20240909IPC to Staff 95(e) - Attachment 4 - MLPR200001 Unit 1 Commissioning MLPR1 - Startup_FCR_AVR Commissioning Guide_R1.pdf
4411#4 U-1 P%mER. Milner Power Plant U1 Auto Voltage Regulator (AVR) Commissioning Guide Nicholas McGhie Senior Engineer Power Production Electrical Engineering Group Initial Controller Settings and AVR Operational Commissioning Procedure 2024 © 2024 Idaho Power Idaho Power Company Abbreviated Title Review/Revision History This document has been approved and revised according to the revision history recorded below. Review Date Revisions 02/01/2024 Document was implemented. Table of Contents Review/Revision History...................................................................................................................i Tableof Contents..............................................................................................................................i Listof Tables ...................................................................................................................................iii Listof Figures..................................................................................................................................iii Listof Appendices...........................................................................................................................iv 1 Preparations.............................................................................................................................. 1 1.1 Project Information.......................................................................................................... 1 1.2 Field Measurements ........................................................................................................ 1 1.3 Equipment Verification .................................................................................................... 1 2 Controls Checkout..................................................................................................................... 2 3 SCADA List................................................................................................................................. 2 4 Initial Settings............................................................................................................................ 2 4.1 Configure............................................................................................................................. 2 1.1.1 Controller Logic Load ................................................................................................. 2 1.1.2 Rated Data ................................................................................................................. 2 1.1.3 Options....................................................................................................................... 3 1.1.4 Auxiliary Inputs .......................................................................................................... 3 1.1.5 Meter Drivers............................................................................................................. 4 Internal Use Only Idaho Power Company Abbreviated Title 1.1.6 System Data ............................................................................................................... 4 1.1.7 Transient Boost.......................................................................................................... 5 1.2 Settings................................................................................................................................ 5 1.2.1 AVR/FCR/FVR............................................................................................................. 5 1.2.2 VAR/PF ....................................................................................................................... 6 1.2.3 Startup ....................................................................................................................... 7 1.3 Gain..................................................................................................................................... 7 1.3.1 AVR Gains (Primary)................................................................................................... 7 1.3.2 AVR Gains (Secondary)............................................................................................... 7 1.3.3 FCR Gains ................................................................................................................... 8 1.3.4 FVR Gains ................................................................................................................... 8 1.3.5 Other Gains................................................................................................................ 8 1.4 Limiting................................................................................................................................ 9 1.4.1 Configuration ............................................................................................................. 9 1.4.2 Summing Point OEL (Primary).................................................................................. 10 1.4.3 Summing Point OEL (Secondary) ............................................................................. 10 1.4.4 UEL (Primary) ........................................................................................................... 11 1.4.5 UEL (Secondary)....................................................................................................... 11 1.4.6 Takeover OEL ........................................................................................................... 11 1.4.7 SCL (Primary & Secondary) ...................................................................................... 11 1.4.8 VARL (Primary & Secondary).................................................................................... 11 1.4.9 Scaling (Primary & Secondary)................................................................................. 11 1.5 Protection ......................................................................................................................... 12 1.5.1 General Protection (Primary)................................................................................... 12 1.5.2 General Protection (Secondary) .............................................................................. 12 1.5.3 24 Voltz/Hz............................................................................................................... 12 1.5.4 Loss of Sensing......................................................................................................... 12 Internal Use Only Page ii Idaho Power Company Abbreviated Title 1.5.5 EDM.......................................................................................................................... 13 1.5.6 Relay Setup .............................................................................................................. 13 1.6 Data Log ............................................................................................................................ 14 1.6.1 Log Setup (Initial) ..................................................................................................... 14 1.6.2 Mode Trigger............................................................................................................ 14 1.6.3 Log Selection............................................................................................................ 14 1.6.4 Mode Triggers.......................................................................................................... 15 1.6.5 Level Triggers........................................................................................................... 15 1.6.6 Logic Triggers ........................................................................................................... 15 5 Commissioning........................................................................................................................ 17 5.1 Operations Loading Summary........................................................................................ 17 5.2 Final Data Acquisition Summary.................................................................................... 18 List of Tables Table ? Enter the table number above its caption and apply the "Caption Table No" style. Enter the caption for the table below its number and apply the "Caption Table" style. Update (right click > Update Field) the List of Tables after all table captions have been added .............................................................................................Error! Bookmark not defined. List of Figures Figure ? Enter the figure number above its caption and apply the "Caption Figure No" style. Enter the caption for the figure below its number and apply the "Caption Figure" style. Update (right click > Update Field) the List of Figures after all figure captions have been added............................................................................Error! Bookmark not defined. Internal Use Only Idaho Power Company Abbreviated Title List of Appendices Appendix ? Enter the appendix number above its caption and apply the "Caption Appendix No" style. Enter the caption for the appendix below its number and apply the "Caption Appendix" style. Update (right click > Update Field) the List of Appendices after all appendix captions have been added.............................................Error! Bookmark not defined. Internal Use Only Page iv Idaho Power Abbreviated Title 1 Preparations 1.1 Project Information • Project Server Location: \\FresnoPowerProduction\Plants_Hydro\17 MLPR Milner\Projects\2020-MLPR12- AVR Upgrade - MLPR200001\Engineering-Commissioning\Unit 1 • Modeling Server Location: \\Fresno\powerproducton\Plants_Hydro\17 MLPR Milner\Condition Assessment and Info\NERC MOD\2023-MLPRI-MOD026 1.2 Field Measurements 1.2.1 ❑ Micro-Ohm Resistance Test, Value: MC) @ 200C a. Original Value is 0.6740 @ 25°C b. Manufacture Value is 0.6740 @ 25°C 1.2.2 ❑ Review Final Rotor IR Test Report, Value: Mfg (Including Slip Rings, Initial Maintenance Record 1.2.3 ❑ Complete final field measurements forms and save to SharePoint Site Plant Condition Assessment Library- All Documents 1.3 Equipment Verification 1.3.1 ❑ Verify Unit Style Number: DECS-400-1-C-5-U 1.1.1..1 1 = PSS 1.1.1..2 C = 125V (ac or dc) 1.1.1.3 5 = 5A CT Secondary 1.1.1..4 U = Battery Backup for real-time clock. Internal Use Only Page 1 Idaho Power Abbreviated Title 2 Controls Checkout 3 SCADA List 4 Initial Settings 4.1 Configure If the unit has a PSS it must be disabled. Reference the PSS Commissioning guide. 4.1.1 Controller Logic Load 1. ❑X Load logic into controller for single DECS with PSS. (Load with Initial Settings) 4.1.2 Rated Data 4c. e=0-��a� Menufac_u:1e= 495000 kVA Pover :ec_cr C 4oA. s=ee: ZCO RPM 2 e 0 0 7-7- V Duty speed 540 RPM 2C50 A stator v:nc-4 nc: :ner__a _ansr. 2. 5i kWs/kVA cznnec_:cn of Hz =xc:t=t:on !sC A �J V 03 Phases Insulac_cr, class statorif_ele vcg. 31recc:cn of rc:at:cn seen . . ca s: _ _ng side y---7-71 Tenoerevure r_se above cold FAiR i:n stsccr vinc:zg: 5C <. '_n . _el�'. vind'ng 60 K Internal Use Only Page 2 Idaho Power Abbreviated Title C. Calculated resistances Generator Field at 25 Degrees Celsius 0 . 674 Generator Armature at 25 Degrees Celsius 0 . 003 (p.u. ) Negative Sequence Resistance 0 . 016 (p.u. ) 4.1.3 Options Setting Comments Voltage Sensing ABC 3-Phase Per 281301A, All phases normal rotation. Field Type Main Field Static Exciter Bridge Control Signal -10V-> +10V Standard Temperature Mode DEG. C Standard Underfrequency Mode V/Hz Standard Current Sensing Three Per 281101.dwg C I Selection A-B Generator Frequency 60 Nameplate Voltage Matching Disabled At Startup, will enable during commissioning later. Internal Tracking Enabled Standard on single DECS to track between FCR and AVR modes. External Tracking Disabled ?d for Dual DECS designs. Inner Loop Field Regulator Disabled 4.1.4 Auxiliary Inputs Setting Comments Input Type Voltage Summing Type Inner Loop Internal Use Only Page 3 Idaho Power Abbreviated Title ��+ i��,.+ /DC'C'1�� in+„�� The Input Function Remote Setpoint met is "r Aux is not used. Aux Gain Settings Only used if using Aux control. AVR (�^ FVR (Mode) Gain VAR (Mode) Gain PF (Mode) Gain Droop Compensation Enabled, 5% This is for parallel generators, otherwise Disabled. Line Droop Compensation Disabled, 0% Cross Current Compensation Disabled, 0% 4.1.5 Meter Drivers Setting Comments Meter Driver 1 Disabled No devices connected per281301A. System Parameter Metered ... Minimum Value ... Maximum Value ... Meter Driver 1 Disabled No devices connected per281301A. System Parameter Metered ... Minimum Value Maximum Value ... 4.1.6 System Data Setting Comments Internal Use Only Page 4 Idaho Power Abbreviated Title Gen PT: Primary Voltage 14,400 Per281101 Gen PT: Secondary Voltage 120 Per281101 Gen CT: Primary Current 3000 Per281101 Gen CT: Secondary Current 5 Per 281101 Per 281105/281107. This will be Bus PT: Primary Voltage 14560 verified prior to synchronizing with relays. Bus PT: Secondary Voltage 120 Per281105/281107 Internal Tracking Delay 1.0 Standard Internal Tracking Transvers Rate 3.0 Standard(2.0 is also used) External I racking (Secondary) Not Used,for Dual Decs. ' T r Not Used,for Dual Decs Field Current Sensing: Shunt 800 Per281301A Field Voltage Isolation Transducer 375 Per281301A 4.1.7 Transient Boost Setting Comments Transient Excitation Boosting Disabled Not used for IPCo. 4.2 Settings 4.2.1 AVR/FCR/FVR Setting Comments AVR Setpoint 13,800 Min % (Rated) 95.0 Standard is 0.95, Verify with TO. Max% (Rated) 105.0 Per nameplate Internal Use Only Page 5 Idaho Power Abbreviated Title Transverse Rate 30 Standard 30. AVR Pre-Position 1 Setpoint 13,800 This brings it up to rated. Mode Release Transverse Rate/Enable Disabled Some as above if disabled. AVR Pre-Position 2 Setpoint 13,800 Mode Release Transverse Rate/Enable Disabled Some as above if disabled. FCR 20% of Rated Field Current to start. Setpoint (270) (450A x 20%=90A) SNL (2017) = -270A (V-curve, online) Min % (Rated) 20.00 Initial Setting for startup. (90A) Max % (Rated) 105.0 Standard 105.0 but may be adjusted later. Transverse Rate 120 60-200 been used. Standard 120. FCR Pre-Position 1 Setpoint 90 Initial Setting for startup Mode Release Transverse Rate/Enable Disabled FCR Pre-Position 2 Setpoint 90 Initial Setting for startup Mode Release Transverse Rate/Enable Disabled 4.2.2 VAR/PF Not Used Internal Use Only Page 6 Idaho Power Abbreviated Title 4.2.3 Startup Setting Comments Primary Soft Start Level 25 Standard 25. Primary Soft Start Time 15 Standard 15. Secondary Soft Start Level Not Used(Make some as primary) Secondary Soft Start Time Not Used(make Same as primary) Field Flash Dropout Level 50 Standard 50. Maximum Field Flash Time 10 Standard 10. (up to 25) Voltage Matching Band 10.00 Standard 10.0 Voltage Matching (Gen-Bus PT) 100.2 Plant, unit specific. Volts/Hz High Limiter 1.08 Standard 1.08 Volts/Hz Low Limiter 1.06 Standard 1.06 Volts/Hz Time Limiter 10.0 Standard 10.0 4.3 Gain 4.3.1 AVR Gains (Primary) Setting Comments Kp— Proportional Gain 80.0 default 80. Ki — Integral Gain 20.0 default 20. Kd — Integral Gain default 40. (Rotating Exciters) Td — Integral Gain default 0.01 Kg—AVR Loop Gain 15.0 default 15. 4.3.2 AVR Gains (Secondary) Make these the same as the primary. Secondary is not used in controller, but just in case making them the same as the primary ensures the same control between them. Internal Use Only Page 7 Idaho Power Abbreviated Title Setting Comments Kp— Proportional Gain 80.0 Existing, default 80. Ki — Integral Gain 20.0 Existing, default 20. — Integral Gain 90.0 Existing, default 4U. (Kotating txciter) Td — Integral Gain 0.01 Existing, default 0.01 Kg—AVR Loop Gain 15.0 Existing, default 15. 4.3.3 FCR Gains Setting Comments Kp— Proportional Gain default 0. Ki — Integral Gain default 0. Kd — Integral Gain default 0. (Rotating Exciter) i------I r--,;- 14- n Kg—AVR Loop Gain 1000 default 1000. 4.3.4 FVR Gains Not Used. 4.3.5 Other Gains Setting Comments VAR Not used Ki — Integral Gair 1.0 Kg— 1 0.0 PF Not Used Ki — Integrz 1.0 Kg— Loop Gain 0.0 Internal Use Only Page 8 Idaho Power Abbreviated Title OEL Ki — Integral Gain 1.0 Standard 1.0-15.0 Kg— Loop Gain 20.0 Standard 2.0-35.0 UEL Ki — Integral Gain 1.0 Standard 1.0 Kg— Loop Gain 20.0 Standard 2.0-20.0 SCL Not Used Ki — Integral Gain 1.0 — Lr- - 0.0 Voltage Matching Kg— Loop Gain 2.0 Standard 1.0-3.0 When inner loop selected in the Inner Loop Field Regulator Settings/Auxiliary Input/Summing Type, then this gain is enabled. Ki— Inner Loop 0.0 Standard. 0.0 Kg— Inner Loop 1.0 Standard. 1.0 VARL Not used? Ki — Integral Gain 1.0 Kg— Loop Gain 0.0 4.4 Limiting 4.4.1 Configuration Setting Comments Limiter Modes OEL Enable Standard. UEL Disable UEL will be enabled in commissioning later. SCL Disable VARL Disable Internal Use Only Page 9 Idaho Power Abbreviated Title OEL Mode Summing Point Standard OEL Voltage Dependency Disabled dv/dt Level Disabled This is enabled by enabling the voltage dependency. UEL Mode Summing Point Standard UEL Voltage Dependency Real Power Exponent 0.0 Typically, 0.0, but also 1.0 can be used. Real Power Filter Time 5.0 Typically, 5.0 Constant 4.4.2 Summing Point OEL (Primary) Setting Comments Offline See IEEE C50.13 standard/PRC-019 Review Saturation curve Initial Set at 105%rated gen volt. High Level 311 270A x 1.15=311A Estimated 318A Field=1.05pu Gen Volt High Time 2 Standard. Initial Set at 10% above rated gen volt. Low Level 297 270A x 1.10=308A May need to be adjusted later. On-Line See IEEE C50.13 standard/PRC-019 Update final values with PRC-019 Coord. High Level 630 Initial set at 140%above rated field Amp High Time 3 Initial set at 3.Os Medium Level 563 Initial set at 125%above rated field Amp Medium Time 10 Initial set at 10.Os Low Level 518 Initial Set at 115% above rated field Amp 4.4.3 Summing Point OEL (Secondary) Not Used, set same as Primary. Internal Use Only Page 10 Idaho Power Abbreviated Title 4.4.4 UEL (Primary) This controller function needs to be coordinated with PRC-019. Setting Comments Primary UEL Curve Selection Internal Point Selection 5 Points 1: Real Power/ Reactive Power 0/ 39.69k Per PRC-019 Points 2: Real Power/ Reactive Power 36k/32k Per PRC-019 Points 3: Real Power/ Reactive Power 40k/ 28.5k Per PRC-019 Points 4: Real Power/ Reactive Power 44k/ 22k Per PRC-019 Points 5: Real Power/ Reactive Power 15.2k/0 Per PRC-019 4.4.5 UEL (Secondary) Not used, same as Primary. 4.4.6 Takeover OEL Not Used. 4.4.7 SCL (Primary& Secondary) Not Used. 4.4.8 VARL (Primary& Secondary) Not Used. 4.4.9 Scaling (Primary& Secondary) Not Used. Internal Use Only Page 11 Idaho Power Abbreviated Title 4.5 Protection 4.5.1 General Protection (Primary) In general, the excitation controller unit protection functions are not used. The unit protection is served by a separate relay protection system. Typically alarms and tripping from this controller would be internal only to the excitation system. Setting Comments Generator Overvoltage Disable Standard Field Overvoltage Disable Standard Loss of Field Iso. Transducer Enable Standard Delay 1.0 Standard Generator Undervoltage Disable Standard Field Overcurrent Disable Standard. Power Supply Low Enable Standard(Mixed depending on site upon review) Loss of Field Disable Standard Field Over Temperature Enable Standard Pickup Level 130 Typical130 Delay 60 Typical60 4.5.2 General Protection (Secondary) Same as Primary. 4.5.3 24 Voltz/Hz Disabled. 4.5.4 Loss of Sensing Setting Comments Option Enable Standard Balanced Level 50.0 default Internal Use Only Page 12 Idaho Power Abbreviated Title Unbalanced Level 20.0 default Delay 2.0 default Transfer to Manual Enable Standard 4.5.5 EDM Not Used. 4.5.6 Relay Setup Setting Comments Relay#1 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#2 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#3 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#4 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default Relay#5 Contact Status Normally Open default Contact Type Maintained default Internal Use Only Page 13 Idaho Power Abbreviated Title Momentary Time 0.10 default Relay#6 Contact Status Normally Open default Contact Type Maintained default Momentary Time 0.10 default 4.6 Data Log 4.6.1 Log Setup (Initial) Setting Comments Data Logging Enabled Enable This sets up for the first energization data capture for 30.Os. Pre-Trigger Points 25 Sample Interval 49.992 4.6.2 Mode Trigger Setting Comments Start/Stop Mode Start Limiter Mode UEL & OEL Test Mode Enabled All other triggers not identified are not used. 4.6.3 Log Selection Setting Comments Parameter 1 Generator Average Voltage Parameter 2 Field Voltage Parameter 3 Field Current Parameter 4 Generator Real Power Could use different signal. Internal Use Only Page 14 Idaho Power Abbreviated Title Parameter 5 Field Temperture Parameter 6 Control Output 4.6.4 Mode Triggers Setting Comments Start/Stop Mode Start Capture Start-ups Soft Start Mode NO TRIGGER Underfrequency Mode NO TRIGGER Control Mode NO TRIGGER Operating Mode NO TRIGGER Limiter Mode NO TRIGGER Voltage Matching Mode NO TRIGGER Sec. DECS Mode NO TRIGGER PSS Controller Mode NO TRIGGER Manual Mode NO TRIGGER Droop Mode NO TRIGGER Line Drop Mode NO TRIGGER Cross Current Comp. Mode NO TRIGGER Test Mode Enable Needed for testing 4.6.5 Level Triggers No triggers are enabled. 4.6.6 Logic Triggers Setting Comments Alarm States None enabled Relay Outputs Enabled Watchdog Internal Use Only Page 15 Idaho Power Abbreviated Title Enable Relay Output 2 Contact Inputs FCR (Manual) Internal Use Only Page 16 Idaho Power Abbreviated Title 5 Commissioning 5.1 Operations Loading Summary Review the PSS Commissioning Guide, and MOD-026/VAR-501 Data Collection Guides. Table 1. Loading Summary for AVR Commissioning Section Test Loading Flow Unit Control Schedule 5.2.1 Initial Field Energization Offline, Rated Speed Manual 5.2.2 FCR Voltage Response Offline, Rated Speed Manual Day 1 5.2.3,4 AVR Voltage Response Offline, Rated Speed Manual 5.2.5 Offline OEL Response Offline, Rated Speed Manual Offline, Rated Speed 5.2.6,7 Soft Start/Voltage Matching Online SNL Manual Offline, Rated Speed 5.3.2 Synchronizing Manual Online SNL 5.3.3 AVR Voltage Response 10MW,2%Variable Vars Manual Day 2 FCR Voltage Response 10MW,2%Variable Vars _ Manual OEL,UEL Limits(AVR/FCR Gains) 10MW,Variable Vars _ Manual 5.3.4 AVR Voltage Response 40MW,2%Variable Vars _ Manual FCR Voltage Response 40MW,2%Variable Vars _ Manual PSS Tuning 15MW,Unity _ Manual PSS Voltage Response 15MW,2%Vars _ Manual OEL,UEL Limits(PSS Gains) 15MW,2%Vars _ Manual 5.3.8 PSS Voltage Response and Stability 35MW,2,5%Variable Vars Manual 1MW/Unity,±9.8MVar Day 3 9.8MW/Unity,±9.8MVar 19.6MW/Unity,±9.8MVar 5.4 V-Curve Validation — Manual 29AMW/Unity,±9.8MVar 39.2MW/Unity,±2.5MVar 44.1MW/Unity,±2.5MVar *No saturation test is to be performed. Manufactures saturation information will be utilized for modeling and verification. Internal Use Only Page 17 Idaho Power Abbreviated Title 5.2 Final Data Acquisition Summary Table 2. Summary of Data Acquisition Step Time Step Pre-Trigger Sample Section Test/Re Method' Magnitude' Delay' Duration' Points3 Interva13 5.2.1 Initial Field Energization Start Mode 25 49.992s Trigger 5.2.2 Offline FCR Voltage Response Manual Step _ 60 16.664ms Response 5.2.3,4 Offline AVR Voltage Response Time Response 2.0% 0.5s 9.Os 25 16.664ms 5.2.5 Offline OEL Response Time Response 2.0% 0.5s 30.Os 0 49.996ms 5.2.6,7 Auto Soft Start/Voltage Start Mode _ 25 49.992s Matching Trigger 5.3.2 Auto Synchronizing Logic Trigger - - - 300 49.992s Input Switch 32 5.3.3 Online AVR Voltage Response Time Response 2.0% 0.5s 9.Os 0 24.996ms (Light Load) Online AVR Voltage Response (Heavy Load) Time Response 2.0% 0.5s 9.Os 0 24.996ms Online FCR Voltage Response Manual Step 5.3.4 20 24.996ms (Light Load) Response - Online FCR Voltage Response Manual Step 20 24.996ms (Heavy Load) Response - 5.3.5,6 OEL Limits-Control Response Time Response 2-5.0% 0.5s 30.Os 0 49.996ms XX UEL Limits-Control Response Time Response 2-5.0% 0.5s 30.Os 0 49.996ms 5.3.7 5C)Voltage Response(Stability Time Response 5.0% 0.5s 9.Os 0 24.996ms 5.3.8 5V)Voltage Response(Stability Time Response 5.0% 0.5s 9.Os 0 24.996ms 5.4 V-Curve Validation Manual/Operator - - Note 1. Selected within the DECS-400 Analysis Time Response Menu. 2. Input switch 3 is the generator breaker closure input. 3. Selected within the DECS-400 Log Setup Menu. 4. Response method or DECS logic operator in Analysis menu Internal Use Only Page 18