Loading...
HomeMy WebLinkAbout20240909IPC to Staff HCPR_AUTOSPILL_GATE_3_COMMISSIONOING PLC_EMERGENCY_FLOAT_EMERGENCY_COMMISSIONING.pdf EMERGENCY AUTOSPILL PLC INPUTS 1. PULL RELAY'S FROM BOP PLC DROP 1 TO OLD AUTOSPILL PLC 2. USE A SEPARATE ANALOG INPUT ON DROP 9 FOR HH HEADWATER 3. REMOVE HH HEADWATER POINT AND INSERT NEW TEST POINT FROM ANALOG INPUT 4. MOVE PROCESS CALIBRATOR TO SIMULATE HH HEADWATER ANALOG POINT 5. VERIFY SPILLGATE MOVES TO 3.3 FT, 5600 CFS 6. MOVE PROCESS CALIBRATOR TO SIMULATE AN EXTREME HIGH HEADWATER ANALOG POINT 7. VERIFY SPILLGATE MOVES AN ADDITIONAL— 2 FT, 3000 CFS 8. TOTAL 5.2 FT, 8500 CFS 9. TEST 1 SETUP — UNIT TRIP WITH HH HEADWATER a. MS RELAY HIGH b. 94G RELAY LOW c. UNIT TRIP RELAY LOW d. UNIT CFS 12mA, 5075 CFS 10.TEST 1 a. UNIT TRIP RELAY FROM LOW TO HIGH b. MS RELAY FROM HIGH TO LOW c. VERIFY CFS MOVE — 5075 + 8500 CFS = 13594 CFS d. VERIFY GATE MOVE — 8.2 FT 11.MOVE PROCESS CALIBRATOR TO PROPER HEADWATER LEVEL 12.MOVE GATE TO 0 POSITION 13.SWITCH ANALOG POINTS FROM HEADWATER TO TAILWATER 14.MOVE PROCESS CALIBRATOR TO SIMULATE LL TAILWATER ANALOG POINT 15.VERIFY SPILLGATE MOVES TO 3.3 FT, 5600 CFS 16.TEST 2 SETUP — UNIT TRIP WITH LL TAILWATER a. MS RELAY HIGH b. 94G RELAY LOW c. UNIT TRIP RELAY LOW d. UNIT CFS 12 mA, 5075 CFS 17.TEST 2 a. UNIT TRIP RELAY FROM LOW TO HIGH b. MS RELAY FROM HIGH TO LOW c. VERIFY CFS MOVE — 5075 + 5600 = 10675 CFS d. VERIFY GATE MOVE — 3.5 + 3.5 = 7 FT 18.MOVE PROCESS CALIBRATOR TO SIMULATE NORMAL TAILWATER 19.TURN LL TAILWATER BYPASS SWITCH TO BYPASS LL TAILWATER 20.MOVE PROCESS CALIBRATOR TO SIMULATE LL TAILWATER ANALOG POINT 21.VERIFY SWITCH DISABLES LL TAILWATER PLC SPILL 22.MOVE PROCESS CAIBRATOR TO SIMULATE NORMAL TAILWATER LEVEL 23.REMOVE TEST EQUIPMENT 24.LEAVE AUTOSPILL RELAY'S ON BOP DROP 1 DISABLED EMERGENCY AUTOSPILL HARD WIRED RELAY'S 1. 1/0 CHECKOUT FOR EMERGENCY AUTOSPILL HARD WIRED RELAY'S 2. MEASURE RESISTANCE ON THE EMERGENCY AUTOSPILL CIRCUIT 3. CLOSE BREAKER 4. SET GATE RAISE TIMER TO 2 MINUTES 5. SET DRIVE TIMER TO 2 MINUTES —VERIFY TIMER MODE AND TIME 6. SET SIREN TIMER FOR 1 MINUTE 7. JUMP HH HEADWATER SWITCH 8. VERIFY GATE RAISES FOR 2 MINUTES 9. VERIFY DRIVE TIMER TIMES FOR 2 MINUTES 10.VERIFY GATE RAISES FOR ANOTHER 2 MINUTES 11.REMOVE JUMPER 12.PLACE SPILLGATE 1 IN AUTO AND LOWER GATE TO 0 POSITION 13.PLACE SPILLGATE 1 IN OFF TO SIMULATE A PLC FAILURE 14.PLACE JUMPER ON LL TAILWATER SWITCH 15.VERIFY SIREN TIMES FOR 1 MINUTE 16.VERIFY GATE RAISES FOR 2 MINUTES 17.VERIFY DRIVE TIMER TIMES FOR 2 MINUTES 18.VERIFY GATE RAISES FOR ANOTHER 2 MINUTES 19.REMOVE JUMPER 20.VERIFY TIMER LOGIC STOPS TIMING 21.PLACE EMERGENCY SPILL DISABLE SWITCH TO DISABLE 22.INSTALLJUMPER ON LL TAILWATER SWITCH 23.VERIFY LL TAILWATER EMERGENCY SPILL DOES NOT OPERATE 24.REMOVE JUMPER 25.RESTORE EMERGENCY SPILL SWITCH TO NORMAL 26.PLACE SPILLGATE 1 IN AUTO AND LOWER GATE TO 0 POSITION 27.CHANGE DRIVE TIMER TO 45 MINUTES 28.VERIFY GATE TIMER IS AT 2 MINUTES 29.VERIFY SIREN TIMER IS AT 1 MINUTE 30.PLACE SPILLGATE SELECTOR SWITCH TO SPILLGATE 2 31.JUMP LL TAILWATER TO VERIFY SPILLGATE 2 RELAY ENERGIZES AND DOES NOT MOVE SPILLGATE 1 32.PLACE SPILLGATE SELECTOR SWITCH TO SPILLGATE 3 33.JUMP LL TAILWATER TO VERIFY SPILLGATE 3 RELAY ENERGIZES AND DOES NOT MOVE SPILLGATE 1 34.PLACE SPILLGATE SELECTOR SWITCH TO SPILLGATE 1 DEREK VANDERMEER 5/27/2024