Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout20240909IPC to Staff 95(e) - Attachment 5 - MLPR200001 Unit 2 Commissioning.pdf IDIAW
POWER®
An IDACORP Company
Milner Unit 2
Power Supply
Electrical Engineering
Excitation Initial Settings and Operational
Commissioning Procedures
October 2023
©2023 Idaho Power
Idaho Power Company Abbreviated Title
Table of Contents
Tableof Contents..............................................................................................................................i
1 Preparation.................................................................................................................................. 1
1.1 Project Information............................................................................................................. 1
1.2 Field Measurements........................................................................................................... 1
1.3 Equipment Verification....................................................................................................... 1
1.4 Initial DECS400 Field Setup&Load DECS Settings File....................................................... 1
1.5 IRIG&Networking Setup....................................................................................................2
2 Controls Checkout........................................................................................................................ 2
2.1 SEL-751A Relay....................................................................................................................2
2.2 DECS-400 Inputs..................................................................................................................3
2.3 DECS-400 Outputs...............................................................................................................3
3 SCADA List....................................................................................................................................3
4 Initial DECS-400 Settings..............................................................................................................3
4.1 Configure.............................................................................................................................3
4.1.1 Controller Logic Load.................................................................................................3
4.1.2 Rated Data.................................................................................................................4
4.1.3 Options.......................................................................................................................4
4.1.4 Auxiliary Inputs..........................................................................................................5
4.1.5 Meter Drivers............................................................................................................. 5
4.1.6 System Data...............................................................................................................6
4.1.7 Transient Boost..........................................................................................................6
4.2 Settings................................................................................................................................ 6
4.2.1 AVR/FCR/FVR............................................................................................................. 6
4.2.2 VAR/PF....................................................................................................................... 7
4.2.3 Startup.......................................................................................................................8
Internal Use Only Page i
Idaho Power Company Abbreviated Title
4.3 Gain.....................................................................................................................................8
4.3.1 AVR Gains(Primary)...................................................................................................8
4.3.2 AVR Gains(Secondary)...............................................................................................9
4.3.3 FCR Gains...................................................................................................................9
4.3.4 FVR Gains...................................................................................................................9
4.3.5 Other Gains................................................................................................................9
4.4 Limiting.............................................................................................................................. 10
4.4.1 Configuration........................................................................................................... 10
4.4.2 Summing Point OEL(Primary).................................................................................. 11
4.4.3 Summing Point OEL(Secondary)............................................................................. 12
4.4.4 UEL(Primary)........................................................................................................... 12
4.4.5 UEL(Secondary)....................................................................................................... 12
4.4.6 Takeover OEL........................................................................................................... 12
4.4.7 SCL(Primary&Secondary)...................................................................................... 12
4.4.8 VARL(Primary&Secondary).................................................................................... 12
4.4.9 Scaling(Primary&Secondary)................................................................................. 13
4.5 Protection......................................................................................................................... 13
4.5.1 General Protection(Primary)................................................................................... 13
4.5.2 General Protection (Secondary).............................................................................. 13
4.5.3 24 Voltz/Hz............................................................................................................... 13
4.5.4 Loss of Sensing......................................................................................................... 13
4.5.5 EDM.......................................................................................................................... 14
4.5.6 Relay Setup.............................................................................................................. 14
4.6 Data Log............................................................................................................................ 15
4.6.1 Log Setup(Initial)..................................................................................................... 15
4.6.2 Mode Trigger............................................................................................................ 15
4.6.3 Log Selection............................................................................................................ 15
Internal Use Only Page ii
Idaho Power Company Abbreviated Title
4.6.4 Level Triggers........................................................................................................... 16
4.6.5 Logic Triggers........................................................................................................... 16
5 Commissioning........................................................................................................................... 17
5.1 Operations Loading Summary........................................................................................... 17
5.2 Final Data Acquisition Summary....................................................................................... 18
5.3 Off-Line Tests—Turbine Spinning..................................................................................... 19
5.2.1 FCR Mode—Verify Field Voltage,Initial Field Voltage............................................ 19
5.2.2 FCR Mode—Step Response 2%............................................................................21
5.2.3 AVR Mode—Step Response 2%...............................................................................22
5.2.4 AVR Mode—Step Response 5%...............................................................................24
5.2.5 OEL—Offline............................................................................................................25
5.2.6 Soft Start..................................................................................................................26
5.2.7 Voltage Matching.....................................................................................................26
5.3 On-Line Testing.................................................................................................................29
5.3.1 Verification(Before Going Online)..........................................................................29
5.3.2 Synchronize the Unit................................................................................................29
5.3.3 AVR Mode-Light Load,Step Response....................................................................30
5.3.4 FCR Mode-Light Load,Step Response....................................................................31
5.3.5 Over Excitation Limit................................................................................................31
5.3.6 Under Excitation Limit.............................................................................................33
5.3.7 FCR Mode-Heavy Load,Step Response..................................................................34
5.3.8 AVR Mode-Heavy Load,Step Response..................................................................34
Glossary...................................................................................................................................36
Review/Revision History.........................................................................................................37
Internal Use Only Page iii
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
1 Preparation
1.1 Project Information
• Project Server Location:
\\FresnoPowerP rod uction\PIants_Hydro\17 MLPR Milner\Projects\2020-MLPRI2-AVR
Upgrade-MLPR200001\Engineering-Commissioning\Unit 2
• Modeling Server Location:
\\Fresno\powerproducton\Plants_Hydro\17 MLPR Milner\Condition Assessment and
Info\NERC MOD\2023-MLPR2-MOD026
1.2 Field Measurements
1. ❑ Micro-Ohm Resistance Test,Value: mf2 @ 20°C
o Original Value is 0.***f2 @ **°C
o Manufacture Value is 1.1850 @ 25°C(This is a questionable value, very large but
maybe)
2. ❑ Review Final Rotor I Test Report,Value: Mfg
(Including Slip Rings,Initial Maintenance Record)
3. ❑ Complete final field measurements forms and save to SharePoint Site;
Plant Condition Assessment Library-All Documents
1.3 Equipment Verification
1. ❑Verify Unit Style Number:DECS-400-1-C-5-U
0 1=PSS
o C=125V(ac or dc)
o 5=5A CT Secondary
o U=Battery Backup for real-time clock.
1.4 Initial DECS400 Field Setup & Load DECS Settings File
1. ❑ Power Up DECS-400(If net Fi fy it tins been power cycled recently;f eg(Sting)
2. ❑ (New Only)Load Predefined Logic Scheme—Single DECS-400 without PSS.
(Reference Figure 111 DECS400Instruction manual,Rev.U)
3. ❑ Load Initial DECS Settings File,or edit existing for pre-commissioning settings.
4. ❑ Verify Isolation Module wiring has:(Per Basler Drawings, 1302A)
Internal Use Only Page 1
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
o Voltage on±125V
o Shunt on 100mV&/800A
5. ❑ Update Field Rated Data with field DLRO Testing values.Use IR to measure
temperature of the rotor not just the ambient air for temperature measurement.
1.5 IRIG & Networking Setup
1. ❑Verify IRIG physically Connected and Setup the IRIG Settings and adjust for MST.
a. Communications->NTP Settings
❑Set the IP address to the NTP(Clock:unknown)
❑ Enable NTP(If using NTP)
❑Set Time zone offset to-420min.(UTC-07:00,MDT:UTC-06:00)
b. Tools->Device Real-Time Clock
❑ Enable Automatically Adjust to Daylight Savings
(UTC-07:00,MDT:UTC-06:00)Thus,
IRIG UTC MDT
15:00 8:00 9:00
18:00 11:00 12:00
23:00 17:00(5pm) 18:00(6pm)
2. ❑ Modbus physical connection and verify communication.
3. ❑ Set or verify IP Address(If Network connected)
2 Controls Checkout
This section would cover any additional checkout items beyond the initial checkout by the
design and installation team.
2.1 SEL-751A Relay
❑ Review if new install.General review of controls and operations per standards.
Internal Use Only Page 2
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
2.2 DECS-400 Inputs
❑ Review if new install.General review of controls and operations per standards.
2.3 DECS-400 Outputs
❑ Review if new install.General review of controls and operations per standards.
3 SCADA List
There should be no changes to the SCADA 10 from the DECS.
❑Verify field data is being set to EMS from the Plant.
❑Verify the field data sent to EMS is also sent to PI and configured correctly.
4 Initial DECS-400 Settings
4.1 Configure
If th., Rot hRr R occ -4 h„Alfr;4b'Pd Rpfpr@Rc;p the occ!'.....FA'SSi9R'Rg guide.This unit will
not utilize a PSS due to the unit's capacity.
4.1.1 Controller Logic Load
1. ❑ Load logic into controller for single DECS without PSS.
Internal Use Only Page 3
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
4.1.2 Rated Data
110. jQQ :c manufact rsd :OS: Standard ANSI
1� cYA ?over lnc:cr D® Noe. stood
l38C0 5: Y Duty CCNT. Runevay speed l090 RPM
53i A Stator vI.k'ing 4yr Inertia Canst. 2.!? kHs/I VA
ccnneCt:on
6J Hz Excitation 4!a A 95 V
EEPhases Insulation class stator/fleld vdq. F/F
%rect:cn of rotation seen from sliprinq s:ee Q
Temperature rise above
cold FAIR In stator v:nalrq: ® K. :n field v:ne:nq= SJ K
4.1.3 Options
Setting Comments
Voltage Sensing ABC 3-Phase Per281302A,All phases normal
rotation.
Field Type Main Field Static Exciter
Bridge Control Signal -10V->+10V Standard
Temperature Mode DEG.C Standard
Underfrequency Mode V/Hz Standard
Current Sensing Three Per 281102.dwg
CT Sr' A-B
Generator Frequency 60 Nameplate
Voltage Matching Disabled At Startup, will enable during
commissioning later.
Internal Tracking Enabled Standard on single DECS to track
between FCR and AVR modes.
External Tracking Disabled This is used for Dual DECS designs.
Inner Loop Field Regulator Disabled
Internal Use Only Page 4
Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure
4.1.4 Auxiliary Inputs
Setting Comments
Input Type Voltage
Summing Type Inner Loop
g,,..,.��T,,..,.input ro«v��,.,.,,r� The
Input Function Remote Setpoint
Aux is not used.
Aux Gain Settings used if using Aux control.
AVR(Mode)Gain 1.0
FCR(Mode)Gain 1.0
FVR(Mode)Gam. 1.0
VAR(Mode)Gain 1.0
PF(Mode)C
Droop Compensation Enabled,5% This is for parallel generators,
otherwise Disabled.
Line Droop Compensation Disabled,0%
Cross Current Compensation Disabled,0%
4.1.5 Meter Drivers
Setting Comments
Meter Driver 1 Disabled No devices connected per 2813402A.
System Parameter Metered ..
Minimum Value ..
Maximum Value ..
Meter Driver 1 Disabled No devices connected per 2813402A.
System Parameter Metered ..
Minimum Value ..
Maximum Value ..
Internal Use Only Page 5
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
4.1.6 System Data
Setting Comments
Gen PT:Primary Voltage 14,400 Per281102
Gen PT:Secondary Voltage 120 Per281102
Gen CT:Primary Current 800 Per281102
Gen CT:Secondary Current 5 Per281102
Bus PT:Primary Voltage 14,560 Per281105/281107
Bus PT:Secondary Voltage 120 Per281105/281107
Internal Tracking Delay 1.0 Standard
Internal Tracking Transvers Rate 3.0 Standard(2.0 is also used)
External Tracking(Secondary) Not Used,for Dual Decs.
External Tracking Transverse R Not Used,for Dual Decs
Field Current Sensing:Shunt 800 Per 281302A
Field Voltage Isolation Transducer 125 Per281302A
4.1.7 Transient Boost
Setting Comments
Transient Excitation Boosting Disabled Not used forWo.
4.2 Settings
4.2.1 AVR/FCR/FVR
Setting Comments
AVR
Setpoint 13,800
Internal Use Only Page 6
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Min%(Rated) 95.0 Standard is 0.95, Verify with TO.
Max%(Rated) 105.0 Per nameplate
Transverse Rate 30 Standard 30.
AVR Pre-Position 1
Setpoint 13,800 This brings it up to rated.
Mode Release
Transverse Rate/Enable Disabled Same as above if disabled.
AVR Pre-Position 2
Setpoint 13,800
Mode Release
Transverse Rate/Enable Disabled Some as above if disabled.
FCR
20%of Rated Field Current to start.
Setpoint (280) (416A x 20%=83A)
SNL(2017)=^280A(MOD025,online)
Min%(Rated) 20.00 Initial Setting for startup.
Max%(Rated) 105.0 Standard 105.0 but may be adjusted
later.
Transverse Rate 120 60-200 been used.Standard 120.
FCR Pre-Position 1
Setpoint 83 Initial Setting for startup
Mode Release
Transverse Rate/Enable Disabled
FCR Pre-Position's
Setpoint 83 Initial Setting for startup
Mode Release
Transverse Rate/Enable Disabled
4.2.2 VAR/PF
Not Used
Internal Use Only Page 7
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
4.2.3 Startup
Setting Comments
Primary Soft Start Level 25 Standard 25.
Primary Soft Start Time 15 Standard 15.
Secondary Soft Start Level Not Used(Make same as primary)
Secondary Soft Start Time Not Used(make Same as primary)
Field Flash Dropout Level 50 Standard 50.
Maximum Field Flash Time 10 Standard 10.(up to 25)
Voltage Matching Band 10.00 Standard 10.0
Voltage Matching(Gen-Bus PT) 100.2 Plant unit specific.
Volts/Hz High Limiter 1.08 Standard 1.08
Volts/Hz Low Limiter 1.06 Standard 1.06
Volts/Hz Time Limiter 10.0 Standard 10.0
4.3 Gain
4.3.1 AVR Gains(Primary)
Setting Comments
Kp—Proportional Gain 80.0 default 80.
Ki—Integral Gain 20.0 default20.
Kd—Integral Gain default 40. (Rotating Exciters)
Td—Integral Gain 00.1 default 0.01
Kg—AVR Loop Gain 15.0 default 15.
Internal Use Only Page 8
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
4.3.2 AVR Gains(Secondary)
Make these the same as the primary.Secondary is not used in controller,but just in case
making them the same as the primary ensures the same control between them.
Setting Comments
Kp—Proportional Gain 80.0 Existing,default 80.
Ki—Integral Gain 20.0 Existing,default 20.
Kd—Integral Gain 90.0 Existing,default 40. (Rotating Exciter)
Td—Integral Gain 0.01 Existing,default 0.01
Kg—AVR Loop Gain 15.0 Existing,default 15.
4.3.3 FCR Gains
Setting Comments
Kp—Proportional Gain default 0.
Ki—Integral Gain default 0.
Kd—Integral Gain default 0.(Rotating Exciter)
Td—Integral Gain Nkdefault 0.
Kg—AVR Loop Gain 1000 default1000.
L in
4.3.4 FVR Gains
Not Used.
4.3.5 Other Gains
Setting Comments
VAR Not used
1.0
Internal Use Only Page 9
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Kg—Loop Gain 0.0
PF Not Used
Ki—Integral Gain 1.0
Kg—Loop Gain 0.0
OEL
Ki—Integral Gain 1.0 Standard 1.0-15.0
Kg—Loop Gain 20.0 Standard 2.0-35.0
UEL
Ki—Integral Gain 1.0 Standard 1.0
Kg—Loop Gain 20.0 Standard 2.0-20.0
SCL Not Used
Ki—Integral Gain 1.0
g—Looplabb, 0.0
Voltage Matching
Kg—Loop Gain 2.0 Standard 1.0-3.0
When inner loop selected in the
Inner Loop Field Regulator Settings/Auxiliary Input/Summing
Type,then this gain is enabled.
Ki—Inner Loop 0.0 Standard.0.0
Kg—Inner Loop 1.0 Standard.1.0
VARL Not used?
1.0
Kg—Loop Gain 0.0
4.4 Limiting
4.4.1 Configuration
Setting Comments
Limiter Modes
Internal Use Only Page 10
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
OEL Enable Standard.
UEL Disable UEL will be enabled in commissioning later.
SCL Disable
VARL Disable
DEL Mode Summing Point Standard
OEL Voltage Dependency Disabled
dv/dt Level Disabled This is enabled by enabling the voltage
dependency.
UEL Mode Summing Point Standard
UEL Voltage Dependency
Real Power Exponent 0.0 Typically,0.0,but also 1.0 can be used.
Real Power Filter Time
5.0 Typically,5.0
Constant
4.4.2 Summing Point OEL(Primary)
Setting Comments
Offline See IEEE C50.13 standard/PRC-019
Initial Set at 15%rated gen volt.
High Level 322 280A x 1.15=322A
Estimated 370A Field=1.05pu Gen Volt
High Time 2 Standard.
Initial Set at 10%above rated gen volt.
Low Level 308 280A x 1.10=308A
May need to be adjusted later.
On-Line Fir See IEEE C50.13 standard/PRC-019
High Level 581 Initial set at 140%above rated field
High Time 3 Initial set at 3.Os
Medium Level 518 Initial set at 125%above rated field
Medium Time 10 Initial set at 10.Os
Low Level 477 Initial Set at 115%above rated field
Internal Use Only Page 11
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
4.4.3 Summing Point OEL(Secondary)
Not Used,set same as Primary.
4.4.4 UEL(Primary)
This controller function needs to be coordinated with PRC-019.
Setting Comments
Primary UEL Matched EMS UEL.
Curve Selection mWernal
Point Selection 5
Points 1:Real Power/Reactive Power 0/7.62k 12.7MVA x 60%=7.62MVar
Points 2:Real Power/Reactive Power 2.54k/7.62k 12.7MW x 20%=2.54MW
Points 3:Real Power/Reactive Power 7.62k/6.858k 12.7MVA x 54%=6.858Mvar
Points 4:Real Power/Reactive Power 11.43k/5.715k 90%and 45%respectively.
Points 5:Real Power/Reactive Power 15.2k/0 1.2 x 12.7MW=15.2MW
**The values originally selected are above capability curves values from manufacture,
trimmed to match existing EMS curve until PRC-019 has been reviewed. **
4.4.5 UEL(Secondary)
Not used,same as Primary.
4.4.6 Takeover OEL
Not Used.
4.4.7 SCL(Primary&Secondary)
Not Used.
4.4.8 VARL(Primary&Secondary)
Not Used.
Internal Use Only Page 12
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
4.4.9 Scaling(Primary&Secondary)
Not Used.
4.5 Protection
4.5.1 General Protection(Primary)
In general,the excitation controller unit protection functions are not used.The unit protection
is served by a separate relay protection system.Typically alarms and tripping from this
controller would be internal only to the excitation system.
Setting Comments
Generator Overvoltage Disable Standard
Field Overvoltage Disable Standard
Loss of Field Iso.Transducer Enable Standard
Delay 1.0 Standard
Generator Undervoltage Disable Standard
Field Overcurrent Disable Standard.
Power Supply Low Enable Standard(Mixed depending on site upon
review)
Loss of Field Disable Standard
Field Over Temperature Enable Standard
Pickup Level 130 Typical130
Delay 60 Typical60
4.5.2 General Protection(Secondary)
Same as Primary.
4.5.3 24 Voltz/Hz
Disabled.
4.5.4 Loss of Sensing
Setting Comments
Internal Use Only Page 13
Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure
Option Enable Standard
Balanced Level 50.0 default
Unbalanced Level 20.0 default
Delay 2.0 default
Transfer to Manual Enable Standard
4.5.5 EDM
Not Used.
4.5.6 Relay Setup
Setting Comments
Relay#1
Contact Status Normally Open default
Contact Type Maintained default
Momentary Time 0.10 default
Relay#2
Contact Status Normally Open default
Contact Type Maintained default
Momentary Time 0.10 default
Relay#3 IV
Contact Status Normally Open default
Contact Type Maintained default
Momentary Time 0.10 default
Relay#4
Contact Status Normally Open default
Contact Type Maintained default
Momentary Time 0.10 default
Relay#5
Internal Use Only Page 14
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Contact Status Normally Open default
Contact Type Maintained default
Momentary Time 0.10 default
Relay#6
Contact Status Normally Open default
Contact Type Maintained default
AL
Momentary Time 0.10 defau
4.6 Data Log
4.6.1 Log Setup(Initial)
Setting Comments
Data Logging Enabled Enable This sets up for the first energization data
capture for 30.0s.
Pre-Trigger Points 49.992
Sample Interval 20.0
4.6.2 Mode Trigger
Setting Comments
Start/Stop Mode Start
Limiter Mode UEL&OEL
Test Mode Enabled
All other triggers not identified are not used.
4.6.3 Log Selection
Setting Comments
Internal Use Only Page 15
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Parameter 1 Generator Average Voltage
Parameter 2 Field Voltage
Parameter 3 Field Current
Parameter 4 Generator Real Power
Parameter 5 Generator Reactive Power
Parameter 6 Control Output
4.6.4 Level Triggers
No triggers are enabled.
4.6.5 Logic Triggers
Setting Comments
Alarm States None enabled
Relay Outputs Enabled Watchdog
Enable Relay Output 2
Contact Inputs FCR(Manual)
Enable Switel.Input 7 A4onuol OCC
Internal Use Only Page 16
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
5 Commissioning
5.1 Operations Loading Summary
Table 1.Loading Summary for AVR Commissioning
Section Test Loading Flow Unit Control Schedule
5.2.1 Initial Field Energization Offline,Rated Speed 90cfs Manual
5.2.2 FCR Voltage Response Offline,Rated Speed 90cfs Manual
Day 1
5.2.3,4 AVR Voltage Response Offline,Rated Speed 90cfs Manual
5.2.5 Offline OEL Response Offline,Rated Speed 90cfs Manual
5.2.6,7 Soft Start/Voltage Matching Offline,Rated Speed 90cfs Manual
OnlineSNL 90cfs
Offline,Rated Speed 90cfs
5.3.2 Synchronizing Manual
OnlineSNL 90cfs
3MW,2%Variable Vars 300cfs
5.3.3 AVR Voltage Response Manual
9MW,2%Variable Vars 750cfs Day 2
3MW,2%VariableVars 300cfs
5.3.4 FCR Voltage Response Manual
9MW,2%Variable Vars 750cfs
5.3.5,6 DEL,UEL Limits 3MW,Variable Vars 300cfs Manual
5.3.7 FCR Voltage Response BMW,5%Variable Vars 650cfs Manual
5.3.8 AVR Voltage Response BMW,5%Variable Vars 670cfs Manual
1MW/Unity,±2.5MVar 150cfs
2.5MW/Unity,±2.5MVar 250cfs
S.OMW/Unity,±2.5MVar 450cfs
5.4 V-Curve Validation Manual Day 3
7.6MW/Unity,±2.SMVar 650cfs
10.2MW/Unity,±2.5MVar 850cfs
12.5MW/Unity,±2.5MVar 1110cfs
*No saturation test is to be performed.Manufactures saturation information will be utilized for modeling and
verification.
Internal Use Only Page 17
Idaho Power MLR2-Initial Setup&FCR/AVR Commissioning Procedure
5.2 Final Data Acquisition Summary
Table 2.Summary of Data Acquisition
Step Time Step Pre-Trigger Sample
Section Test/Record Method' Magnitude' Delay' Duration' Points' Interval'
5.2.1 Initial Field Energization Start Mode 25 49.992s
Trigger
5.2.2 Offline FCR Voltage Response Manual Step - 60 16.664ms
Response
5.2.3,4 Offline AVR Voltage Response Time Response 2.0% 0.5s 6.0s 25 16.664ms
5.2.5 Offline OEL Response Time Response 2.0% 0.5s 6.0s 0 16.664ms
Auto Soft Start/Voltage Start Mode
5.2.6,7 Matching Trigger 25 49.992s
5.3.2 Auto Synchronizing Logic Trigger - - - 300 49.992s
Input Switch 31
5.3.3 Online AVR Voltage Response Time Response 2.0% 0.5s 9.0s 0 24.996ms
(Light Load)
Online AVR Voltage Response Time Response 2.0% 0.5s 6.0s 0 24.996ms
(Heavy Load)
5.3.4 Online FCR Voltage Response Manual Step 20 24.996ms
(Light Load) Response
Online FCR Voltage Response Manual Step
(Heavy Load) Response 20 24.996ms
5.3.5,6 OEL Limits-Control Response Time Response 2-5.0% 0.5s 26.0s 10 49.996ms
XX UEL Limits-Control Response Time Response 2-5.0% 0.5s 31.0s 10 49.996ms
FCR Voltage Response(Stability
5.3.7 5%) Time Response 5.0o� 0.5s 9.0s 20 24.996ms
5.3.8 S/)Voltage Response(Stability Time Response 5.0% 0.5s 9.0s 20 24.996ms
5.4 V-Curve Validation Manual/Operator -
Note
1. Selected within the DECS-400 Analysis Time Response Menu.
2. Input switch 3 is the generator breaker closure input.
3. Selected within the DECS-400 Log Setup Menu.
4. Response method or DECS logic operator in Analysis menu
Internal Use Only Page 18
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
5.3 Off-Line Tests—Turbine Spinning
5.2.1 FCR Mode-Verify Field Voltage,Initial Field Voltage
This task is to ensure proper gate operation,field flash,and general operation.Initial start-up in
manual mode.
❑ Perform a final walkdown prior to spinning and flashing the field.
1. ❑ Switch to FCR Mode
There have been times when the current is not enough and the unit will fail to build.
Review the open circuit saturation results from the manufacture or previous testing.In
2017 data was collected and the field current was 287A,at 1.6MVA unity loading.83A
may not cut it as noted from the Basler manual.
2. Go to Settings->AVR/FCR/FVR
a. Adjust Field Current Regulator(FCR)
i. ❑ Setpoint(20%)=415A x 0.20=83A
ii. ❑ FCR Pre-position 1(20%)=83A
iii. ❑ FCR Pre-position 2(20%)=83A
3. Manually Start the DECS400(generator should build to percentage of rated voltage)
a. ❑ Use a fluke to verify the voltage is firing correctly.
May need to raise the voltage if 20%is not sufficient,see step 4.
b. ❑ Capture all diodes firing within the waveform and record.
4. ❑ Increase the field current until 100%rated terminal voltage is reached.
a. The OEL limiter should limit the current to Rated Field Current x 75%=311A(Or
use past MOD data, refer to the initial settings tables).
According to Limiters->Summing Point OEL.Adjust this if needed.
b. Record the:
i. No load field current: A
ii. No load field Volts: V
c. Manually adjust the voltage to 2%above rated. 13.8kV x 1.02=14.076kV,this
will provide the field current required for manual step responses in FCR mode.
i. Rated+2%field current: A
ii. (Rated)/(Rated+2%)_ %
5. Go to Meter->Operation
a. Verify the phase angle,positive and negative sequences to make sure values look
correct.
Internal Use Only Page 19
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
i. ❑There should be little negative sequence values,if there are,a CT or
PT might be rolled.
ii. ❑ General review of field current and generator voltage.
iii. ❑ Verify any protective relays are reading correct.(SEL-751A)
6. ❑Verify the field temperature appears accurate.= C at startup
7. ❑ Verify the phasing looks accurate.
Internal Use Only Page 20
Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure
5.2.2 FCR Mode—Step Response 2%
This is to determine the stability of the excitation system in manual mode.
The difficulty in this test is the know how far to change the percent of field current. Manually
raise the voltage
1. Setup the data log to capture the test results.
a. Go to Data Log->Mode Triggers
„; E Notes
Ccmn ications Tools window Help 2. Enable Test Mode
•�E`Corrf9— S.M. Gain tinni Pmta— ISS for this.
Malys. Data Log M— 1o9.
m� �I��
Log Setup Mode Triggers I Log Selection I Level Triggers I Logic Triggers Trending
llllllll
Start DELII SCL NDTRIGGER .
Fq TRIGGER NO TRIGGER •• .TRIGGER -
tb TRIGGER ,• . .TRIGGER P10 TRIGGER
IJO TRIGGER P10 TRIGGER Enabled
NO TRIGGER NO TRIGGER
9
b. Go to Data Log >Log Setup
ja 1,1, Notes
Y� Configure Settings Gain L.d— Proletlbn I PSs
m
m ✓ L�-I �j L ?nalysis Dale Log Me[a lnpc
L J S-h+P I Mode TTriggers I Log Selection I Lad Triggers Logic Triggers I T.ndirg
Uim Sele.ace Of Evert
r Dala Lo9gin9 Enabled
50
Pre-Trigger Points Mew/Donaio�Data
® Pre-Trigger Duration(sec) Dansioed Trend
®i Pent-Trigger Pains
® Post-Trigger Duration{see)
za 9% Swoe Interval{mil
® ToW Duration{sec)
c. Go to Data Log->Log Selection
Internal Use Only Page 21
Idaho Power ML112—Initial Setup&FCR/AVR Commissioning Procedure
'g Notes
`i Configure Settings Gain L.ft— Rdaclm I Pss
A ICI Wj
Maysis Data Log Meer Lajc
Logs-1-pi Mode Triggers Log Selection I Level Triggers I Logic Triggers I Trending I
Generator Average Vollage w) Generator Real Power{pu)
Feld Vokage{Du) lGenerator Reactive Power(pu)
Feld Current(pu) ITime Response W)
2. ❑X Go to Analysis->Step Response to perform an FCR step response(Must use Step
Response within the Analysis Menu)
a. Set a 2%step
L Check trigger data logging on step change
ii. Decrease the value
iii. Increase the value
b. Review the step response,the response should be very stable
3. ❑X Go to Analysis->Step Response to perform an FCR step response(Must use Step
Response)
a. Set a 5%step
L Check trigger data logging on step change
ii. Decrease the value
iii. Increase the value
b. Review the step response,the response should be very stable
4. ©Test the OEL response,drive the FCR 5%into the OEL.
5. ❑x Stop the AVR
5.2.3 AVR Mode—Step Response 2%
[description]
1. © Setup Data Logger
a. Go to Data Log->Log Setup
Internal Use Only Page 22
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
in File 'view Communication; Tools Window Help L mote
et� Coniigse I Seeing. I Gan I Lmit. Protection I PSS S
m ® ,�} Analysis Data Log Miler Logic
Log Setup I Mode Triggers I Log Selection I Level Triggers I Logic Triggers I Trending
s- - View Sent..of Eveds
r Data Logging Enabled
—50 M./Download Data Log
Pre-Trigger Points
t t® Pre-Trigger Duration;sec) DowrdoM Triad Log
Post-Trigger Pants
Post-Trigger Duration,sec)
16 kq Sample Interval(ms)
Total Duration(sec)
2. ❑x If not already in AVR mode,Transfer to AVR mode
3. ❑x Start the AVR if not already on.
4. © From Analysis screen setup and run a Time Response Test as shown:
Test Signal
Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings
0.5 Fo AVR Summing Step . Sweep Type Start Frequency
I— PSS Comp Frequency Linear Ssvee .Q5 Q0
r PSS Electric Power
Sta t2.0 tude(�') 0.D00 Offset(�) '
r PSS Derived Speed Frequency Step Stop Frequency
Exit I— Manual Summing Frequency(Hz) Duration(Sec) 0.001 3.OD0
r VARIPF FO.000 5.0
a.
5. ❑X Adjust PID settings as needed.Go to Gains->AVR Gain
a. Adjust KID to display a good rise
b. Adjust Ki to be about%to 1/5 of Kp
c. Adjust Kg until we have about a.3 second response time(Rise Time)
d. Add info about the rotating exciter....
Internal Use Only Page 23
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
VP Commented[Al]:Kg is the rise time,Vc is the set point.
VREF + E --AR`
KG KP + E II VR
VRLMT/VP +
VC K
s
0
sKp
1 +sTp
e.
Commented[A2]:Basler mentioned this may be to much.1
5.2.4 AVR Mode—�tep Response S*
believe rich and I experienced that as well.
1. ❑x Setup Data Logger
a. Go to Data Log->Log Setup
_t-ESTCOMS-DECS400-[Data Log]
File View Communications Tools Window Help
a, Calque Settings Gain Limier Protection P55
m '--, �p Aralyas�_ Data Log Mete Lope
Log Setup I Mode Triggers I Lop SelMion I level Trippers I Logic Triggers I Trading I
s- View Sepumce Of Evenb
W Data Logging Enabled
-50 Pra-Trigger Pants View i DowrioW Data Ui➢
® Pra-Trigger Duration{sec) Dowiload Trerd Log
® Post-Trigger Pants
Post-Tngger Duration isec)
21.9% Sample Interval{msl
Total Duration ism)
b.
2. ❑ If not already in AVR mode,Transfer to AVR mode.
3. St -, the A °already running
4. ❑x From Analysis screen setup and run a Time Response Test as shown:
Internal Use Only Page 24
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Test Signal
Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings
0.5 F7 AVR Summing Step Sweep Type Start Frequency
r PSS Comp Frequency Magnitude(%) Offset(dc) Unear Sweep 0.050
Start r PSS Bectric Power
r PSS Derived Speed 5.0 O.D00
Frequency Step Stop Frequency
"" I
( r Manual Summing Frequency(Hz) Duration(Sec) 0.001 3.OD0
` r VAR'PF O.D00 5.0
a.
5. Adjust PID settings as needed
a. Adjust Kg until we have about a—0.3 second response time.
5.2.5 OEL—Offline
This is the testing to ensure the OEL is operating correctly.
1. ❑X Go to meter
a. Note the current value for Ifd:842A @ 14.400kV
2. ❑X Go to Limiters->Configuration
a. ❑X Check OEL Enable
3. Go to Limiters->Summing Point OEL
a. ❑X Change the Off-Line High Level to 10%higher than the value recorded in step
1,w/delay of 5 seconds(Original 10 seconds).Ifd(842A)x 1.10=926A(Original
880A for both,0 seconds)
b. 0 Change the Off-Line Low Level to 2%higher than the value recorded in step 1, Commented[A3]:Found the 5%was to much,changed to
Ifd(842A)x 1.02=858A(Original 880A) 2
4. Go to->Settings->AVR/FCR/FVR
a. 0 Increase the field current by increasing the voltage setpoint,so it is above the
low level setting programmed in step 1.
i. This should slowly move the field current into the over excitation limit
and after the delay time should move the field current to the low level
setting.(Record Terminal Voltage:14.400kV (commented[A4]:What is this for?
ii. Make sure that the response is stable.
1. If not: Go to Gain->Other Gain
a. Adjust OEL Kgl Commented[A5]:Have a note to adjust Data Log
❑Verify Stable
5. Once stable,Go to Analysis Screen
Internal Use Only Page 25
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
a. Setup graphs with
i. Vavg
ii. Ifd
b. Setup a Time Response as shown
Test Signal
Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings
1.0 F AVR Summing Step Sweep Type Start Frequency
F PSS Comp Frequency Magnitude(G) Offset(dc) Unear Sweep - F
r PSS Electric Power
r PSS Derived Speed 5.0 F 0.000
Frequency Step Stop Frequency
5tit r Manual Summing Frequency(Hz) Duration(See)
� 1.000
r VAR,'PF p.ppD I LV
C.
d. Start the Time Response test
i. Should see the current limit come in and control the field current to the
OEL setpoints.If the response time seems too slow increase IKgI Commented[A6]:How long should it take?I had it at about
1. Go to Gain->Other Gain 6-8sec
a. OEL Ki-Adjust from 1.0 to 1.5(Original 1.0)
b. OEL Kg-Adjusted to 20.0 from 25(Original 25.0)
6. ❑X Return OEL Values to their starting values 880A/Os/880A
5.2.6 Soft Start
1. ❑ Stop the AVR and make sure it is in AVR Mode
2. ❑ Start the AVR from the analysis screen commented[A7]:The DECS will record a record for the
a. El Verify the Soft Start in the graph for primary values start of the AVR,use the 49.992 sample interval
i. Soft start level: 25
ii. Soft Start Time: 15
3. ❑ Record the startup and save.(50-pre,49.9ms Sample,29s Duration)
a. File Name:"HCPR33 Softstart Offline OffOn"
We merged the Soft start and the Voltage matching records.
5.2.7 Voltage Matching
1. ❑x Transfer to AVR Mode
2. Set voltage matching here.
3. ❑x Start the AVR
4. Go to Configure->Options
a. © Enable Voltage Matching
Internal Use Only Page 26
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
5. Go to Settings->Startup
a. ❑X Set band to:5(standard is 10,left it tight)
b. ®Set Gen to Bus PT match level to:100.0(standard is 100.2,but left at 100
since voltage is high normally)
6. Adjust the setpoint to the upper end of Voltage matching level(Adjust to 14.4kV)
a. 0 Verify it reduces the voltage to match commented[AS]:wejustwatched ittrack it.
b. If the response Its too slow or too fast Commented[A9]:How fast do we want it?We left it 3.0
i. Go to Gain->Other Gain bliss gain was 1.0
1. Adjust Voltage Matching Kg Commented[A10]:Played with different values 1 to 3(unit
7. Adjust the setpoint to the lower end of Voltage matching level(Adjust to 6.5kV,90% 2).....Set Unit 1 to 3.
rated)
a. ❑Verify it brings the voltage up to match
b. If the response is too slow or too fast
i. Go to Gain->Other Gain
1. Adjust Voltage Matching Kg
8. ❑Adjust the setpoint outside the voltage matching to see that it does not automatically
adjust the voltage for both above and below the Min/Max of rated(Value in the
Settings->AVRI) Commented[All]:The decs does not like the values
outside the window.
We watched it,did not do all the steps.
Internal Use Only Page 27
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
5 7 l?/1r.er. c..r.....f:.,., !'...-..e (a d.d:t:eRal test)
Nn#n•Be r• ..+:n..r and iyat h the terminal.elF•,nn make r l.e i#deer not net en..n
1 r17 o/c of rated voltage(1 c A9" '
1 n T n 94 yeltage Mateh'n
Ig
2. We had to Fall out the Rele..7 96E test feel. n+l.n....i. it trip nn 19SS nF re RSinn
'Ale have d4i;ahled the.101A Af';PRS*Rg voltage OR the plceteetdeR(Fealized that
3. Settle Data II egger
a. ce to Data Leg .Ian Setup
--d, Window Help
d Configure Settings I Gan I Linters I Protection PSS
A.*. Data Log I Meter Logic
Log Setup I Mode Triggers I Log Selection I L.1 Triggers I Logic Triggers I Trending
s• View Sequence Of Events
F74 Data Logging Enabled
10 Pre-Trigger Points Mew/Download Data Log
r r•r Pre-Trigger Duration(sec) Download Trend Log
Post-Trigger Points
Post-Trigger Duration(sec)
i Ao4.Dm - Sample Interval(ms)
.I r Total Duration(sec)
b.
/I GE)to Ce#+inne >C#erWn
a. Adjust the¢eft Start se++'n
gs
i. Seft StaFt Level--2(ariginal�value- �
ii. 994 Sitaf+Tea—60(QlCigiRai.-'We— Z
5. r_a+e cE?ttiR.e >Avo/Pro/W
i. SSe peiR.. 15,2l1�Tginal..�-1�rlvt
i AVR°irepesit'nn 1 - 115,200 Tgin l�value--13,9
OFF PGR°rr�e5itiGIR 2—19,209=(9,+g+Rel„• „a—13,809T) Commented[Al2]:Not sure why I need this.
6 n G-e+e cettiR e >Sta Ft e
a. Adjust Volts/Hz Limiter Settipgs
i. V{HZ High L Fe-_1.12 (GF*g+R l Imo, a-1.0�4
7—r'e+e I irni+e . QeRfig e+'e
a. I Ine heel.QEl ERab!L-
Commented[A33]:Keep,the values are large.
Internal Use Only Page 28
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
a. get the gFaph-r te me—Rite-IF
Vavg:Average Voltage
1-1 FrA__R;the sGFeeR stak the gFaph. The veltage and field cwwFept should be the
c.,F+r+ter+r+a+.,-,..rl rl.....1..ram.....the Fi..lrl e.err,,..+and+.,r...i..-,I....I+-,...,
Commented[A14]:Update with actual method.
17 Rpt,,r..-.II settiRgs te their eFigiRal values.
h n WH i!Values
e. n Lomoter OE-
5.3 On-Line Testing
5.3.1 Verification(Before Going Online)
1. Setting Group Logic.
a. In most machines this is disabled. But at HCPR and BLPR5 it is utilized and this
should be left on to start????
2. Go to PSS->Configure
a. ❑X Verify enable box is unchecked
3. Go to PSS->Control
a. ❑X Verify PSS Control is unchecked
4. Go to Meter->Operation
a. ® Verify the phase angle and positive and negative sequences to make sure
values look correct.
i. There should be little negative sequence values,if there are,a CT or PT
might be rolled.
5. ® Transfer to AVR Mode(May already be in AVR mode)
6. ❑x Verify the BUS PT signal is correct and make any adjustments to the Bus PT ration on
the System Data tab.
5.3.2 Synchronize the Unit
1. ❑X Transfer to AVR Mode
Internal Use Only Page 29
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
2. © Make sure the unit startup is in manual mode
3. ❑X Start the unit
4. © When up to speed,start the AVR(This may be in Auto to check 95%and matching)
a. Monitor the Voltage level to make sure it does not overshoot too much.
5. © Close the breaker when it is appropriate(operator in manual)
5.3.3 AVR Mode-Light Load,Step Response
1. Setup Data Logger
a. ❑X Go to Data Log->Log Setup
J@ _ -,
M rp. _ C,t,r .nl.a+lnrr. Tnnh Window Help
a Configure Settings Gan I Li0en I Rdis bm PSS
N
ro m Maysis Data Log Meter Logic
_
Log Setup I Mode Triggers I Log Selection I Level Triggers I Logic Triggers I Trending
a- - Mew Sequence Of Events
W, Data Logging Enabled
� View/Download Data Log
I Jy Pre-Trigger Pants
Pre-Trigger Duration(sec) _ Download Trend Log
Post-Trigger Pants
Post-Trigger Duration(seci
Sample Interval(msi
Total Duration(sm,
b.
2. 0 Unit should be online and loaded to about 20%
a. 0 Make sure to adjust load to avoid any rough zones
3. 0 Verify Unit is in AVR Mode
4. 0 From Analysis screen setup and run a 2%Time Response Test as shown:
Test Signal
Time Delay Signal Input Stabilizer Test Signal Se eep Signal Frequency Settings
0.5 P-1 AVR Summing Step _ Sweep Type Start Fregtxncy
r PSS Comp Frequency Magnitude(4) Offset(de) JLinear Sweep 0.050
Start r PSS Electric Power
r PSS Derived Speed 2.0 0.000
Frequency Step Stop Frequatcy
bat r Manual Summing Fray(Hz) Duration(Sec) 0.001 3.000
r VAR'PF 0.000 5.0
a.
S. Adjust PID settings as needed and retest 2%if parameters are changed.
a. Kp affects raise time Commented[A15]:If these are changed you have to go
back and re verify the offline effects,and update the
b. Kg affects response time, records.
Internal Use Only Page 30
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
G n if„ „te Fs aFe „table at the test. .ith -.5 Time Respe„se test
7 Adjust oin settings Of needed and retest_5% Of parameters are changed. — Commented[A36]:Same if you adjust,will need to retest
8. © Download file:"Online 2MW-AVR Mode-Step Response-2%Up-Down" lower levels.
5.3.4 FCR Mode-Light Load,Step Response
1. Setup Data Logger
a. ❑x Go to Data Log->Log Setup
2. ❑X Perform a 2%step response
5.3.5 Over Excitation Limit
OEL test reference in Basler manual pg. 146
---------------------------------------------
CC Cured
Level
U T eeuneft tt a.a-3aPtle
W err= I Leval
LL rr)--v oconmucw CuieRoa-2oAdr
t}l0eec o-1 Xsec Level
a.a-15 AdC
TIME IN SECONDS °'o.aioi
Figure 3-10.Summing Point,On-Line Overexcitation Limiting
Figure 1.Basler IL DECS-400.
1. © Load Machine to—10%(14.5 MW)—We are at 301MW.
2. Go to meter
a. Note the current value for Ifd:834A(14AW),(-7MVar)
3. Go to Limiters->Configuration
a. ® Check OEL Enable
4. Record Original On-Line Values
1480 High Level
Internal Use Only Page 31
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
5 High Time
1465 Medium Level
15 Medium Time
1450 Low Level
5. Go to Limiters->Summing Point OEL
a. ❑X Change the On-Line High Level to 15%higher(959A)than the value recorded
in step 2 w/delay of 5 seconds.
b. ® Change the On-Line Medium Level to 10%higher(918A)than the value
recorded in step 2 w/delay of 5 seconds
c. © Change the On-Line Low Level to 5%higher(876A)than the value recorded in
step 2.
6. Go to->Settings->AVR/FCR/FVR
a. ❑ Increase the field current by increasing the voltage setpoint,so it is above the
medium level setting programmed in step 2. 1 did a 5%step into the OEL.
i. This should slowly move the field current into the over excitation limit
and after the delay time should move the field current to the low level
setting.
ii. ❑X Make sure that the response is stable.
1. If not: Go to Gain->Other Gain
a. Leave OEL KI at 1.0 1 set the KI to 1.5 Commented[A17]:This is how others are,why?
b. ❑X Adjust OEL Kg Made no adjustments. Commented[A18]:Seemed stable as is.
7. Once stable,Go to Analysis Screen
a. Setup graphs with
i. Vavg
ii. Ifd
b. Setup a Time Response as shown
Test Signal
Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings
AVR Summing Step
1.0 Sweep Type Start Frequency
r PSS Comp Frequency r PSS Electric Power Li Magnitude(4) Offset(dc) near Sweep 1.000
Start
r PSS Derived Speed 5.0 O.ODO
Frequency Step Stop Frequency
E�dt r Manual Summing Frequency(Hz) Duration(Sec)
� 1.000 10.000
r VAR PF 0,0D0 I 20
C.
d. Start the Time Response test
Internal Use Only Page 32
Idaho Power IVLR2—Initial Setup&FCR/AVR Commissioning Procedure
L Should see the current limit come in and control the field current to the
OEL setpoints.If the response time seems too slow increase Kg
1. Go to Gain->Other Gain
a. ❑Adjust OEL Kg
2. ❑X Download Record:"Online**MW—AVR Mode—OEL Test 5%
Step Up-Down
8. ❑X Return OEL Limiter Values(Primary and Secondary)to their Initial settings values
5.3.6 Under Excitation Limit
UEL test reference in Basler manual pg. 146
1. Go to Limiters->Configuration
a. ❑X Uncheck UEL Enable
b. ❑ Record Existing Values
Primary 5—dary
Customized Cove Sdedion
C'3 Point r 5 Point
1 tOC.650 1
5 ,, Z 101.500 Z
101.5, 3 A.750 3
130.500 A 5 ,, d
169.650 5 F 5
C.
2. Go to Limiters->UEL(Starting at 7,500 War)
a. ❑ Change reactive power limit value to 5%Vars into the machine(about 11,000
War)
3. Go to->Settings->AVR/FCR/FVR
a. ❑ Decrease voltage setpoint until about 15%to 25%of Vars into the machine
(about 600 kVar)I Commented[A19]:Not needed?
4. Go to Limiters->Configuration
a. ❑X Check UEL Enable
5. Go to Analysis Screen
a. ❑ Setup graphs with
i. Vavg
ii. Kvar
b. Start the graph
Internal Use Only Page 33
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
L IShould see the UEL come in and control the field current to the OEL
setpoint. If the response time seems too slow increase Kg Commented[A20]:comes in pretty fast then it brings the
6. Go to Gain->Other Gain field current back pretty quick.
a. IOEL Kg Commented[A21]:????
b. ❑X Download Record:"Online**MW—AVR Mode—UELTest 5%Step Down-Up"
7. ❑X Return UEL Settings to their starting values(Roughly 80%of Rated Machine MVA)
5.3.7 FCR Mode-Heavy Load,Step Response
5.3.8 AVR Mode-Heavy Load,Step Response
3. Setup Data Logger
a. ® Go to Data Log->Log Setup
]@ File 'View Communications Tools Window Help Fthe
nted[A22]:I used a longer sample since it seems
i current was slower from light test.I wanted to
Ct. Smnp Gain Limiters Protection PSS it a11.
m L*A * Analysis Data Log Miler Logic
Log Setup Mode Triggers I Log Selection I Level Triggers I Logic Triggers I Trending
s I View Sequence Of Everts
W_ Data Logging Enabled
View/Dowdoad Data Log
5p Pre-Trigger Points
t® Pre-Trigger Duration isec) Dmroad TreW Log
Post-Trigger Points
Post-Trigger Duration isec)
16.664 Sample Interval ims)
Total Duration isec,
b.
4. ❑x Unit should be online and loaded to about 80%-100%.
a. ❑x Make sure to adjust load to avoid any rough zones
5. ❑X Verify Unit is in AVR Mode
6. ❑X From Analysis screen setup and run a-2.0%Time Response Test as shown:(we did a
+2%)
Internal Use Only Page 34
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Test Signal
Time Delay Signal Input Stabilizer Test Signal Sweep Signal Frequency Settings
0.5 Po AVR Summing Step Sweep Type Start Frequency
F PSS Comp Frequency Magnitude(%) Offset(dc) JLinear Sweep Y 50
Start r PSS Bectric Power
r PSS Derived Speed -2.0 0.000 Frequency Step Stop Frequency
but r Manual Summing Frequency(Hz) Duration(Sec) O.OD1 3.OD0
F VAR/PF O.ODO 15.0
a.
7. ❑x Adjust PID settings as needed and retest 2%if parameters are changed.
a. Kp affects raise time
b. Kg affects response time
8. ❑x If parameters are acceptable,repeat the test with a 5%Time Response test
9. ®Adjust PID settings if needed and retest 5%if parameters are changed.
10. © Download file:"Online**MW-AVR Mode-Step Response-2%Down-Up"
a. And%5
Send DECS configurations file to PRC-19 custodian.
Appendix?
Enter the appendixnumber above its caption and apply the"Caption Appendix No"style.Enter the
caption for the appendix below its number and apply the"Caption Appendix"style.
(appendix info goes here)
Internal Use Only Page 35
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Glossary
Instructions for glossary terms:Turn on bold(Ctrl+b),key the glossary term,insert an em dash
(with Num Lock on,press Alt+0151),turn off bold(Ctrl+b),then key the definition.See the
following sample.
Glossary Term—This is a sample.This is a sample of a formatted glossary term.This is a sample.
This is a sample of a formatted glossary term.
Internal Use Only Page 36
Idaho Power MLR2—Initial Setup&FCR/AVR Commissioning Procedure
Review/Revision History
This document has been approved and revised according to the revision history
recorded below.
Review Date Revisions
Mm/dd/yyyy Document was implemented.
14
Internal Use Only Page 37