HomeMy WebLinkAboutI202007 LOC Response i'v td
EXECUTIVE OFFICES
INTERMOUNTAIN GAS COMPANY w 14 9_ 2
555 SOUTH COLE ROAD-P.O.BOX 7608• BOISE,IDAHO 83707• (208)377-6000• FAX:377-6097
October 9,2020
Mr.Darrin Ulmer,Programs Manager
Idaho Public Utility Commission
PO Box 83720
Boise,ID 83720-0074
Subject:Response to Letter of Concern dated September 14,2020(Report# 1202007)
Dear Mr.Ulmer,
This letter is intended to address one area of concern stemming from an onsite specialized field inspection in
Intermountain Gas Company's(IGC)Idaho Falls District conducted August 31—September 2,2020. Specifically,
we are addressing how we have brought the area of concern into full compliance.
AREA(S) OF CONCERN
1. Cascade Natural Gas Corporation-OPS 703 (Sec 8), 8.1.5-reads: If a plug is not adequately
lubricated, apply valve sealant. (Inability to operate without significant force is an indication of
inadequate lubrication.)Refer to section 6.
Emergency Valve 700 0226 is not able to be operated without significant force(takes 2 personnel to
operate).
Intermountain Gas Response
IGC acknowledges the findings brought forth by the IPUC stated above. On September 25, 2020, Idaho Falls
Valve 48747-VLV-29560 (Legacy ID 700-0226) was flushed, re-lubricated, and confirmed to be operational
by IGC field personnel. (See Figure 1.)
Additionally, as the 2020 valve inspection and maintenance near a close, the Director of Operations Services
will send a Compliance Message to MDU Utilities Group employees prior to the start of 2021 valve inspection
and maintenance.The purpose of the Compliance Message will be to remind employees of the requirements of
OPS 703— Valve Inspection and Maintenance and the importance of proper documentation to ensure that the
applicable follow-up orders are generated in Compliance Tracking Software when valves do not turn without
significant force.
Please contact Josh Sanders at(701)222-7773 with questions or comments.
Respectfully Submitted,
Pat Darras
Vice President,Engineering&Operations Services
Intermountain Gas Company
EXECUTIVE OFFICES
INTERMOUNTAIN GAS COMPANY
555 SOUTH COLE ROAD-P.O.BOX 7608- BOISE,IDAHO 83707-(208)377-6000-FAX:377-6097
Figure 1
PCAD Job ID: MDUG-20200925-21603
FA ID:8023281495
ATTN-.tW r SAXTCN MAINTENANCE ON VALVE s'700 01M INSf 11
E� r_ rnlC 737EMCIN '
Y to l
23240775 1502328155
&423d815i 5'iAkVf I UCON 4fr-25 2024MOO USfMour°tai, SA%T17N �ftEARE6
Ji_CC.J. Plrmi!.r numv valve trvf f MAMI7,vn,rked.'.'ar'e.VGtve is_esi&.J tum ard is
OPERATONAL i
"i"ea
Order Summary
PCADJOCIt7 141DUG-20200925.21603 FA ID 18023281495 SeNicecode G-VALVE
i»u5iamer
Address I Virtual Premise.UCON Attachmer'M 0
Action Taken
Compiered Veler Anon M CGI Reason Material c*ULBble VVoW
Existing PAeter/ERT Information
,*ter N,mber Correct h'tr Na? tc rested"Air ha 41scenn tt:caaticn Gnve Rate index.Real
Or,Number Caned ERT No, Corrected ERT tao. C>'-b'ery prexs:;re GrT.'e Rate Pound ERT fiend
Additional Order information
Date Work Performea eypassable Meter Set Pipe Conditran Qcorana Percept,bbe Conxpany Pei,gnt' Lock up-Found L;,=k up-Leff
Comments
flushed valve and GREASED, norked valve. Valve is easier to C!`titeRE,,evr' PRvevRea•"
turn end is OPERATIONAL
-"::eSYEr v