. UEL Mode Summing Point Standard UEL Voltage Dependency Real Power Exponent 0.0 Typically,0.0,but also 1.0 can be used. Real Power Filter Time 5.0 Typically,5.0 Constant 4.4.2 Summing Point OEL(Primary) Setting Comments Offline See IEEE C50.13 standard/PRC-019 Initial Set at 15%rated gen volt. High Level 322 280A x 1.15=322A Estimated 370A Field=1.05pu Gen Volt High Time 2 Standard. Initial Set at 10%above rated gen volt. Low Level 308 280A x 1.10=308A May need to be adjusted later. On-Line Fir See IEEE C50.13 standard/PRC-019 High Level 581 Initial set at 140%above rated field High Time 3 Initial set at 3.Os Medium Level 518 Initial set at 125%above rated field Medium Time 10 Initial set at 10.Os Low Level 477 Initial Set at 115%above rated field Internal Use Only Page 11 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 4.4.3 Summing Point OEL(Secondary) Not Used,set same as Primary. 4.4.4 UEL(Primary) This controller function needs to be coordinated with PRC-019. Setting Comments Primary UEL Matched EMS UEL. Curve Selection mWernal Point Selection 5 Points 1:Real Power/Reactive Power 0/7.62k 12.7MVA x 60%=7.62MVar Points 2:Real Power/Reactive Power 2.54k/7.62k 12.7MW x 20%=2.54MW Points 3:Real Power/Reactive Power 7.62k/6.858k 12.7MVA x 54%=6.858Mvar Points 4:Real Power/Reactive Power 11.43k/5.715k 90%and 45%respectively. Points 5:Real Power/Reactive Power 15.2k/0 1.2 x 12.7MW=15.2MW **The values originally selected are above capability curves values from manufacture, trimmed to match existing EMS curve until PRC-019 has been reviewed. ** 4.4.5 UEL(Secondary) Not used,same as Primary. 4.4.6 Takeover OEL Not Used. 4.4.7 SCL(Primary&Secondary) Not Used. 4.4.8 VARL(Primary&Secondary) Not Used. Internal Use Only Page 12 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 4.4.9 Scaling(Primary&Secondary) Not Used. 4.5 Protection 4.5.1 General Protection(Primary) In general,the excitation controller unit protection functions are not used.The unit protection is served by a separate relay protection system.Typically alarms and tripping from this controller would be internal only to the excitation system. Setting Comments Generator Overvoltage Disable Standard Field Overvoltage Disable Standard Loss of Field Iso.Transducer Enable Standard Delay 1.0 Standard Generator Undervoltage Disable Standard Field Overcurrent Disable Standard. Power Supply Low Enable Standard(Mixed depending on site upon review) Loss of Field Disable Standard Field Over Temperature Enable Standard Pickup Level 130 Typical130 Delay 60 Typical60 4.5.2 General Protection(Secondary) Same as Primary. 4.5.3 24 Voltz/Hz Disabled. 4.5.4 Loss of Sensing Setting Comments Internal Use Only Page 13 Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure Option Enable Standard Balanced Level 50.0 default Unbalanced Level 20.0 default Delay 2.0 default Transfer to Manual Enable Standard 4.5.5 EDM Not Used. 4.5.6 Relay Setup Setting Comments Relay#1 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#2 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#3 IV Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#4 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#5 Internal Use Only Page 14 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#6 Contact Status Normally Open default Contact Type Maintained default AL Momentary Time 0.10 defau 4.6 Data Log 4.6.1 Log Setup(Initial) Setting Comments Data Logging Enabled Enable This sets up for the first energization data capture for 30.0s. Pre-Trigger Points 49.992 Sample Interval 20.0 4.6.2 Mode Trigger Setting Comments Start/Stop Mode Start Limiter Mode UEL&OEL Test Mode Enabled All other triggers not identified are not used. 4.6.3 Log Selection Setting Comments Internal Use Only Page 15 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Parameter 1 Generator Average Voltage Parameter 2 Field Voltage Parameter 3 Field Current Parameter 4 Generator Real Power Parameter 5 Generator Reactive Power Parameter 6 Control Output 4.6.4 Level Triggers No triggers are enabled. 4.6.5 Logic Triggers Setting Comments Alarm States None enabled Relay Outputs Enabled Watchdog Enable Relay Output 2 Contact Inputs FCR(Manual) Enable Switel.Input 7 A4onuol OCC Internal Use Only Page 16 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 5 Commissioning 5.1 Operations Loading Summary Table 1.Loading Summary for AVR Commissioning Section Test Loading Flow Unit Control Schedule 5.2.1 Initial Field Energization Offline,Rated Speed 90cfs Manual 5.2.2 FCR Voltage Response Offline,Rated Speed 90cfs Manual Day 1 5.2.3,4 AVR Voltage Response Offline,Rated Speed 90cfs Manual 5.2.5 Offline OEL Response Offline,Rated Speed 90cfs Manual 5.2.6,7 Soft Start/Voltage Matching Offline,Rated Speed 90cfs Manual OnlineSNL 90cfs Offline,Rated Speed 90cfs 5.3.2 Synchronizing Manual OnlineSNL 90cfs 3MW,2%Variable Vars 300cfs 5.3.3 AVR Voltage Response Manual 9MW,2%Variable Vars 750cfs Day 2 3MW,2%VariableVars 300cfs 5.3.4 FCR Voltage Response Manual 9MW,2%Variable Vars 750cfs 5.3.5,6 DEL,UEL Limits 3MW,Variable Vars 300cfs Manual 5.3.7 FCR Voltage Response BMW,5%Variable Vars 650cfs Manual 5.3.8 AVR Voltage Response BMW,5%Variable Vars 670cfs Manual 1MW/Unity,±2.5MVar 150cfs 2.5MW/Unity,±2.5MVar 250cfs S.OMW/Unity,±2.5MVar 450cfs 5.4 V-Curve Validation Manual Day 3 7.6MW/Unity,±2.SMVar 650cfs 10.2MW/Unity,±2.5MVar 850cfs 12.5MW/Unity,±2.5MVar 1110cfs *No saturation test is to be performed.Manufactures saturation information will be utilized for modeling and verification. Internal Use Only Page 17 Idaho Power MLR2-Initial Setup&FCR/AVR Commissioning Procedure 5.2 Final Data Acquisition Summary Table 2.Summary of Data Acquisition Step Time Step Pre-Trigger Sample Section Test/Record Method' Magnitude' Delay' Duration' Points' Interval' 5.2.1 Initial Field Energization Start Mode 25 49.992s Trigger 5.2.2 Offline FCR Voltage Response Manual Step - 60 16.664ms Response 5.2.3,4 Offline AVR Voltage Response Time Response 2.0% 0.5s 6.0s 25 16.664ms 5.2.5 Offline OEL Response Time Response 2.0% 0.5s 6.0s 0 16.664ms Auto Soft Start/Voltage Start Mode 5.2.6,7 Matching Trigger 25 49.992s 5.3.2 Auto Synchronizing Logic Trigger - - - 300 49.992s Input Switch 31 5.3.3 Online AVR Voltage Response Time Response 2.0% 0.5s 9.0s 0 24.996ms (Light Load) Online AVR Voltage Response Time Response 2.0% 0.5s 6.0s 0 24.996ms (Heavy Load) 5.3.4 Online FCR Voltage Response Manual Step 20 24.996ms (Light Load) Response Online FCR Voltage Response Manual Step (Heavy Load) Response 20 24.996ms 5.3.5,6 OEL Limits-Control Response Time Response 2-5.0% 0.5s 26.0s 10 49.996ms XX UEL Limits-Control Response Time Response 2-5.0% 0.5s 31.0s 10 49.996ms FCR Voltage Response(Stability 5.3.7 5%) Time Response 5.0o� 0.5s 9.0s 20 24.996ms 5.3.8 S/)Voltage Response(Stability Time Response 5.0% 0.5s 9.0s 20 24.996ms 5.4 V-Curve Validation Manual/Operator - Note 1. Selected within the DECS-400 Analysis Time Response Menu. 2. Input switch 3 is the generator breaker closure input. 3. Selected within the DECS-400 Log Setup Menu. 4. Response method or DECS logic operator in Analysis menu Internal Use Only Page 18 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 5.3 Off-Line Tests—Turbine Spinning 5.2.1 FCR Mode-Verify Field Voltage,Initial Field Voltage This task is to ensure proper gate operation,field flash,and general operation.Initial start-up in manual mode. ❑ Perform a final walkdown prior to spinning and flashing the field. 1. ❑ Switch to FCR Mode There have been times when the current is not enough and the unit will fail to build. Review the open circuit saturation results from the manufacture or previous testing.In 2017 data was collected and the field current was 287A,at 1.6MVA unity loading.83A may not cut it as noted from the Basler manual. 2. Go to Settings->AVR/FCR/FVR a. Adjust Field Current Regulator(FCR) i. ❑ Setpoint(20%)=415A x 0.20=83A ii. ❑ FCR Pre-position 1(20%)=83A iii. ❑ FCR Pre-position 2(20%)=83A 3. Manually Start the DECS400(generator should build to percentage of rated voltage) a. ❑ Use a fluke to verify the voltage is firing correctly. May need to raise the voltage if 20%is not sufficient,see step 4. b. ❑ Capture all diodes firing within the waveform and record. 4. ❑ Increase the field current until 100%rated terminal voltage is reached. a. The OEL limiter should limit the current to Rated Field Current x 75%=311A(Or use past MOD data, refer to the initial settings tables). According to Limiters->Summing Point OEL.Adjust this if needed. b. Record the: i. No load field current: A ii. No load field Volts: V c. Manually adjust the voltage to 2%above rated. 13.8kV x 1.02=14.076kV,this will provide the field current required for manual step responses in FCR mode. i. Rated+2%field current: A ii. (Rated)/(Rated+2%)_ % 5. Go to Meter->Operation a. Verify the phase angle,positive and negative sequences to make sure values look correct. Internal Use Only Page 19 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure i. ❑There should be little negative sequence values,if there are,a CT or PT might be rolled. ii. ❑ General review of field current and generator voltage. iii. ❑ Verify any protective relays are reading correct.(SEL-751A) 6. ❑Verify the field temperature appears accurate.= C at startup 7. ❑ Verify the phasing looks accurate. Internal Use Only Page 20 Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure 5.2.2 FCR Mode—Step Response 2% This is to determine the stability of the excitation system in manual mode. The difficulty in this test is the know how far to change the percent of field current. Manually raise the voltage 1. Setup the data log to capture the test results. a. Go to Data Log->Mode Triggers „; E Notes Ccmn ications Tools window Help 2. Enable Test Mode •�E`Corrf9— S.M. Gain tinni Pmta— ISS for this. Malys. Data Log M— 1o9. m� �I�� Log Setup Mode Triggers I Log Selection I Level Triggers I Logic Triggers Trending llllllll Start DELII SCL NDTRIGGER . Fq TRIGGER NO TRIGGER •• .TRIGGER - tb TRIGGER ,• . .TRIGGER P10 TRIGGER IJO TRIGGER P10 TRIGGER Enabled NO TRIGGER NO TRIGGER 9 b. Go to Data Log >Log Setup ja 1,1, Notes Y� Configure Settings Gain L.d— Proletlbn I PSs m m ✓ L�-I �j L ?nalysis Dale Log Me[a lnpc L J S-h+P I Mode TTriggers I Log Selection I Lad Triggers Logic Triggers I T.ndirg Uim Sele.ace Of Evert r Dala Lo9gin9 Enabled 50 Pre-Trigger Points Mew/Donaio�Data ® Pre-Trigger Duration(sec) Dansioed Trend ®i Pent-Trigger Pains ® Post-Trigger Duration{see) za 9% Swoe Interval{mil ® ToW Duration{sec) c. Go to Data Log->Log Selection Internal Use Only Page 21 Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure 'g Notes `i Configure Settings Gain L.ft— Rdaclm I Pss A ICI Wj Maysis Data Log Meer Lajc Logs-1-pi Mode Triggers Log Selection I Level Triggers I Logic Triggers I Trending I Generator Average Vollage w) Generator Real Power{pu) Feld Vokage{Du) lGenerator Reactive Power(pu) Feld Current(pu) ITime Response W) 2. ❑X Go to Analysis->Step Response to perform an FCR step response(Must use Step Response within the Analysis Menu) a. Set a 2%step L Check trigger data logging on step change ii. Decrease the value iii. Increase the value b. Review the step response,the response should be very stable 3. ❑X Go to Analysis->Step Response to perform an FCR step response(Must use Step Response) a. Set a 5%step L Check trigger data logging on step change ii. Decrease the value iii. Increase the value b. Review the step response,the response should be very stable 4. ©Test the OEL response,drive the FCR 5%into the OEL. 5. ❑x Stop the AVR 5.2.3 AVR Mode—Step Response 2% [description] 1. © Setup Data Logger a. Go to Data Log->Log Setup Internal Use Only Page 22 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure in File 'view Communication; Tools Window Help L mote et� Coniigse I Seeing. I Gan I Lmit. Protection I PSS S m ® ,�} Analysis Data Log Miler Logic Log Setup I Mode Triggers I Log Selection I Level Triggers I Logic Triggers I Trending s- - View Sent..of Eveds r Data Logging Enabled —50 M./Download Data Log Pre-Trigger Points t t® Pre-Trigger Duration;sec) DowrdoM Triad Log Post-Trigger Pants Post-Trigger Duration,sec) 16 kq Sample Interval(ms) Total Duration(sec) 2. ❑x If not already in AVR mode,Transfer to AVR mode 3. ❑x Start the AVR if not already on. 4. © From Analysis screen setup and run a Time Response Test as shown: Test Signal Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings 0.5 Fo AVR Summing Step . Sweep Type Start Frequency I— PSS Comp Frequency Linear Ssvee .Q5 Q0 r PSS Electric Power Sta t2.0 tude(�') 0.D00 Offset(�) ' r PSS Derived Speed Frequency Step Stop Frequency Exit I— Manual Summing Frequency(Hz) Duration(Sec) 0.001 3.OD0 r VARIPF FO.000 5.0 a. 5. ❑X Adjust PID settings as needed.Go to Gains->AVR Gain a. Adjust KID to display a good rise b. Adjust Ki to be about%to 1/5 of Kp c. Adjust Kg until we have about a.3 second response time(Rise Time) d. Add info about the rotating exciter.... Internal Use Only Page 23 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure VP Commented[Al]:Kg is the rise time,Vc is the set point. VREF + E --AR` KG KP + E II VR VRLMT/VP + VC K s 0 sKp 1 +sTp e. Commented[A2]:Basler mentioned this may be to much.1 5.2.4 AVR Mode—�tep Response S* believe rich and I experienced that as well. 1. ❑x Setup Data Logger a. Go to Data Log->Log Setup _t-ESTCOMS-DECS400-[Data Log] File View Communications Tools Window Help a, Calque Settings Gain Limier Protection P55 m '--, �p Aralyas�_ Data Log Mete Lope Log Setup I Mode Triggers I Lop SelMion I level Trippers I Logic Triggers I Trading I s- View Sepumce Of Evenb W Data Logging Enabled -50 Pra-Trigger Pants View i DowrioW Data Ui➢ ® Pra-Trigger Duration{sec) Dowiload Trerd Log ® Post-Trigger Pants Post-Tngger Duration isec) 21.9% Sample Interval{msl Total Duration ism) b. 2. ❑ If not already in AVR mode,Transfer to AVR mode. 3. St -, the A °already running 4. ❑x From Analysis screen setup and run a Time Response Test as shown: Internal Use Only Page 24 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Test Signal Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings 0.5 F7 AVR Summing Step Sweep Type Start Frequency r PSS Comp Frequency Magnitude(%) Offset(dc) Unear Sweep 0.050 Start r PSS Bectric Power r PSS Derived Speed 5.0 O.D00 Frequency Step Stop Frequency "" I ( r Manual Summing Frequency(Hz) Duration(Sec) 0.001 3.OD0 ` r VAR'PF O.D00 5.0 a. 5. Adjust PID settings as needed a. Adjust Kg until we have about a—0.3 second response time. 5.2.5 OEL—Offline This is the testing to ensure the OEL is operating correctly. 1. ❑X Go to meter a. Note the current value for Ifd:842A @ 14.400kV 2. ❑X Go to Limiters->Configuration a. ❑X Check OEL Enable 3. Go to Limiters->Summing Point OEL a. ❑X Change the Off-Line High Level to 10%higher than the value recorded in step 1,w/delay of 5 seconds(Original 10 seconds).Ifd(842A)x 1.10=926A(Original 880A for both,0 seconds) b. 0 Change the Off-Line Low Level to 2%higher than the value recorded in step 1, Commented[A3]:Found the 5%was to much,changed to Ifd(842A)x 1.02=858A(Original 880A) 2 4. Go to->Settings->AVR/FCR/FVR a. 0 Increase the field current by increasing the voltage setpoint,so it is above the low level setting programmed in step 1. i. This should slowly move the field current into the over excitation limit and after the delay time should move the field current to the low level setting.(Record Terminal Voltage:14.400kV (commented[A4]:What is this for? ii. Make sure that the response is stable. 1. If not: Go to Gain->Other Gain a. Adjust OEL Kgl Commented[A5]:Have a note to adjust Data Log ❑Verify Stable 5. Once stable,Go to Analysis Screen Internal Use Only Page 25 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure a. Setup graphs with i. Vavg ii. Ifd b. Setup a Time Response as shown Test Signal Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings 1.0 F AVR Summing Step Sweep Type Start Frequency F PSS Comp Frequency Magnitude(G) Offset(dc) Unear Sweep - F r PSS Electric Power r PSS Derived Speed 5.0 F 0.000 Frequency Step Stop Frequency 5tit r Manual Summing Frequency(Hz) Duration(See) � 1.000 r VAR,'PF p.ppD I LV C. d. Start the Time Response test i. Should see the current limit come in and control the field current to the OEL setpoints.If the response time seems too slow increase IKgI Commented[A6]:How long should it take?I had it at about 1. Go to Gain->Other Gain 6-8sec a. OEL Ki-Adjust from 1.0 to 1.5(Original 1.0) b. OEL Kg-Adjusted to 20.0 from 25(Original 25.0) 6. ❑X Return OEL Values to their starting values 880A/Os/880A 5.2.6 Soft Start 1. ❑ Stop the AVR and make sure it is in AVR Mode 2. ❑ Start the AVR from the analysis screen commented[A7]:The DECS will record a record for the a. El Verify the Soft Start in the graph for primary values start of the AVR,use the 49.992 sample interval i. Soft start level: 25 ii. Soft Start Time: 15 3. ❑ Record the startup and save.(50-pre,49.9ms Sample,29s Duration) a. File Name:"HCPR33 Softstart Offline OffOn" We merged the Soft start and the Voltage matching records. 5.2.7 Voltage Matching 1. ❑x Transfer to AVR Mode 2. Set voltage matching here. 3. ❑x Start the AVR 4. Go to Configure->Options a. © Enable Voltage Matching Internal Use Only Page 26 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 5. Go to Settings->Startup a. ❑X Set band to:5(standard is 10,left it tight) b. ®Set Gen to Bus PT match level to:100.0(standard is 100.2,but left at 100 since voltage is high normally) 6. Adjust the setpoint to the upper end of Voltage matching level(Adjust to 14.4kV) a. 0 Verify it reduces the voltage to match commented[AS]:wejustwatched ittrack it. b. If the response Its too slow or too fast Commented[A9]:How fast do we want it?We left it 3.0 i. Go to Gain->Other Gain bliss gain was 1.0 1. Adjust Voltage Matching Kg Commented[A10]:Played with different values 1 to 3(unit 7. Adjust the setpoint to the lower end of Voltage matching level(Adjust to 6.5kV,90% 2).....Set Unit 1 to 3. rated) a. ❑Verify it brings the voltage up to match b. If the response is too slow or too fast i. Go to Gain->Other Gain 1. Adjust Voltage Matching Kg 8. ❑Adjust the setpoint outside the voltage matching to see that it does not automatically adjust the voltage for both above and below the Min/Max of rated(Value in the Settings->AVRI) Commented[All]:The decs does not like the values outside the window. We watched it,did not do all the steps. Internal Use Only Page 27 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 5 7 l?/1r.er. c..r.....f:.,., !'...-..e (a d.d:t:eRal test) Nn#n•Be r• ..+:n..r and iyat h the terminal.elF•,nn make r l.e i#deer not net en..n 1 r17 o/c of rated voltage(1 c A9" ' 1 n T n 94 yeltage Mateh'n Ig 2. We had to Fall out the Rele..7 96E test feel. n+l.n....i. it trip nn 19SS nF re RSinn 'Ale have d4i;ahled the.101A Af';PRS*Rg voltage OR the plceteetdeR(Fealized that 3. Settle Data II egger a. ce to Data Leg .Ian Setup --d, Window Help d Configure Settings I Gan I Linters I Protection PSS A.*. Data Log I Meter Logic Log Setup I Mode Triggers I Log Selection I L.1 Triggers I Logic Triggers I Trending s• View Sequence Of Events F74 Data Logging Enabled 10 Pre-Trigger Points Mew/Download Data Log r r•r Pre-Trigger Duration(sec) Download Trend Log Post-Trigger Points Post-Trigger Duration(sec) i Ao4.Dm - Sample Interval(ms) .I r Total Duration(sec) b. /I GE)to Ce#+inne >C#erWn a. Adjust the¢eft Start se++'n gs i. Seft StaFt Level--2(ariginal�value- � ii. 994 Sitaf+Tea—60(QlCigiRai.-'We— Z 5. r_a+e cE?ttiR.e >Avo/Pro/W i. SSe peiR.. 15,2l1�Tginal..�-1�rlvt i AVR°irepesit'nn 1 - 115,200 Tgin l�value--13,9 OFF PGR°rr�e5itiGIR 2—19,209=(9,+g+Rel„• „a—13,809T) Commented[Al2]:Not sure why I need this. 6 n G-e+e cettiR e >Sta Ft e a. Adjust Volts/Hz Limiter Settipgs i. V{HZ High L Fe-_1.12 (GF*g+R l Imo, a-1.0�4 7—r'e+e I irni+e . QeRfig e+'e a. I Ine heel.QEl ERab!L- Commented[A33]:Keep,the values are large. Internal Use Only Page 28 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure a. get the gFaph-r te me—Rite-IF Vavg:Average Voltage 1-1­ FrA__R;the sGFeeR stak the gFaph. The veltage and field cwwFept should be the c.,F+r+ter+r+a+.,-,..rl rl.....1..ram.....the Fi..lrl e.err,,..+and+.,r...i..-,I....I+-,..., Commented[A14]:Update with actual method. 17 Rpt,,r..-.II settiRgs te their eFigiRal values. h n WH i!Values e. n Lomoter OE- 5.3 On-Line Testing 5.3.1 Verification(Before Going Online) 1. Setting Group Logic. a. In most machines this is disabled. But at HCPR and BLPR5 it is utilized and this should be left on to start???? 2. Go to PSS->Configure a. ❑X Verify enable box is unchecked 3. Go to PSS->Control a. ❑X Verify PSS Control is unchecked 4. Go to Meter->Operation a. ® Verify the phase angle and positive and negative sequences to make sure values look correct. i. There should be little negative sequence values,if there are,a CT or PT might be rolled. 5. ® Transfer to AVR Mode(May already be in AVR mode) 6. ❑x Verify the BUS PT signal is correct and make any adjustments to the Bus PT ration on the System Data tab. 5.3.2 Synchronize the Unit 1. ❑X Transfer to AVR Mode Internal Use Only Page 29 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 2. © Make sure the unit startup is in manual mode 3. ❑X Start the unit 4. © When up to speed,start the AVR(This may be in Auto to check 95%and matching) a. Monitor the Voltage level to make sure it does not overshoot too much. 5. © Close the breaker when it is appropriate(operator in manual) 5.3.3 AVR Mode-Light Load,Step Response 1. Setup Data Logger a. ❑X Go to Data Log->Log Setup J@ _ -, M rp. _ C,t,r .nl.a+lnrr. Tnnh Window Help a Configure Settings Gan I Li0en I Rdis bm PSS N ro m Maysis Data Log Meter Logic _ Log Setup I Mode Triggers I Log Selection I Level Triggers I Logic Triggers I Trending a- - Mew Sequence Of Events W, Data Logging Enabled � View/Download Data Log I Jy Pre-Trigger Pants Pre-Trigger Duration(sec) _ Download Trend Log Post-Trigger Pants Post-Trigger Duration(seci Sample Interval(msi Total Duration(sm, b. 2. 0 Unit should be online and loaded to about 20% a. 0 Make sure to adjust load to avoid any rough zones 3. 0 Verify Unit is in AVR Mode 4. 0 From Analysis screen setup and run a 2%Time Response Test as shown: Test Signal Time Delay Signal Input Stabilizer Test Signal Se eep Signal Frequency Settings 0.5 P-1 AVR Summing Step _ Sweep Type Start Fregtxncy r PSS Comp Frequency Magnitude(4) Offset(de) JLinear Sweep 0.050 Start r PSS Electric Power r PSS Derived Speed 2.0 0.000 Frequency Step Stop Frequatcy bat r Manual Summing Fray(Hz) Duration(Sec) 0.001 3.000 r VAR'PF 0.000 5.0 a. S. Adjust PID settings as needed and retest 2%if parameters are changed. a. Kp affects raise time Commented[A15]:If these are changed you have to go back and re verify the offline effects,and update the b. Kg affects response time, records. Internal Use Only Page 30 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure G n if„ „te Fs aFe „table at the test. .ith -.5 Time Respe„se test 7 Adjust oin settings Of needed and retest_5% Of parameters are changed. — Commented[A36]:Same if you adjust,will need to retest 8. © Download file:"Online 2MW-AVR Mode-Step Response-2%Up-Down" lower levels. 5.3.4 FCR Mode-Light Load,Step Response 1. Setup Data Logger a. ❑x Go to Data Log->Log Setup 2. ❑X Perform a 2%step response 5.3.5 Over Excitation Limit OEL test reference in Basler manual pg. 146 --------------------------------------------- CC Cured Level U T eeuneft tt a.a-3aPtle W err= I Leval LL rr)--v oconmucw CuieRoa-2oAdr t}l0eec o-1 Xsec Level a.a-15 AdC TIME IN SECONDS °'o.aioi Figure 3-10.Summing Point,On-Line Overexcitation Limiting Figure 1.Basler IL DECS-400. 1. © Load Machine to—10%(14.5 MW)—We are at 301MW. 2. Go to meter a. Note the current value for Ifd:834A(14AW),(-7MVar) 3. Go to Limiters->Configuration a. ® Check OEL Enable 4. Record Original On-Line Values 1480 High Level Internal Use Only Page 31 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure 5 High Time 1465 Medium Level 15 Medium Time 1450 Low Level 5. Go to Limiters->Summing Point OEL a. ❑X Change the On-Line High Level to 15%higher(959A)than the value recorded in step 2 w/delay of 5 seconds. b. ® Change the On-Line Medium Level to 10%higher(918A)than the value recorded in step 2 w/delay of 5 seconds c. © Change the On-Line Low Level to 5%higher(876A)than the value recorded in step 2. 6. Go to->Settings->AVR/FCR/FVR a. ❑ Increase the field current by increasing the voltage setpoint,so it is above the medium level setting programmed in step 2. 1 did a 5%step into the OEL. i. This should slowly move the field current into the over excitation limit and after the delay time should move the field current to the low level setting. ii. ❑X Make sure that the response is stable. 1. If not: Go to Gain->Other Gain a. Leave OEL KI at 1.0 1 set the KI to 1.5 Commented[A17]:This is how others are,why? b. ❑X Adjust OEL Kg Made no adjustments. Commented[A18]:Seemed stable as is. 7. Once stable,Go to Analysis Screen a. Setup graphs with i. Vavg ii. Ifd b. Setup a Time Response as shown Test Signal Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings AVR Summing Step 1.0 Sweep Type Start Frequency r PSS Comp Frequency r PSS Electric Power Li Magnitude(4) Offset(dc) near Sweep 1.000 Start r PSS Derived Speed 5.0 O.ODO Frequency Step Stop Frequency E�dt r Manual Summing Frequency(Hz) Duration(Sec) � 1.000 10.000 r VAR PF 0,0D0 I 20 C. d. Start the Time Response test Internal Use Only Page 32 Idaho Power IVLR2—Initial Setup&FCR/AVR Commissioning Procedure L Should see the current limit come in and control the field current to the OEL setpoints.If the response time seems too slow increase Kg 1. Go to Gain->Other Gain a. ❑Adjust OEL Kg 2. ❑X Download Record:"Online**MW—AVR Mode—OEL Test 5% Step Up-Down 8. ❑X Return OEL Limiter Values(Primary and Secondary)to their Initial settings values 5.3.6 Under Excitation Limit UEL test reference in Basler manual pg. 146 1. Go to Limiters->Configuration a. ❑X Uncheck UEL Enable b. ❑ Record Existing Values Primary 5—dary Customized Cove Sdedion C'3 Point r 5 Point 1 tOC.650 1 5 ,, Z 101.500 Z 101.5, 3 A.750 3 130.500 A 5 ,, d 169.650 5 F 5 C. 2. Go to Limiters->UEL(Starting at 7,500 War) a. ❑ Change reactive power limit value to 5%Vars into the machine(about 11,000 War) 3. Go to->Settings->AVR/FCR/FVR a. ❑ Decrease voltage setpoint until about 15%to 25%of Vars into the machine (about 600 kVar)I Commented[A19]:Not needed? 4. Go to Limiters->Configuration a. ❑X Check UEL Enable 5. Go to Analysis Screen a. ❑ Setup graphs with i. Vavg ii. Kvar b. Start the graph Internal Use Only Page 33 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure L IShould see the UEL come in and control the field current to the OEL setpoint. If the response time seems too slow increase Kg Commented[A20]:comes in pretty fast then it brings the 6. Go to Gain->Other Gain field current back pretty quick. a. IOEL Kg Commented[A21]:???? b. ❑X Download Record:"Online**MW—AVR Mode—UELTest 5%Step Down-Up" 7. ❑X Return UEL Settings to their starting values(Roughly 80%of Rated Machine MVA) 5.3.7 FCR Mode-Heavy Load,Step Response 5.3.8 AVR Mode-Heavy Load,Step Response 3. Setup Data Logger a. ® Go to Data Log->Log Setup ]@ File 'View Communications Tools Window Help Fthe nted[A22]:I used a longer sample since it seems i current was slower from light test.I wanted to Ct. Smnp Gain Limiters Protection PSS it a11. m L*A * Analysis Data Log Miler Logic Log Setup Mode Triggers I Log Selection I Level Triggers I Logic Triggers I Trending s I View Sequence Of Everts W_ Data Logging Enabled View/Dowdoad Data Log 5p Pre-Trigger Points t® Pre-Trigger Duration isec) Dmroad TreW Log Post-Trigger Points Post-Trigger Duration isec) 16.664 Sample Interval ims) Total Duration isec, b. 4. ❑x Unit should be online and loaded to about 80%-100%. a. ❑x Make sure to adjust load to avoid any rough zones 5. ❑X Verify Unit is in AVR Mode 6. ❑X From Analysis screen setup and run a-2.0%Time Response Test as shown:(we did a +2%) Internal Use Only Page 34 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Test Signal Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings 0.5 Po AVR Summing Step Sweep Type Start Frequency F PSS Comp Frequency Magnitude(%) Offset(dc) JLinear Sweep Y 50 Start r PSS Bectric Power r PSS Derived Speed -2.0 0.000 Frequency Step Stop Frequency but r Manual Summing Frequency(Hz) Duration(Sec) O.OD1 3.OD0 F VAR/PF O.ODO 15.0 a. 7. ❑x Adjust PID settings as needed and retest 2%if parameters are changed. a. Kp affects raise time b. Kg affects response time 8. ❑x If parameters are acceptable,repeat the test with a 5%Time Response test 9. ®Adjust PID settings if needed and retest 5%if parameters are changed. 10. © Download file:"Online**MW-AVR Mode-Step Response-2%Down-Up" a. And%5 Send DECS configurations file to PRC-19 custodian. Appendix? Enter the appendixnumber above its caption and apply the"Caption Appendix No"style.Enter the caption for the appendix below its number and apply the"Caption Appendix"style. (appendix info goes here) Internal Use Only Page 35 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Glossary Instructions for glossary terms:Turn on bold(Ctrl+b),key the glossary term,insert an em dash (with Num Lock on,press Alt+0151),turn off bold(Ctrl+b),then key the definition.See the following sample. Glossary Term—This is a sample.This is a sample of a formatted glossary term.This is a sample. This is a sample of a formatted glossary term. Internal Use Only Page 36 Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure Review/Revision History This document has been approved and revised according to the revision history recorded below. Review Date Revisions Mm/dd/yyyy Document was implemented. 14 Internal Use Only Page 37